SPIRIT II G 6-10KVA PF0.9 LCD - UPS www.visionups.com
- 9 -
LED indicator definition
1) Fault Indicator
(
red
):
On indicates when a fault occurred; Off means no fault
2) Indicator
(
Green
):
On means AC is normal, Off means AC is not present,
blinking means voltage is beyond normal range
3) Inverter Indicator
(
Green
):
On : when load is powered by inverter, Off : when it
is not working, blinking: when overload
4) Bypass Indicator
(
Green
):
On : when UPS is in bypass mode, Off: not in bypass
mode; blinking: when the input is beyond normal range
5) Battery Indicator
(
Green
):
On: when UPS is in battery mode, Off : Not in Battery
mode; Blinking: when battery voltage is low or battery is not connected
6) Output Indicator
(
Green
):
On: when there is output, Off: no output.
LCD display content
1) Running parameters
Input voltage/frequency, output voltage/frequency/current/loading, output power,
inverter voltage, battery voltage/battery remaining capacity, Bus voltage/bus
running time, temperature inside UPS
2
)
Alarm information (priority from high to low)
It provides shutting down, auxiliary power fault, output short circuit, inverter fault,
rectifier fault, over temperature, overload, charger fault, battery fault, battery
capacity low, ready to shut down and output fault.
3
)
Parameter setting
Menu setting, working mode setting, battery capacity setting, ID of parallel UPS,
output voltage/frequency level, bypass voltage range, Buzzer enable
Boosting charging voltage 2.30 to 2.35V per cell, floating charging voltage
2.20 to 2.29V per cell
(
use PC to setting
)
Battery capacity setting includes the Ah of each battery unit, battery quantity
16 to 20, parallel group number
Parallel setting
UPS ID setting
UPS amount setting