- 10 -
6. Parameter Programming
1) Press and hold the
SET
+
keys until the “
°C” or “°F”
LED starts flashing,
then release the keys.
2) Press and hold again the
SET
+
keys until the
Pr2
label is displayed, then
release the keys. The first parameter
Hy
will be displayed.
3) Press up/down keys
/
to scroll to the required parameter within 10 sec.
4) Press the “
SET
” key to display its value.
5) Use up/down keys
to change its value within 10 sec.
6) Press “
SET
” to store the new value and the display will flash 3 times.
7)
To exit
: Press
SET +
or wait 15sec without pressing a key.
PARAMETER DESCRIPTION
DEFAULT
VALUE
Set
set-point (
°
)
55
Hy
temperature regulation differential
(
°
)
4
AC
anti-short cycle delay (min)
10
Con
compress on with probe faulty (min)
20
CoF
compress off with probe faulty (min)
20
CF
temperature unit
(
°
F
/ °
C
)
F: Fahrenheit
rES
display resolution
in: integer
dLy
temperature display delay (min)
1
ot
probe calibration
(
°
)
0
LS
minimum set-point
(
°
)
50
US
maximum set-point
(
°
)
65
idF
defrost cycle interval time (hour)
12
MdF
defrost cycle endurance time (min)
30
ALC
temperature alarm type
rE: relative to set-point
ALU
high temperature alarm
(
°
)
10
ALL
low temperature alarm
(
°
)
10
AFH
alarm recovery differential
(
°
)
5
ALd
temperature alarm delay (min)
60
dAo
temperature alarm delay on startup (hr)
23
SAA
heater set-point
(
°
)
40
SHy
heater regulation differential
(
°
)
4
FSU
fan action
Std
FnC
fan operating mode
C-n: on with compressor & off during defrost
C-y: on with compressor & on during defrost
O-n: on all the time & off during defrost
O-y: on all the time & on during defrost
Fon
fan on with compressor off (min)
0
FoF
fan off with compressor off (min)
15
NOTE
: Depending on the controller, not all parameters are used.
Summary of Contents for Wine-Mate WM-4510HZD
Page 24: ...23 Fig 4 15 Cold air supply cellar air return and hot air exhaust ducts...
Page 29: ...28 Electrical Wiring Diagrams Fig 7 1 WM 4510 8510HZD standard wiring diagram...
Page 30: ...29 Fig 7 2 WM 4510 8510HZD crankcase heater wiring diagram...
Page 31: ...30 Fig 7 3 WM 4510 8510HZD alarm call wiring diagram...
Page 32: ...31 Fig 7 4 WM 4510 8510HZD cellar heater wiring diagram...
Page 33: ...32 Fig 7 5 WM 4510 8510HZD crankcase heater alarm call wiring diagram...
Page 34: ...33 Fig 7 6 WM 4510 8510HZD crankcase heater cellar heater wiring diagram...
Page 35: ...34 Fig 7 7 WM 4510 8510HZD alarm call cellar heater wiring diagram...
Page 36: ...35 Fig 7 8 WM 4510 8510HZD crankcase heater alarm call cellar heater wiring diagram...