background image

General Installation Manual

EVERVOLT™ PHOTOVOLTAIC MODULE

EVPVXXX SERIES (WHITE BACK SHEET)

EVPVXXXK SERIES (BLACK BACK SHEET)

Summary of Contents for EVERVOLT EVPV Series

Page 1: ...General Installation Manual EVERVOLT PHOTOVOLTAIC MODULE EVPVXXX SERIES WHITE BACK SHEET EVPVXXXK SERIES BLACK BACK SHEET ...

Page 2: ... Specifications 3 Standards Fire Class of Product Junction Box Terminals and Connectors Bypass Diode Installation 6 General Operating Conditions Unpacking and Handling Cable Management Module Installation Use of Rails and Clamps Mounting with Continous Rails Parallel to Long Side of the Module Mounting with Short Rails Mounting Methods Mounting Holes Wiring 12 General Module Wiring Array Wiring Dr...

Page 3: ... in parallel producing higher current and as modules are connected in series producing higher voltages The shock hazard increases as modules rated for maximum system voltage in excess of 50 V Wear suitable clothing gloves and guards to prevent from direct contact with 30 VDC or greater Work only in dry conditions with dry modules and dry tools Children and unauthorized persons should not be allowe...

Page 4: ... Therefore the Isc value of modules should be multiplied by a factor of 1 25 to determine ampacity An additional factor of 1 25 may be required for sizing conductors fuses disconnects etc Please refer to section 690 8 of the National Electric Code NEC for guidelines The Voc must be factored according to the lowest recorded ambient temperature recorded for the location where the modules will be ins...

Page 5: ...ort Circuit Current Isc 10 55A 10 49A 10 49A 10 44A Cell Type Silicon hetero junction Silicon hetero junction Silicon hetero junction Silicon hetero junction Maximum System Voltage 1000V 1000V 1000V 1000V Factory Installed Bypass Diodes 3 3 3 3 Maximum series fuse A 25 25 25 25 Electrical Specifications Values at standard test conditions STC air mass AM 1 5 irradiance 10 75 W sq ft 1000 W m temper...

Page 6: ... terminal is provided with factory installed lead cables and a latching connector for series and string connections Always use these connectors and do not detach them from cables The PV module comes pre wired Each module has two 12 AWG type PV wire stranded sunlight resistant output cables each terminated with connectors The positive terminal has a male connector while the negative terminal has a ...

Page 7: ...e cables follow the instructions below To prevent stress on the junction box casing ensure the cable exits the junction box in a straight line before any bend in the cable The cables must have a minimum bending radius of 1 2 in 30 mm to avoid damage to the insulation refer Figure 4 Ensure cables do not hang loose where they may be damaged through friction or stress e g caused by mechanical abrasio...

Page 8: ...sture shall not be employed alone or in combinations that could result in deterioration or corrosion USE OF RAILS AND CLAMPS Installing the EverVolt modules with clamps and rails has been found to comply with UL 61730 requirements for downward pressure e g snow of up to 7000 Pa 4666 Pa design load and upward pressure e g wind of up to 4000 Pa 2666 Pa design load according to the following instruct...

Page 9: ...1800 Pa 1800 Pa 1200 Pa 1200 Pa 6200 Pa 4000 Pa 4133 Pa 2666 Pa 7000 Pa 4000 Pa 4666 Pa 2666 Pa X 22 2 23 8 in 565 605 mm 1200 Pa 1200 Pa 800 Pa 800 Pa 3000 Pa 2400 Pa 2400 Pa 1600 Pa 5400 Pa 2400 Pa 3600 Pa 1600 Pa X 23 8 27 4 in 605 695 mm 2400 Pa 2400 Pa 1600 Pa 1600 Pa 2400 Pa 2400 Pa 1600 Pa 1600 Pa 2400 Pa 2400 Pa 1600 Pa 1600 Pa X 0 4 in 0 100 mm X 1200 Pa 1200 Pa 800 Pa 800 Pa 1600 Pa 1600...

Page 10: ...1200 Pa 1200 Pa 800 Pa 800 Pa 3000 Pa 2400 Pa 2400 Pa 1600 Pa 5400 Pa 2400 Pa 3600 Pa 1600 Pa X 0 4 in 0 100 mm X 1200 Pa 1200 Pa 800 Pa 800 Pa 1600 Pa 1600 Pa 1066 Pa 1066 Pa X 4 9 8 in 100 250 mm X 800 Pa 800 Pa 533 Pa 533 Pa 2400 Pa 2400 Pa 1600 Pa 1600 Pa X Once a module is secured in each of the 4 zones fig 2 additional clamps i e 5 may be freely located on panel frame without affecting the w...

Page 11: ...a 1800 Pa 1200 Pa 1200 Pa 2400 Pa 2400 Pa 1600 Pa 1600 Pa 2400 Pa 2400 Pa 1600 Pa 1600 Pa X 0 4 in 0 100 mm X 1200 Pa 1200 Pa 800 Pa 800 Pa 1600 Pa 1600 Pa 1066 Pa 1066 Pa X 4 9 8 in 100 250 mm X 800 Pa 800 Pa 533 Pa 533 Pa 2400 Pa 2400 Pa 1600 Pa 1600 Pa X Rail length under module 4 7 9 in Min 1 in 4 7 9 in 0 8 2 in 0 208 mm X 1200 Pa 1200 Pa 800 Pa 800 Pa 1600 Pa 1600 Pa 1066 Pa 1066 Pa X 8 2 13...

Page 12: ...ant material e g aluminum or galvanized steel and appropriate for the local environment All four mounting holes in the frame must be used fig 8 Additional electrical bonding to Ground is required for the support structure Refer to the fixing device manufacturer s installation instructions for preload or torque values Do not contact a tip of a mounting bolt to back sheet of the module when fixing t...

Page 13: ...lations that account for specific project requirements and site conditions If modules will be used in an offgrid system a compatible MPPT Maximum Power Point Tracking charge controller is required Especially charge battery can not be used without MPPT These modules contain factory installed bypass diodes If these modules are incorrectly connected to each other the bypass diodes cable or junction b...

Page 14: ...ze should be between 4 14 AWG 2 1 mm 21 2 mm Attach grounds to the grounding holes in the module frames Fix lug to the frame using a star washer and lock nut ensuring a conductive connection Follow the grounding device manufacturer s installation instructions to ensure a safe and conductive connection including any supplementary hardware e g star washer and tighten according to recommended torque ...

Page 15: ... may be deteriorated or damaged SYSTEM INSPECTION The system should be inspected regularly to ensure that Fasteners are secure tight and free from corrosion Electrical connections are secure tight clean and free of corrosion The mechanical integrity of the cables is intact Bonding points to ground are tight secure and free from corrosion which could break the continuity between the modules and gro...

Page 16: ...15 General Installation Manual REVISION HISTORY Edition Revision Date Revised Item Revised Content NEW 10 13 2020 ...

Page 17: ...ing an MLPE device to a solar module it must be secured to the module frame Follow MLPE manufacturer instructions to ensure optimum mounting of MLPE device and prevent any slippage during operation MLPE devices may also be attached to the mounting construction In such cases refer to the instructions provided by the manufacturer Wherever possible the installation of the MLPE device should not cover...

Page 18: ...any of America Two Riverfront Plaza Newark NJ 07102 panasonicHIT us panasonic com na panasonic com us solar All Rights Reserved 2020 COPYRIGHT Panasonic Corporation Specifications are subject to change without notice RS20183BRO r6 ...

Reviews: