![VIPA System 300S IM 353-1DP01 Manual Download Page 52](http://html1.mh-extra.com/html/vipa/system-300s-im-353-1dp01/system-300s-im-353-1dp01_manual_1029242052.webp)
Chapter 3 Deployment
Manual VIPA System 300S
3-30
HB140E - IM - RE_353-1DP01 - Rev. 14/46
… continue
Interrupt status at diagnostic interrupt Bytes x+8 to x+19
(corresponds to CPU diagnostic record set 1)
Byte Bit 7 ... Bit 0
x+8
70h: Module with digital inputs
71h: Module with analog inputs
72h: Module with digital outputs
73h: Module with analog outputs
74h: Module with analog in-/-outputs
76h: Counter
x+9
Length of the channel-related diagnostic
x+10 Number of channels per module
x+11 Position (channel) with diagnostic event
x+12 Diagnostic event on the channel/channel group 0
Assignment see module description
x+13 Diagnostic event on the channel/channel group 1
Assignment see module description
.
.
.
.
.
.
x+19 Diagnostic event on the channel/channel group 7
Assignment see module description
Interrupt status at hardware interrupt Bytes x+4 to x+7
More detailed information to the diagnostic data is to find in the concerning
module descriptions.