background image

H E A T   I N T E R F A C E   U N I T  

P R O D U C T   D E S C R I P T I O N 

Page 8

H E A T   I N T E R F A C E   U N I T  

P R O D U C T   D E S C R I P T I O N

Page 9

4. PRODUCT DESCRIPTION

4.1 General Function

The design of the HIU is for parallel production of 
DHW and HTG.

  4.1.1 Keep Warm Bypass

The keep warm function of the HIU is required to 
maintain heat to the HIU, this function assists a 
fast DHW response time to the DHW outlets. 

A bypass is installed across the primary flow and 
return pipework to allow a small flow of water 
through the HIU without warming the plates. The 
flow of water through the bypass is controlled by 
a PICV, the PICV is controlled by a thermostatic 
actuator with the probe measuring the 
temperature at the entry point of the DHW plate.

  4.1.2 Domestic Hot Water

The DHW is controlled by two control valves, 
which control the flow of primary water through 
the plate to generate instantaneous DHW.

1. 

Taco valve: When a DHW outlet is opened the    

    valve detects MCW flow, the valve then opens to    
    allow the primary flow through the plate.

2.

 Thermostatically controlled PICV. The actuators  

    thermostat is installed in the DHW flow out of   
    the plate, the actuator then controls the PICV        
    and the required primary flow rate through the  
    plate to maintain the DHW temperature.

The recommended setting is for 55 deg C 
domestic hot water. Lower temperatures can 
increase the risk of bacteria growth and higher 
temperatures can cause scalding and damage 
the HIU by increasing limescale formation. It is the 
recommendation of CIBSE CP1 and NHBC section 
8 that the temperature is set at this level.

  4.1.3 Central Heating

The Central Heating Room Thermostat / 
Programmer is connected directly to the HIU. 

When there is a HTG demand, the primary side 
HTG on/off control valve opens to allow primary 
water to circulate through the HTG plate, the 
heating pump is enabled to circulate water 
through the radiators. The thermostatic actuator 
controls the flow of primary water through the 
PICV and heat exchanger to maintain the heating 
flow temperature, which is measured by the 
actuators thermostat installed in the outlet of the 
HTG plate. 

 

   

A manometer and thermometer are installed on 
the heating flow pipework within the HIU. This 
is visible through the front cover of the HIU. This 
gauge displays the heating flow temperature and 
heating system pressure. 

The HIU has an expansion vessel installed on the 
heating circuit to accommodate water expansion 
as the system heats up. The heating system is 
filled through the filling loop with MCW. A suitable 
inhibitor should be used to protect the HIU and HTG 
system.

  4.1.4 Metering

There is a flow meter installed on the primary return 
connection which monitors the flow of water to 
the HIU. This combined with temperature sensors 
allows the energy usage to be calculated. The meter 
calculator is positioned on the front of the HIU in 
an accessible location to allow usage to be checked 
regularly.

  4.1.5 Safety Devices

The central HTG system has a safety relief valve 
installed, rated at 3bar. This valve has been installed 
to protect the HIU and HTG system from over 
pressurisation. The valve will require a connection 
to drain, refer to approval document G typical 
discharge safety valve arrangement. 

It is recommended that a high temperature cut 
off switch is installed to protect floor construction 
when serving UFH. This should be installed on the 
flow pipe leaving the HIU serving the UFH manifold.

Note: High temperature thermostat must be 
installed on pipework by HIU installer, it is not 
installed during manufacture. 

The switch should be set 5 deg C higher than 
the flow temperature of the UFH, but not higher 
than the floor material maximum temperature 
specification.

REF

COMPONENT

1

Backplate

2

Bracket (Expansion Vessel)

3

Bracket (Pipes)

4

EPP Cabinet

5

DHW Heat Exchanger

6

DHW Actuator

7

DHW Control Valve

8

Heating Heat Exchanger

9

Heating Actuator

10

Heating Control Valve 

11

Heat Meter (Flow Sensor)

12

Pump

13

Junction Box

14

Check Valve

15

Mini Expansion Vessel

16

Expansion Vessel

17

Thermomanometer

18

Safety Relief Valve (SRV)

19

Test Point (Blue)

20

Test Point (Red)

21

Strainer

22

Ball Valve

23

Filling Loop Connections

24

Drain Valve 

25

Spool Piece For Prepay 

Valve

26

Heating On/Off Valve

27

Heat Meter Calculator

28

Keep Warm Actuator

29

Keep Warm Control Valve

30

MCW Strainer

31

Proportional Flow Controller

HIU Components

Fig. 2

Summary of Contents for vThermt

Page 1: ...Installation Commissioning and Maintenance Manual Version No 002 Always keep the instructions close to the HIU and read the operating instructions carefully before starting any work...

Page 2: ...ydraulic separation between the primary circuit and the secondary DHW and HTG installations The HIU is thermostatically controlled to give good and reliable control of temperature which improves effic...

Page 3: ...g safely and take extreme care DANGER Electrical hazard Failure to follow safety procedures can result in severe injury or death This work may only be performed by a trained electrician CAUTION Risk o...

Page 4: ...ures based on the manufacturer literature DANGER Electricity can cause serious and fatal injuries Always isolate the electrical supply and test before commencing work Before undertaking any work on th...

Page 5: ...nstalled in the outlet of the HTG plate A manometer and thermometer are installed on the heating flow pipework within the HIU This is visible through the front cover of the HIU This gauge displays the...

Page 6: ...AISI 316L Cu Brazing Insulation Expanded Polypropylene Some other materials are used by component manufacturers such as valves and pumps These are in sealing shafts and other small components of the a...

Page 7: ...HIU must only be installed in a suitable location that provides protection against moisture and freezing temperatures The location must have sufficient ventilation to prevent heat build up within the...

Page 8: ...s Step 4 Fit the frame to the wall Step 5 Slide the insulation back onto the valve rail backplate Step 6 Replace all valves Step 7 Fit tighten the nuts and bolts 2 x A and 1 x B so they are secure in...

Page 9: ...alve 8 Heating Heat Exchanger 9 Heating Actuator 10 Heating Control Valve 11 Heat Meter Flow Sensor 12 Pump 13 Junction Box 14 Check Valve 15 Mini Expansion Vessel 16 Expansion Vessel REF COMPONENT 17...

Page 10: ...ion box Before adding power to the unit verify that no electrical connections have been disconnected on the components All accessories and main power supply will be connected in the junction box housi...

Page 11: ...sink tap until a cold clean steady flow of water is achieved Open each DHW outlet within the property until all air and any remaining debris has been flushed through Check HIU for leaking joints on t...

Page 12: ...connections tighten connections as required Do not overtighten the fibre washers as this will result in damage Should a fibre washer become damaged replace the washer immediately ensuring to isolate...

Page 13: ...below which identifies the location of the heating PICV Before undertaking any of the steps below close primary system isolation valves at the top of the HIU and confirm electrical connection is isola...

Page 14: ...or three minutes Complete the Heating section of the Commissioning sheet whilst the HTG is on Switch the HTG off at the room thermostat and isolate the HIU at the fused spur Close the secondary HTG is...

Page 15: ...t be removed after filling Every 2 years Bypass If present check that the flushing bypass valve is closed Every 2 years Pump Check pump setting is Proportional Pressure Auto Adapt Every 2 years HTG Co...

Page 16: ...cted correctly if connected correctly and flow temperature is low consult network operator 10 Plate heat exchanger is blocked Remove PHE clean and re install or replace if necessary FAULT POSSIBLE CAU...

Page 17: ...ted expressly disclaims any liability in relation to the accuracy or completeness of this information Any reliance or use of the information contained within this brochure is at your risk Vital Energi...

Page 18: ...viable sustainable energy solutions for the future For more information about the vTherm t Heat Interface Unit HIU call 01254 296 000 or email hiusales vitalenergi co uk www vitalenergi co uk vTherm...

Reviews: