
Issue February 2002
Document Number: 13124
- 32 -
7.2 General faults
Fault display
Cause
Display remains blank.
- supply voltage is missing.
- equipment fuse is defective. Possibly the applied supply voltage is too high.
Controller does not react to changes; display shows actual cos
ϕ
and LED
'
AUTO
'
flashes.
- Controller has been changed to '
MAN
', press key to revert to automatic
operation.
Controller is hunting.
- C/k value is too low (only with
AU3
mode)
Controller displays a capacitive power factor while inductive
load is present, and no capacitor steps are switched in.
- C.T. connection
k/l
(S1/S2)
is mixed up (only with
AU3
mode)
The set target power factor is reached but does not coincide with
the actual power factor of the plant.
- a wrong measuring voltage connection is set in mode
AU2
or
AU3
.
The displayed current does not coincide with the actual current.
- the current transformers connected to the summation current transformer are
wrongly 'poled'.Terminals
k/l (S1/S2)
are mixed up, i.e. the currents are not added
up but subtracted.
-
the current measuring path of the Controller is connected in parallel with other
measuring equipment; current measuring paths should be connected in series.
- A wrong setting of the C.T. transformation ratio k (parameter 18) was made.
Upon switching it in, the Controller starts with initialization
mode
AU2
and, after this mode is completed, operates
incorrectly.
- Controller is set to
AU1
and uses wrongly memorized data. Possibly the Controller
had been applied in another plant before, wiring of measuring connections were
changed, or a fault occurred with mode
AU1
.
- refer to items 6.0 and 6.3 'setting menu' in order to select the initialization mode
new.