Via the index A4h, the module configuration of DP slave can be monitored.
The assignment
identification
to
module type
can be found at the following
table:
Module type
Identification
Input byte
Output byte
DI 8
9FC1h
1
-
DI 8 - Alarm
1FC1h
1
-
DI 16
9FC2h
2
-
DI 14 / 2C
08C0h
6
6
DI 32
9FC3h
4
-
DO 8
AFC8h
-
1
DO 16
AFD0h
-
2
DO 32
AFD8h
-
4
DIO 8
BFC9h
1
1
DIO 16
BFD2h
2
2
AI2
15C3h
4
-
AI4
15C4h
8
-
AI4 - fast
11C4h
8
-
AI8
15C5h
16
-
AO2
25D8h
-
4
AO4
25E0h
-
8
AO8
25E8h
-
16
AI2 / AO2
45DBh
4
4
AI4 / AO2
45DCh
8
4
To access the function modules with the Siemens SIMATIC Manager the
module address
, which can be set by properties, is used as
ID
.
Using the following record set no. as
Index
you get access for reading (R)
res. writing (W) to the listed function module elements:
Index Access Description
R
Diagnostic – record set 0
00h
W
Write Module parameters
01h
R
Diagnostic – record set 1
Device
configuration
Data of the
function modules