HB97E - CPU - RE_21x-1Bx06 - Rev. 13/20
3-27
Using test functions for control and monitoring of variables
For troubleshooting purposes and to display the status of certain variables
you can access certain test functions via the menu item
Debug
of the
Siemens SIMATIC manager.
The status of the operands and the VKE can be displayed by means of the
test function
Debug
>
Monitor
.
You can modify and/or display the status of variables by means of the test
function
PLC
>
Monitor/Modify Variables
.
This test function displays the current status and the VKE of the different
operands while the program is being executed.
It is also possible to enter corrections to the program.
Note!
When using the test function “Monitor” the PLC must be in RUN mode!
The processing of the states may be interrupted by means of jump
commands or by timer and process-related alarms. At the breakpoint the
CPU stops collecting data for the status display and instead of the required
data it only provides the PG with data containing the value 0.
For this reason, jumps or time and process alarms can result in the value
displayed during program execution remaining at 0 for the items below:
•
the result of the logical operation VKE
•
Status / AKKU 1
•
AKKU 2
•
Condition byte
•
absolute memory address SAZ. In this case SAZ is followed by a "?".
The interruption of the processing of statuses does not change the
execution of the program. It only shows that the data displayed is no longer.
Overview
Debug
>
Monitor
Summary of Contents for CPU 214
Page 1: ...VIPA System 200V CPU Manual HB97E_CPU RE_21x 1Bx06 Rev 13 20 May 2013...
Page 4: ...Contents Manual VIPA System 200V ii HB97E CPU RE_21x 1Bx06 Rev 13 20...
Page 8: ...Safety information Manual VIPA System 200V 4 HB97E CPU RE_21x 1Bx03 Rev 13 20...
Page 26: ...Chapter 1 Basics and Assembly Manual VIPA System 200V 1 18 HB97E CPU RE_21x 1Bx06 Rev 13 20...