Table with C/k values for 400V:
C/k values for 400 V
current
trans-
former
smallest capacitor step [kvar]
5
10
12.5
15
16.7
20
25
30
40
50
60
100
150
50:5
0.72 1.44
-
-
-
-
-
-
-
-
-
-
-
75:5
0.48 0.96
1.20
1.44
-
-
-
-
-
-
-
-
-
100:5
0.36 0.72
0.90
1.08
1.21
1.44
-
-
-
-
-
-
-
150:5
0.24 0.48
0.60
0.72
0.80
0.96
1.20
1.44
-
-
-
-
-
200:5
0.18 0.36
0.45
0.54
0.60
0.72
0.90
1.08
1.44
-
-
-
-
250:5
0.14 0.29
0.36
0.43
0.48
0.58
0.72
0.87
1.5
1.44
-
-
-
300:5
0.12 0.24
0.30
0.36
0.40
0.48
0.60
0.72
0.96
1.20
1.44
-
-
400:5
0.09 0.18
0.23
0.27
0.30
0.36
0.45
0.54
0.72
0.90
1.08
-
-
500:5
0.07 0.14
0.18
0.22
0.24
0.29
0.36
0.43
0.58
0.72
0.87
1.44
-
600:5
0.06 0.12
0.15
0.18
0.20
0.24
0.30
0.36
0.48
0.60
0.72
1.20
-
800:5
0.05 0.09
0,11
0.14
0.15
0.18
0.23
0.27
0.36
0.45
0.54
0.90
1.35
1000:5
0.04 0.07
0.09
0.11
0.12
0.14
0.18
0.22
0.29
0.36
0.43
0.72
1.08
2000:5
0.02 0.04
0.05
0.05
0.06
0.07
0.09
0.11
0.14
0.18
0.22
0.36
0.54
2500:5
-
0.03
0.04
0.04
0.05
0.07
0.07
0.09
0.12
0.14
0.17
0.29
0.43
3000:5
-
0.02
0.03
0.04
0.04
0.05
0.06
0.07
0.10
0.12
0.14
0.24
0.36
4000:5
-
0.02
0.02
0.03
0.03
0.04
0.05
0.05
0.07
0.09
0.11
0.18
0.27
If
RST
is selected (see page 20),
0.05
is reset.
6.3.6. Parameter
-6-
: Number of switching steps
The number of the connected steps can be set by means of the LED step display. The setting range
comprises 1-6 or12 steps respectively. The number of steps has to be set in case of initialization mode
AU3
. The minimum number of steps is determind by the switching program. In case the number of set
steps is lower than the allowed minimum number of steps, the number of steps will be adjusted
respectively.
If
RST
is selected (see page 20),
6
(
PFC6
) or
12
(
PFC12
) is reset.
6.3.7. Parameter
-7-
: Blocking delay time for re-switching
The time between switching out a certain capacitor step and the earliest moment of switching it in
again is defined as blocking delay time for re-switching. This time is required in order to reduce the
voltage existing at the capacitor to an acceptable level. The re-switching blocking delay time will have
to be selected in accordance with the existing discharge device. Switching-in must take place only
after the residual voltage has fallen below 10% of the operating voltage. The standard setting of the
blocking delay time is 20 seconds.
Re-switching blocking delay time
Display
20 sec
20
60 sec
60
180 sec
180
300 sec
300
If
RST
is selected (see page 20),
20
is reset.