background image

8)  Power Supply Selection 

 

It is important that a suitable power supply is used to run the 
equipment. The power supply selected must have the 
necessary capacity to provide the input current to all of the 
units. 

 

The following table shows the input current taken by the 
various sounders and shows the maximum voltage at which 
the sounders can be operated: 

 

The input current will vary according to the voltage input level 
and the frequency of the tone selected. The current levels 
shown above are for the 440Hz Continuous tone @ nominal 
input voltage.  

 

9)  Selection of Cable. Cable Glands, Blanking 

Elements & Adapters

 

 

When selecting the cable size, consideration must be given 
to the input current that each unit draws (see table above), 
the number of sounders on the line and the length of the 
cable runs. The cable size selected must have the necessary 
capacity to provide the input current to all of the sounders 
connected to the line.  

 

For ambient temperatures over +40ºC the cable entry 
temperature may 70ºC and therefore suitable heat 
resisting cables and cable glands must be used, with a rated 
service temperature of at least 110ºC 

 

The dual cable gland entries have an M20 x 1.5 entry thread. 
To maintain the ingress protection rating and mode of 
protection, the cable entries must be fitted with suitably rated 
ATEX / IECEx certified cable glands and/or suitably rated 
ATEX / IECEx certified blanking devices during installation 
according to EN / IEC60079-14. 

 

If a high IP (Ingress Protection) rating is required then a 
suitable sealing washer must be fitted under the cable glands 
or blanking plugs.  

 

For use in explosive dust atmospheres, a minimum ingress 
protection rating of IP6X must be maintained. 

 

The BEx sounder range can be supplied with the following 
types of adapters: 

 

M20 to ½” NPT 
M20 to ¾” NPT 
M20 to M25 

 

It is important to note that stopping plugs cannot be fitted 
onto adapters, only directly onto the M20 entries. 
Any other adapters used must be suitably rated and ATEX / 
IECEx certified adapters. 

 
 
 
 

10) Earthing 

 

Both AC and DC sounder units must be connected to an 
earth. The units are provided with internal and external earth 
terminals which are both located on the terminal chamber 
section of the unit. 

 

Fig. 3 Internal View of Cover 

 

When using the internal earth terminal ensure that the 
stainless steel M4 flat washer is between the incoming earth 
wire and the enclosure.  

 

Internal earthing connections should be made to the Internal 
Earth terminal in the base of the housing using a ring crimp 
terminal to secure the earth conductor under the earth clamp. 
The earth conductor should be at least equal in size and 
rating to the incoming power conductors. 

 

External earthing connections should be made to the M5 
earth stud, using a ring crimp terminal to secure the earth 
conductor to the earth stud. The external earth conductor 
should be at least 4mm² in size. 

 

11) Cable Connections 

 

Electrical connections are to be made into the terminal blocks 
on the PCBA located in the flameproof enclosure. See 
section 7 of this manual for access to the flameproof 
enclosure.  

 

Wires having a cross sectional area between 0.5 mm² to 
2.5mm² can be connected to each terminal way. If an input 
and output wire is required the 2-off Live/Neutral or +/- 
terminals can be used. If fitting 2-off wires to one terminal 
way the sum of the 2-off wires must be a maximum cross 
sectional area of 2.5mm². Strip wires to 8mm. Wires may also 
be fitted using ferrules. Terminal screws need to be tightened 
down with a tightening torque of 0.45 Nm / 5 Lb-in. When 
connecting wires to the terminals great care should be taken 
to dress the wires so that when the cover is inserted into the 
chamber the wires do not exert excess pressure on the 
terminal blocks. This is particularly important when using 
cables with large cross sectional areas such as 2.5mm². 
 
 
 
 
 
 
 
 
 

Model No. 

Nominal I/P 

Voltage 

Input 

Current 

Max. I/P 

Volts 

BExS110DDC012 12Vdc  195mA  15V 

BExS110DDC024 24Vdc  265mA  30V 

BExS110DDC048 48Vdc  130mA  60V 

BExS110DAC115 

115Vac 

110mA  

126V  

BExS110DAC230 230Vac  56mA  253V 

External Earthing 

Internal 
Earthing 

Internal 
Bonding 
Wire 
Terminal 

2-off M20 
Cable 
Entries

www.acornfiresecurity.com

www.acornfiresecurity.com

Summary of Contents for BExS110D

Page 1: ... Zone 2 Explosive gas atmosphere not likely to occur in normal operation but may be present for short periods Gas Groupings Group IIA Propane Group IIB Ethylene Group IIC Hydrogen and Acetylene up to 55 C ambient Temperature Classification T1 450ºC T2 300ºC T3 200ºC T4 135ºC Area Classification Dust Zone 21 Explosive dust air mixture likely to occur in normal operation Zone 22 Explosive dust air m...

Page 2: ...f the unit The BEx sounder should be secured to any flat surface using the three 7mm fixing holes on the stainless steel U shaped mounting bracket See Figure 1 The required angle can be achieved by loosening the two large bracket screws in the side of the unit which allow adjustment of the sounder in steps of 18 On completion of the installation then two large bracket adjustment screws on the side...

Page 3: ...ified adapters 10 Earthing Both AC and DC sounder units must be connected to an earth The units are provided with internal and external earth terminals which are both located on the terminal chamber section of the unit Fig 3 Internal View of Cover When using the internal earth terminal ensure that the stainless steel M4 flat washer is between the incoming earth wire and the enclosure Internal eart...

Page 4: ...0 AC sounder Stage two S2 Operation Power L and N link the Common C and S2 terminal Dip switch alters stage 2 tone Stage three S3 Operation Power L and N link the Common C and S3 terminals Dip switch alters stage 3 tone Fig 4 AC Terminals 13 DC Wiring A 4 way terminal block is provided on the DC Sounder There are 1 off ve 1 off ve 1 off stage 2 and 1 off stage 3 terminals in total 13 1 Wiring Diag...

Page 5: ...o the left hand marked ve and centre pins For ve switching connect the headers to the right hand marked ve and the centre pins Refer to Fig 7 Fig 7 Stage Switching Polarity 13 4 Line Monitoring On BExS110D DC units dc reverse line monitoring can be used if required All DC sounders have a blocking diode fitted in their supply input lines An end of line monitoring diode or an end of line monitoring ...

Page 6: ...Maintenance Overhaul Repair Maintenance repair and overhaul of the equipment should only be carried out by suitably qualified personnel in accordance with the current relevant standards EN60079 19 IEC60079 19 Explosive atmospheres Equipment repair overhaul and reclamation EN 60079 17 IEC60079 17 Explosive atmospheres Electrical installations inspection and maintenance To avoid a possible ELECTROST...

Page 7: ...ne 5 15 Continuous at 800Hz 0 1 1 1 0 Tone 2 Tone 5 16 Intermittent 660Hz 150mS on 150mS off 1 1 1 1 0 Tone 18 Tone 5 17 Alternating 544Hz 100mS 440Hz 400mS 0 0 0 0 1 Tone 2 Tone 27 18 Intermittent 660Hz 1 8s on 1 8s off 1 0 0 0 1 Tone 2 Tone 5 19 1400Hz to 1600Hz sweep up over 1s 1600Hz to 1400Hz sweep down over 0 5s 0 1 0 0 1 Tone 2 Tone 5 20 Continuous 660Hz 1 1 0 0 1 Tone 2 Tone 5 21 Alternati...

Page 8: ...R P T A P 105 6 106 8 107 4 106 4 106 2 103 6 104 1 105 3 106 8 106 7 105 0 103 3 15 800Hz Continuous 100 1 103 3 105 6 107 6 103 0 100 3 10 2 102 9 105 2 106 8 102 4 99 6 16 660Hz 150mS ON 150mS OFF Intermittent 92 5 93 9 97 9 97 5 92 5 91 5 92 1 94 5 98 5 97 9 93 1 92 2 17 544Hz 100mS 440Hz 400mS NF S 32 001 101 0 102 5 106 5 107 5 103 9 100 7 101 7 102 5 105 7 107 9 103 6 101 5 BExS110D Input V...

Reviews: