Chapter 3   Installation Guidelines

 

Manual VIPA HMI 

3-6 

 

HB160E - TP - RE_610-3B2J0 - Rev. 09/09 

EMC-equitable assembly 

 

Mostly, measures for suppressing interference voltages are only taken, 
when the control is already in commission and the perfect receive of a 
wanted signal is disturbed. 

Causes for such interference's are in the most cases inadequate reference 
potentials, coming from mistakes at the device assembly and installation. 

 

When assembling the devices, you have to ensure the large-surface 
grounding of the inactive metal parts. A correctly done grounding supports 
an unambiguous reference potential for the control and reduces the impact 
of coupled interference's. 

Grounding means the conducting connection of all inactive metal parts. 
The sum of all interconnected inactive parts is called Ground. 

Inactive parts are all conductive parts electrically separated from all active 
parts by means of a basic isolation and that may only get voltage in case of 
an error. 

The ground must not adopt dangerous contact voltage even in case of an 
error. Thus you have to connect the ground with the protected earth 
conductor. To avoid ground loops, local distant ground constructions 
(cubicles, construction and machine parts) have to be connected with the 
protected earth conductor system in star-topology. 

 

Please regard at grounding: 

• 

Connect the inactive metal parts as carefully as the active ones. 

• 

Take care of impedance-low metal-metal-connections, for e.g. with 
large-surface and well conductive contacts. 

• 

If you include coated or anodized metal parts in the grounding, you have 
to come through the isolating protection layers. For this you may use 
special contact washers or remove the isolation layer. 

• 

Protect the connection points from corrosion, e.g. with grease. 

• 

Moveable grounding parts (e.g. cubicle doors) have to be connected via 
flexible ground strips. The ground strips should be short and have a 
large surface, because the surface is decisive for the diversion of high 
frequency interference's. 

 

 

 

Guidelines for 
assembling and 
grounding of 
inactive metal 
parts 

Summary of Contents for HMI 610-3B2J0

Page 1: ...der no VIPA HB160E_TP Reference RE_610 3B2J0 Rev 09 09 This manual is part of the documentation package with order number VIPA HB160E_TP and relevant for Product Order number as of state HW OS TP 610C...

Page 2: ...Lerrzeichen...

Page 3: ...ensure that it conforms with the described hardware and software However discrepancies can not be avoided The specifications in this manual are examined regularly and corrections will be included in s...

Page 4: ...also find the dimensions that are required for the installation The chapter closes with the technical data Chapter 2 Deployment Touch Panel This chapter deals with the employment of the Touch Panel A...

Page 5: ...sioning 2 4 Connection to a PLC system 2 6 Operating system Windows CE 2 7 Communication via ActiveSync 2 12 Integrated Server 2 15 Access to the network resources 2 22 Integration to WLAN network 2 2...

Page 6: ...Contents Manual VIPA HMI ii HB160E TP RE_610 3B2J0 Rev 09 09...

Page 7: ...ter An index at the end of the manual The manual is available in printed form on paper in electronic form as PDF file Adobe Acrobat Reader Button Buttons are put in brackets e g NEXT or OK Key Key ent...

Page 8: ...nual must be available to all personnel in the project design department installation department commissioning operation The following conditions must be met before using or commissioning the componen...

Page 9: ...TP 610C CAN from VIPA Besides of a description of the single components of the Touch Panel you will also find the dimensions that are required for the installation The chapter closes with the technica...

Page 10: ...reby causing the module to become inoperable or unusable Modules that have been damaged by electrostatic discharges may fail after a temperature change mechanical shock or changes in the electrical lo...

Page 11: ...g and controlling of process cycles Microsoft Windows CE V 5 0 full version as option Different HMI SCADA Runtime selectable 800MHz pulse frequency Work memory 128Mbyte about 1800Mbyte memory for user...

Page 12: ...1 Slot for storage medium CF SD MMC 2 Connection for interfaces and power supply T o u c h P a n e l 1 2 3 3 Display with touch sensitive area touch screen 1 Compact Flash 2 MMC SD 1 2 Note Please reg...

Page 13: ...9 1 RS422 485 interface COM 2 2 RS232 interface COM 1 3 CAN interface 4 2x Host USB A interface 5 Slave USB B interface 6 7 RJ45 jack for Ethernet Communication switch 8 Slot for DC 24V voltage suppl...

Page 14: ...at My Device Slot for CF Here you may plug a CompactFlash type II The card may be plugged and removed during runtime and is immediately listed as Storage Card at My Device Every CompactFlash storage m...

Page 15: ...5 4 3 2 1 9 8 7 6 9 RxD Line B TxD A TxD B RxD A RxD B Shield RS422 Periphery 3 8 4 9 M5V TxD TxD RxD RxD P5V 5 6 Serial bus connection in 2 wire technology using half duplex mode Connection RS485 iso...

Page 16: ...er rate up to 115 2kBaud 9pin plug Connection RS232 Pin RS232 1 CD 2 RxD 3 TxD 4 DTR 5 GND 6 DSR 7 RTS 8 CTS 1 2 3 4 5 6 7 8 9 9 RI RxD TxD GND TxD RxD 3 2 GND 5 RTS CTS 7 8 Shield RS232 Periphery Shi...

Page 17: ...nt is as follows Slave USB B Pin Assignment 1 VCC 2 DM 3 DP 2 1 3 4 4 GND The USB A interface of your PC can be connected to the Slave USB B interface of your Touch Panel deploying the USB programming...

Page 18: ...tallation cutting W x H 287 x 217mm Front panel W x H 304 x 233mm Back side W x H x D 285 x 215 x 45mm Installation depth 45mm Note The degrees of protection are only guaranteed when the following is...

Page 19: ...ly Operating temperature 0 50 C Relative humidity max 85 Storing Transport temperature 20 to 60 C Display Size 10 4 Resolution 600 x 800 800 x 600 Colors TFT color 64K colors MTBF Backlights 25 C ca 5...

Page 20: ...Chapter 1 Hardware description Manual VIPA HMI 1 12 HB160E TP RE_610 3B2J0 Rev 09 09...

Page 21: ...connection of the Touch Panel The main part of the chapter introduces Windows CE and the various communication options offered by the Touch Panel Topic Page Chapter 2 Deployment Touch Panel 2 1 Instal...

Page 22: ...le For the installation into a operating tableau and control cabinet fronts the Touch Panel requires the following front plate cutting W H Touch Panel W x H in mm 610 3B2J0 287 x 217 The fixing techni...

Page 23: ...e flexible wires without end case as well as stiff wires You fix the conductors to the CageClamps like this DC 24V 1 2 3 1 Round opening for wires 2 Locking orange for screwdriver 3 Test point for 2mm...

Page 24: ...Panel is provided by power supply the Touch Panel starts with the VIPA Startup Manager The VIPA Startup Manager has the following buttons A project is started within the VIPA Startup Manager after a c...

Page 25: ...zation software is used LOCATION Indicates the file location of the visualization software FILE Path and file name of the last started project FONT Indicates the storage location of additional fonts t...

Page 26: ...d runtime version of the HMI SCADA project engineering platforms your project is run able By using the according communication driver the Touch Panel supports connecting options to the PLC via field b...

Page 27: ...ed to the absolute essentials with mouse operation touch screen that requires only small hardware resources Here the 2 icons My Device and Recycle Bin may exclusively be found at the Desktop The Profe...

Page 28: ...selects the touched objects Characteristics with Windows CE Professional Plus V 5 0 In the Professional Plus version mouse functions are fully supported As soon as the touch screen is touched with the...

Page 29: ...tings file browser etc 2 Open applications For every open application a button is to be found in the task bar There is no button for minimizing The switch between the applications happens via this but...

Page 30: ...clusively entered via the software keyboard Keyboard Normal At pushed SHIFT key Meaning Home Position 1 End End BS Backspace up dn lt rt pgup Page pgdn Page ins Insert del Delete Tab Tabulator Shift C...

Page 31: ...ou may use the grid pattern to preset a double click velocity and test this on the symbol below OK takes over the set value The calibration of the touch screens happens via the register Calibration by...

Page 32: ...Panel from the PC via ActiveSync you have to install it at the PC ActiveSync is freeware and may be downloaded from www microsoft de Download the ActiveSync from the Microsoft website and start the fi...

Page 33: ...ouch Panel is recognized and the dialog window new partnership opens Choose yes that you want to fix a partnership and push Next In the now opening window de activate all synchronization settings and...

Page 34: ...able the Touch Panel to be accessed via Ethernet you have to activate the option enable network connection in ActiveSync via File Connection Settings Disconnect the USB cable of the Touch Panel Confir...

Page 35: ...via START Programs KuK Tools before switching off Per default the following server are integrated ftp server activated http server activated Telnet activated VNC not activated Phrases that are used in...

Page 36: ...ns for an ftp connection If there are still problems with the ftp access ask your system administrator ftp access possible with version 5 5 or higher use passive ftp mode activate directory view for f...

Page 37: ...nnect your Touch Panel with the network where your PC is a member via an Ethernet cable Switch on your Touch Panel As soon as your Touch Panel is connected via Ethernet you may monitor the IP address...

Page 38: ...into the address bar IP address webadmin Enter the following into the authentification User name wince Password vipatp Remember to store your changes permanently in the registry via Start Programs KuK...

Page 39: ...plication is not possible The establishing of a Telnet connection is password protected and has the following approach Start a Telnet client like for example MS DOS console at your PC and enter the fo...

Page 40: ...3B2J0 Rev 09 09 After establishment of a Telnet connection the Touch Panel provides you with commands A list of possible commands with a short description is available via the command help By beginnin...

Page 41: ...n the VNC server is on delivery deactivated The VNC connection establishment has the following approach Click on and open the Windows directory You have to deactivate every option at View Options to s...

Page 42: ...test the physical connection a PING to the IP address of the network PC may be executed if there are problems while contacting the network PC The connection of a local name at the Touch Panel with a...

Page 43: ...etwork printer For example you may print the content of the current directory with dir network printer The listing of all network connections of your Touch Panel happens via net use You may terminate...

Page 44: ...s is opened Continue with WLAN integration Please regard only WLAN USB sticks are supported with the chip of the company Funkwerk inside PowerOFF the Touch Panel Plug the WLAN USB stick to the USB A i...

Page 45: ...tivated For this open the register Wireless Information in the dialog window and click to the Advanced button The following window is shown By activating of Automatically connect to non preferred netw...

Page 46: ...sed Switch off the power supply from your panel Plug the memory card to your panel and switch on the power supply again As soon as a new firmware is found at the memory card it is downloaded to the To...

Page 47: ...Here we describe possible paths in which interference can enter the controller how you ensure the electromagnetic compatibility EMC and how to approach shielding and screening issues Topic Page Chapte...

Page 48: ...industrial environments and complies with EMC requirements to a large degree In spite of this you should implement an EMC strategy before installing any components which should include any possible s...

Page 49: ...te to the time wise change of the voltage Interference through parallel signal lines Static discharge of the personnel Contactors Inductive coupling Automation System Disruptor inductive coupling line...

Page 50: ...groups High voltage lines power supply lines signal lines data lines Always install high voltage lines and signal or data lines in separate channels or bundles Install signal and data lines as close...

Page 51: ...cent lamps Create a single reference potential and ensure that all electrical equipment is grounded wherever possible Ensure that grounding measures are implemented effectively The controllers are ear...

Page 52: ...may only get voltage in case of an error The ground must not adopt dangerous contact voltage even in case of an error Thus you have to connect the ground with the protected earth conductor To avoid gr...

Page 53: ...to divide the cables in different groups and install each group itself Group A screened bus and data lines screened analog lines unshielded lines for direct voltage 60V unshielded lines for alternatin...

Page 54: ...be installed on metallic cable trays A galvanic connection must be provided for joints between cable trays You must abide by the applicable lightning protection and grounding regulations when install...

Page 55: ...mm 2 Cu for equipotential bonding conductors up to 200m 25mm2 Cu for equipotential bonding conductors exceeding 200m Use copper or galvanized steel for equipotential bonding conductors These must be c...

Page 56: ...recommended that the remove the insulation from the screened cable without cutting the screen and to attach this point to the screening neutral rail Note Potential differences can give rise to an equ...

Page 57: ...ections of DC activated inductors Connections of AC activated inductors using a diode using a Z diode using a varistor using RC network Every cubicle must be provided with a power outlet for the PU Th...

Page 58: ...l contact washer Have the connection been protected from corrosion e g by means of grease Have doors been grounded by means of grounding straps connected to the body of the cubicle Cable routing Cabli...

Page 59: ...F Firmware update 2 26 Flash disc 1 6 ftp server 2 16 H http server 2 18 I Installation 2 2 cutting 2 2 guidelines 3 1 L Login data 2 15 M Memory management 1 6 MMC 1 6 N net use 2 22 net view 2 22 Ne...

Page 60: ...Index Manual VIPA HMI A 2 HB160E TP RE_610 3B2J0 Rev 09 09 M Stich...

Reviews: