- 12 - 

 
 
e.  Malfunctioning fans 
 
f.  Evaporator or condenser airflow 

 

g.  Dirty Condenser 
h.  Iced evaporator 
i.  Refrigeration system restriction 
j.  Refrigerant leak 
k.  Undercharge or overcharge 
l.  Failed components 
 

minimum  1  foot  clearance  for  the 
ambient air intake side  

e.  Check  for  both  evaporator  and 

condenser fans  

f.  Check  for  air  restrictions,  air  short-

circulation, grille directions 

g.  Clean condenser 
h.  Defrost and reset temperature 
i.  Call service 
j.  Call service  
k.  Call service  
l.  Check  compressor  windings,  start 

relay and overload protector 

7. Unit running too 

long 

 

a.  Improper cellar insulation & seal 
 
b.  Exhaust restricted 
 
 
 
c.  Cellar too large 
d.  Ambient temperature > 90°F 
e.  Dirty Condenser 
f.  Improper condenser air flow 
 

a.  Check  insulation,  gasket  and  door 

opening 

b.  Leave minimum 3 feet clearance for 

the  hot  air  exhaust  side  and  leave 
minimum  1  foot  clearance  for  the 
ambient air intake side 

c.  Check for excessive size   
d.  Check for installation location 
e.  Clean condenser 
f.  Check  for  fan  and  air  short 

circulation 

8. Condenser fan 

running but 
compressor 
not running

 

a.  Incorrect or loose wirings 
b.  Failed components 

 

c.  Liquid 

refrigerant 

in 

the 

compressor 

a.  Check all wirings and  connections 
b.  Check  start  relay,  start  capacitor, 

overload protector, compressor. 

c.  Call service. 

9. Compressor 

running but 
condenser fan 
not running

 

a.  Fan blade stuck 
b.  Incorrect or loose wirings 
c.  Failed motors 
d.  Fan cycle control 

a.  Check for proper clearance 
b.  Check all wirings 
c.  Call service 
d.  Check for setting 

10.Temperature  

high, 
compressor 
stopping and 
starting but 
very short 
running time

 

a.  Failed components 
 
b.  Improper condenser airflow 
c.  Dirty condenser 
d.  Overcharge of refrigerant 
e.  Discharge  or  suction  pressure 

too high 

a.  Check  compressor  windings,  start 

relay and overload protector. 

b.  Check for condenser fan  
c.  Clean condenser 
d.  Call service for removing refrigerant 
e.  Call service for information 
 

11.Evaporator fan 

running too 
long 

a.  Post-compressor  fan  running 

mode for humidity modulation 

 

a.  Reset FON 
 

12. Evaporator fan 

running but 
condensing 
unit not 
running

 

a.  Incorrect or loose wirings 
b.  Failed components 
 
c.  Low refrigerant 

a.  Check all wirings and  connections 
b.  Check  start  relay,  start  capacitor, 

overload protector, compressor. 

c.  Call service 
 

13.Temperature 

low 

a.  Low temperature setting 
b.  Low ambient temperature 
c.  Air probe fault 
 
d.  Temperature controller fault 

a.  Raise the setting 
b.  Move to another location 
c.  Check probe connections or change 

a new one 

d.  Change a new one 

14.Evaporator 

freezing up

 

a.  Evaporator air flow restriction 
b.  Condenser air flow restriction 

a.  Check for fans and CFM 
b.  Check for fans and CFM 

Summary of Contents for WINE-MATE WM-12000SSA

Page 1: ...A LA WM 6500SSA WM 6500SSA LA WM 8500SSA WM 8500SSA LA WM 12000SSA WM 12000SSA LA www vinote www vinotemp com mp com Read and save these instructions Read and save these instructions Vinotemp Internat...

Page 2: ...1 Important Safety Information...

Page 3: ...2 Table of Contents Cellar Construction Guide 3 Features Specifications 4 Temperature Humidity 6 Care Guide 10 User Troubleshooting 11 Installer s Instructions 14 Electrical Wirings 26 Warranty 29...

Page 4: ...temperature surrounding the cellar shall not exceed the temperature of the cellar by more than 25 F No cellar walls shall receive direct sun or strong wind Lighting shall be of low wattage with a tim...

Page 5: ...for long term storage of wine like that in natural caves SSA evaporator units are designed for mounting on the floor making them an ideal choice for quick and convenient installation SSA cooling syste...

Page 6: ...temperatures or lower insulations will cause reducing capacity and the cellar temperature may not be maintained at 55 F The specifications are listed as follows Model No Capacity Btu h Airflow CFM Max...

Page 7: ...ock the keypad SET To enter in the programming mode SET To return to the temperature display 2 Lock and unlock the keys To lock the keys press up down keys until POF is displayed to unlock the keys pr...

Page 8: ...nstrument 2 Temperature Setting Set the temperature at 55 F for the optimum aging of wine On initial start up the time required to reach the desired temperature will vary depending on the quantity of...

Page 9: ...e regulation differential 4 AC anti short cycle delay min 10 hidden Con compress on with probe faulty min 15 CoF compress off with probe faulty min 30 CF temperature unit F C F Fahrenheit rES display...

Page 10: ...ative humidity Use a separate hygrometer to monitor the humidity 10 How to set alarm call 1 Speech notice will be sent to your phones when the cellar temperature is ALU higher or ALL lower than the se...

Page 11: ...ng Clean the condenser coil regularly Coil may need to be cleaned at least every 6 months Use a vacuum cleaner with an extended attachment to clean the coil when it is dusty or dirty 2 Condensate Remo...

Page 12: ...oling unit turns on at 59 F of air temperature It may be higher than 59 F if it is in anti short cycle or defrost and turns off at 55 F of air temperature The average air temperature is 57 F and then...

Page 13: ...rt capacitor overload protector compressor c Call service 9 Compressor running but condenser fan not running a Fan blade stuck b Incorrect or loose wirings c Failed motors d Fan cycle control a Check...

Page 14: ...cessive condensate b High humidity causing excessive condensate c Drain restricted a Check for any air leak b Use drain line c Clean the drip tray and drain line 17 Condensate inside ducts a Drain lin...

Page 15: ...Installation of the system must be done in accordance with all state and local building and electrical codes The condensing unit and evaporator unit are connected by a liquid line and an insulated suc...

Page 16: ...2A 115V 60HZ 6A 20A 42 60 WM 4500SSA LA WM 45SFCA 20 7 8 x 15 5 8 x 25 1 8 17 11 16 x 12 1 16 x 14 x 12 WM 450SCUR LA 18 x 14 x 12 115V 60HZ 2A 115V 60HZ 7A 20A 42 60 WM 6500SSA WM 65SFCA 20 7 8 x 15...

Page 17: ...16 Fig 3 Temperature Controller 4 5 L X 4 5 W X 3 75H Fig 4 WM 25 120SFCA Evaporator Unit...

Page 18: ...17 Fig 5 WM 250 450SCUR Condensing Unit Fig 6 WM 650 1203SCUR Condensing Unit...

Page 19: ...l wires are necessary 18 gauge wires may be used to extend the air probe 3 Evaporator Unit Location 1 WM 25 120SFCA evaporator units shall be installed for floor mount with the supply air at the top a...

Page 20: ...valent Line Set Liquid Line Suction Line Drain Line Recommended Initial Charge WM 2500SSA WM 2500SSA LA 75 FT 1 4 OD 3 8 OD 7 8 MPT R134a 19 OZ WM 4500SSA WM 4500SSA LA 75 FT 1 4 OD 1 2 OD 7 8 MPT R13...

Page 21: ...ng Charging and Starting the System 1 Manifold High or Low Pressure Hose 2 Receiver Discharge or Compressor Suction Port 3 Liquid or Suction Line 4 Pressure Control BACK POSITION FRONT POSITION MIDDLE...

Page 22: ...es to evacuate the system 4 Close the manifold high and low pressure valves and switch it to a charging scale 5 Open the manifold high and low pressure valves to charge the system using the recommende...

Page 23: ...installed at the bottom of the compressor and shall be turned on all the time The heater is self regulated B The condenser fan control The condenser fan control is installed at the high side It close...

Page 24: ...the condensing unit shall be around 10 F The charge may be complete when there are no more bubbles forming in the liquid indicator 4 The head pressure shall be 120 150 psig at 70 90 F condensing unit...

Page 25: ...be in the middle positions Complaint Possible Causes 1 High suction pressure and low head pressure Zero superheat and zero subcooling 2 High suction pressure and low head pressure Low superheat and lo...

Page 26: ...15 low to normal suction pressure and high head pressure Normal to high superheat and high subcooling 7 Undercharge 8 Liquid line restricted after receiver solenoid valve restricted 9 Suction line res...

Page 27: ...he field wirings Use minimum 14 gauge wires for power lines If equipped with low ambient condition kit use low ambient temperature wiring diagrams A safety switch is always recommended for the condens...

Page 28: ...27 Fig 17 WM 2500 4500SSA LA Electrical Wiring Diagram Fig 18 WM 6500 12000SSA Electrical Wiring Diagram...

Page 29: ...28 Fig 19 WM 6500 12000SSA LA Electrical Wiring Diagram...

Page 30: ...and is in lieu of all other warranties express or implied including any of fitness for a particular purpose In no event shall VINOTEMP be responsible for any consequential damages what is so ever Any...

Page 31: ...NOT LIMITED TO IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE While great effort has been made to provide accurate guidelines VINOTEMP cannot warrant its units to properly...

Reviews: