- 11 -
7. How to calibrate the air probe
If the actual cellar temperature differs from the setting temperature, set
parameter
ot
= actual cellar temperature minus set-point.
8. How to adjust defrost cycle
I
n case there is excessive frost, the parameters
FnC
=
C-y
, idF
=
4
and
MdF
=
20
can be used to avoid frost.
9. How to adjust the humidity
The parameter
Fon
is used to adjust the humidity in the wine cellar. Higher
Fon
results in higher relative humidity.
Use a separate hygrometer to monitor the
humidity.
10. How to set alarm call
1) S
peech notice will be sent to your phones when the cellar temperature is
ALU
higher or
ALL
lower than the set-point
Set
.
2) In order to test the call function, set parameters
Ald
= 0 and
dAO
= 0. After
testing, set
Ald
= 60 and
dAO
= 23.
11. How to set low cellar temperature heater
The heater turns on at
SAA
minus
Shy;
the heater turns off at
SAA
.
NOTES:
•
Use a forced air heater to warm up the wine cellar.
•
If there is a thermostat on the heater, bypass it or set the thermostat at the
highest level.
If the heater runs more than 10 A current, use a 120VAC coil contactor.
Summary of Contents for Wine-Mate WM-4510HZD
Page 24: ...23 Fig 4 15 Cold air supply cellar air return and hot air exhaust ducts...
Page 29: ...28 Electrical Wiring Diagrams Fig 7 1 WM 4510 8510HZD standard wiring diagram...
Page 30: ...29 Fig 7 2 WM 4510 8510HZD crankcase heater wiring diagram...
Page 31: ...30 Fig 7 3 WM 4510 8510HZD alarm call wiring diagram...
Page 32: ...31 Fig 7 4 WM 4510 8510HZD cellar heater wiring diagram...
Page 33: ...32 Fig 7 5 WM 4510 8510HZD crankcase heater alarm call wiring diagram...
Page 34: ...33 Fig 7 6 WM 4510 8510HZD crankcase heater cellar heater wiring diagram...
Page 35: ...34 Fig 7 7 WM 4510 8510HZD alarm call cellar heater wiring diagram...
Page 36: ...35 Fig 7 8 WM 4510 8510HZD crankcase heater alarm call cellar heater wiring diagram...