520375-R_RevA
Adenovirus PRO24-186 System
Page 1: ...520375 R_RevA Adenovirus PRO24 186 System ...
Page 2: ... 5 3 2 Pressure Drop 5 3 3 UV Dose Monitoring 6 3 3 1 Dose Curve 6 3 3 2 Dose Alarm Selection 7 3 3 3 UV Sensor 8 3 3 4 Sensor Response Curve 9 3 3 5 Flow Meter 9 3 3 6 Controller Interface 10 3 3 7 COMMcenter 10 3 4 UV Lamp 11 3 4 1 Mercury Discharge Lamp Spectral Output 11 3 4 2 Degradation Chart 12 3 4 3 Temperature Profile 12 3 4 4 Quartz Sleeve 13 3 5 Product Features and Benefits 13 3 5 1 Li...
Page 3: ...mmitment to deliver advanced water treatment solutions that make water safety a reality worldwide VIQUA is an ISO9001 2008 registered company specializing in the design manufacture and sale of ultraviolet systems for household drinking water light commercial drinking water point of use treatment point of entry treatment VIQUA has over 600 000 systems installed worldwide and VIQUA systems can be fo...
Page 4: ... 3 ppm max UVT 75 min after pretreatment 1 2 System Description Model PRO24 186 Spare Parts Quantity Quantity Lamps Sleeves Chamber Material 316L SST UV sensors Dimensions 41 x 4 103 x 10 cm Flow Meters Inlet outlet ports Combo 1 1 4 MNPT 1 FNPT CoolTouch Fans UL Certified burst pressure 300 psi 2 067 kPa COMMcenters Orientation Vertical Electrical Optional Accessories Quantity Power Supply 13 x 6...
Page 5: ...ne featured here Chambers must be installed vertically and right side up according to the indicators on the chambers Ensure there is room above the chambers for lamp removal 1 Sample Valve 2 Pre treatment 3 Shu off Valve 4 Sample Valve 5 Flow Sensor 6 Sensor 2 7 Primary UV Chamber 8 Secondary UV Chamber 9 CoolTouch TM Fan 10 Controller 2 11 COMMcenter TM 12 Solenoid Valve 13 Power Source ...
Page 6: ...3 2 2 Mounting Diagram 2 3 Flow Meter Installation Options 12 min 42 max 37 5 4 47 max 56 max 6 min ...
Page 7: ...4 2 4 Exploded View Refer to pdf and step files for engineering drawings and part numbers ...
Page 8: ...or 4 log Adenovirus reduction In addition to the virus reduction each of the chambers has been validated to provide 4 log reduction of Cryptosporidium and Giardia Benefits Ultra high output amalgam lamp technology allows for compact installation Intense disinfection dose reduces or removes the need for chemical treatment Real time UV intensity and flow rate sensor activate visual and audible contr...
Page 9: ...ance with the 2006 UVDGM There is no flow restrictor on the Adenovirus system Therefore the system can physically exceed 24 GPM however at flow rates above 24 GPM the system will go into alarm and the solenoid valve if connected will cut off the flow of water 0 100 200 300 400 500 600 700 5 10 15 20 25 Dose RED mJ cm 2 Flow rate gpm 95 UVT 85 UVT 75 UVT 65 UVT 186mJ cm 2 ...
Page 10: ...g on input from these components There are two dose settings to choose from variable or stepped dose alarm The system will come factory set as variable but may be set to stepped depending on regional regulations 60 65 70 75 80 85 90 95 100 0 5 10 15 20 25 UVT System Flow GPM Variable Dose Alarm Normal operation 60 65 70 75 80 85 90 95 100 0 5 10 15 20 25 UVT System Flow GPM Stepped Dose Alarm Norm...
Page 11: ...tput and quartz sleeve fouling Rather than basing set points on any one of these factors alarm set points are based on the quantity of light that actually reaches the sensor In this way the UV sensor detects when the water flowing furthest away from the lamp is no longer being disinfected properly due to any factor VIQUA s UV sensors reliably detect low UV output and identify the need for maintena...
Page 12: ...low rate of water passing through the UV systems The flow meter utilizes a paddle wheel and a flow detect arm to ensure reliable measurements The flow meter outputs a 4 20 mA signal to the controller 0 0 02 0 04 0 06 0 08 0 1 0 12 0 14 0 16 1E 8 1E 7 1E 6 1E 5 1E 4 1E 3 1E 2 1E 1 1E 0 200 250 300 350 400 450 500 Linear Spectral Response S A W Logarithmic Spectral Response S A W Wavelength λ nm Log...
Page 13: ... COMMcenterTM this means the UV disinfection dose is monitored even if the COMMcenterTM should fail To achieve 186 mJ cm2 both systems must be on and working properly Should one controller lose communication with the other or if the COMMcenterTM loses communication with either controller the system will go into visual and audible alarm Features Continuously monitors and controls the system Communi...
Page 14: ...al Output The lamp produces germicidal ultraviolet light UV C at a wavelength of 253 7 nm The absence of a peak at 185 nm is significant because it means no harmful ozone will be produced VIQUA s amalgam lamps have a mercury content of less than 15 mg IMERC registered VIQUA s amalgam lamps use a mercury amalgam matrix as opposed to mercury in its pure liquid form Therefore the mercury is contained...
Page 15: ...ful life of approximately 18 000 hours They can provide adequate disinfection for up to two years and then require replacement 3 4 3 Temperature Profile VIQUA s lamps use a mercury amalgam mix to control the vapour pressure and produce a more stable output than conventional standard output lamps 0 20 40 60 80 100 0 5000 10000 15000 20000 253 7nm Output Burning Hours 50 60 70 80 90 100 0 10 20 30 4...
Page 16: ...ghtWise technology allows the system s electronic controller to automatically reduce lamp power during periods of no water flow In order to maintain dose levels above alarm setpoint values the controller will dim to 62 power output The dimming capability ultimately reduces the rate of sleeve fouling Benefits Lower maintenance up to 60 less maintenance Lower energy consumption estimated savings of ...
Page 17: ...th between these contacts are closed The Electrical path between these contacts are open BLACK COM Common COM Common The Electrical path between these contacts are open The Electrical path between these contacts are closed GREEN N C Normally Closed Contact 3 6 2 4 20 mA Interface An optional 4 20 mA interface allows the user to read the current output by the UV sensor or the flow meter The interfa...
Page 18: ...table below During this time VIQUA will repair or replace at its option any defective parts covered by the warranty Component Warranty UV Chamber ten 10 years from the date of purchase Electrical controller and Hardware Components five 5 years from the date of purchase UV Lamps Sleeves and UV Sensors one 1 year from the date of purchase ...
Page 19: ...ments VIQUA s product development process ensures comprehensive product validation and certification VIQUA manufactures each UV disinfection system to the highest quality standards Each system is subjected to rigorous functional testing prior to shipment to guarantee proper operation VIQUA is an ISO9001 2008 registered company 425 Clair Rd W Guelph Ontario Canada N1L 1R1 Tel 1 519 763 1032 Toll Fr...