background image

H E A T   I N T E R F A C E   U N I T  

C O M M I S S I O N I N G

Page 22

H E A T   I N T E R F A C E   U N I T  

C O M M I S S I O N I N G    

Page 23

CAUTION

The actuators on the valves must not be  

dismantled during operation. This could result in 

them being destroyed. Dismantling should only 

be carried out when the HIU is isolated from all 

systems (mechanical and electrical) and when 

the system has cooled down. 

 

Remove end caps and fit flexible hose between  

    both valves

 

The secondary HTG circuit pressure should be   

    typically between 1.0 and 1.5bar, the secondary   
    HTG system pressure may be read from the    
    pressure gauge at the front of the HIU

 

Open the secondary HTG valve first and then         

    open the MCW valve until the desired pressure  
    has been achieved

 

Vent system radiators of all air, top up pressure  

    after each radiator has been vented

 

When the system has been fully vented, and    

    the desired pressure has been achieved, turn    
    off both valves identified in Fig 15

 

Remove hose and replace end caps tightly  

    

    (always disconnect the filling hose following    
    use)

 

Check HIU for leaking joints on the secondary       

    HTG connections, tighten connections as  

 

    required. Do not overtighten the fibre washers  
    as this will result in damage. Should a fibre 

 

    washer become damaged, replace the washer  
    immediately ensuring to isolate the HIU  

 

    mechanically and electrically first

 

Connect the power cable to the pump (Fig 16).  

    This cable is removed on purpose to avoid the   
    pump operating with no water in the system.    
    To access the pump, move the HIU controller    
    out of the way

Fig. 16

 

Once all radiators have been vented, system is at  

    desired pressure and no leaks are evident, move  
    to the next step identified in 8.2.3

  8.2.3 Filling the Primary System

 Only fill the primary system when both  

 

    secondary side circuits have been filled as  

 

    identified in 8.2.1 and 8.2.2

 Open the primary system isolation valves at the  

    top of the HIU. Always open the flow valve first       
    to prevent debris entering the HIU

 Check HIU for leaking joints on the primary        

    connections, tighten connections as required.       
    Do not overtighten the fibre washers as this will   
    result in damage. Should a fibre washer become  
    damaged, replace the washer immediately  

 

    ensuring to isolate the HIU mechanically and    
    electrically first

8.3 Finalising the HIU Installation 

 All joints within the HIU and the final connections  

    to the HIU are water tight

 All DHW outlets have been flushed through to  

    remove air and debris

 All radiators have been vented

 Confirm safety relief valve (SRV) has been  

 

    connected to drain. Test SRV in line with  

 

    manufacturer’s instructions to ensure valve is    
    operating correctly

WARNING

The safety relief valve is a factory set unit, do 
not tamper with the valve. Should the valve not 
function when tested or pass water, the valve must 
be replaced.

 Check all electrical connections are in good    

    condition and are connected correctly

 Confirm all wiring has been completed (power  

    supply, room stat & programmer) in accordance  
    with wiring regulations and the HIU has a safe   
    means of isolating the power supply

8.4 Final Commissioning

 Complete correct commissioning form; address,  

    date, commissioning engineer, HIU details, heat  
    meter details, confirm any flushing bypass is    
    closed on the primary connections

 Check primary flow temperature is within 5°C of  

    design set point via the heat meter. If not, wait to  
    allow hot water to reach HIU

  8.4.1 DHW and Keep Warm Control Valve    
           Adjustment

DHW and keep warm control is provided by Danfoss 
AB-QM PICVs. During the commissioning process 
the flow rate will need to be checked and adjusted. 
See Fig 17 opposite which identifies the location of

(A) DHW PICV and (B) Keep warm PICV.

Fig. 17

 

Fig. 18

A

B

Before undertaking any of the steps below, close 
primary system isolation valves at the top of the 
HIU and confirm electrical connection is isolated.

Lift the grey adjustment pointer above the setting 
grooves (Fig 19). Located on the adjustment 
pointer is a red line which is the index for the 
adjustment.

Remove thermostatic actuator by loosening the 
brass collar (Fig 18).

Fig. 19

Rotate the pointer to the required flow percentage. 
Clockwise to decrease the setting percentage, 
counter-clockwise to increase the setting 
percentage (Fig 20).

Fig. 20

Summary of Contents for vThermt

Page 1: ...Installation Commissioning and Maintenance Manual Version No 002 Always keep the instructions close to the HIU and read the operating instructions carefully before starting any work...

Page 2: ...ydraulic separation between the primary circuit and the secondary DHW and HTG installations The HIU is thermostatically controlled to give good and reliable control of temperature which improves effic...

Page 3: ...g safely and take extreme care DANGER Electrical hazard Failure to follow safety procedures can result in severe injury or death This work may only be performed by a trained electrician CAUTION Risk o...

Page 4: ...ures based on the manufacturer literature DANGER Electricity can cause serious and fatal injuries Always isolate the electrical supply and test before commencing work Before undertaking any work on th...

Page 5: ...nstalled in the outlet of the HTG plate A manometer and thermometer are installed on the heating flow pipework within the HIU This is visible through the front cover of the HIU This gauge displays the...

Page 6: ...AISI 316L Cu Brazing Insulation Expanded Polypropylene Some other materials are used by component manufacturers such as valves and pumps These are in sealing shafts and other small components of the a...

Page 7: ...HIU must only be installed in a suitable location that provides protection against moisture and freezing temperatures The location must have sufficient ventilation to prevent heat build up within the...

Page 8: ...s Step 4 Fit the frame to the wall Step 5 Slide the insulation back onto the valve rail backplate Step 6 Replace all valves Step 7 Fit tighten the nuts and bolts 2 x A and 1 x B so they are secure in...

Page 9: ...alve 8 Heating Heat Exchanger 9 Heating Actuator 10 Heating Control Valve 11 Heat Meter Flow Sensor 12 Pump 13 Junction Box 14 Check Valve 15 Mini Expansion Vessel 16 Expansion Vessel REF COMPONENT 17...

Page 10: ...ion box Before adding power to the unit verify that no electrical connections have been disconnected on the components All accessories and main power supply will be connected in the junction box housi...

Page 11: ...sink tap until a cold clean steady flow of water is achieved Open each DHW outlet within the property until all air and any remaining debris has been flushed through Check HIU for leaking joints on t...

Page 12: ...connections tighten connections as required Do not overtighten the fibre washers as this will result in damage Should a fibre washer become damaged replace the washer immediately ensuring to isolate...

Page 13: ...below which identifies the location of the heating PICV Before undertaking any of the steps below close primary system isolation valves at the top of the HIU and confirm electrical connection is isola...

Page 14: ...or three minutes Complete the Heating section of the Commissioning sheet whilst the HTG is on Switch the HTG off at the room thermostat and isolate the HIU at the fused spur Close the secondary HTG is...

Page 15: ...t be removed after filling Every 2 years Bypass If present check that the flushing bypass valve is closed Every 2 years Pump Check pump setting is Proportional Pressure Auto Adapt Every 2 years HTG Co...

Page 16: ...cted correctly if connected correctly and flow temperature is low consult network operator 10 Plate heat exchanger is blocked Remove PHE clean and re install or replace if necessary FAULT POSSIBLE CAU...

Page 17: ...ted expressly disclaims any liability in relation to the accuracy or completeness of this information Any reliance or use of the information contained within this brochure is at your risk Vital Energi...

Page 18: ...viable sustainable energy solutions for the future For more information about the vTherm t Heat Interface Unit HIU call 01254 296 000 or email hiusales vitalenergi co uk www vitalenergi co uk vTherm...

Reviews: