- OUT4 on: OUT1, OUT2, OUT3, OUT4, OUT5, OUT6 are configured for roller shutter output,
the other 2 outputs for lighting control;
- OUT5 on: all the relays are used for roller shutter control.
Press one of the buttons from OUT1 to OUT5 to select one of the five options; the correspond-
ing LED below the button will come on.
The settings for the outputs from 6 to 8 however are not exclusive but can be active or not, and
they specify some device behaviour.
- If LED OUT6 is off the "Lights OFF and Roller Shutters DOWN" message is sent to/received
by the bus; if the LED is on, the message is neither sent (the action remains within the
device) nor received. This function is useful, for example, in all installations in which you want
to restrict the shutdown scenario within a room without it being propagated throughout the
system via the bus.
Pressing the OUT6 button changes the status of the LED and so the behaviour of the device;
by default the LED is off and the message is sent and received.
- If LED OUT7 is off, push buttons are managed on the lights inputs with "toggle on the rising
edge". When connecting switches, the inputs need to be set as "toggle on both edges."
Pressing button OUT7 changes the status of the LED and so the inputs go from one opera-
tion to the other; by default the LED is off, and then you can connect push buttons.
- If LED OUT8 is off, the roller shutter outputs are managed as roller s slat; if the LED
is on, they are managed as traditional roller shutters.
Pressing the OUT8 button changes the status of the LED; by default the LED is off, and so
the roller shutter outputs are managed as roller s slat.
Press the
button again to exit and save the chosen configuration.
Operation of a relay for lights control:
if selected for working in "toggle on the rising edge"
mode, when connecting a NO push button (for example art. 20008-19008-14008), the relay is
commanded to toggle (for example, when I1 closes O1 is closed and when I1 is subsequently
closed again O1 is opened); if selected to work in "toggle on both edges" mode, when con-
necting a switch (e.g., art. 20001-19001-14001), the relay is commanded to toggle when the
switch opens and closes.
Operation of 2 relays for roller shutter control
: when the first input is closed for a long time
(e.g., I1) the roller shutter is raised, when the second input is closed for a long time (e.g., I2) the
roller shutter is lowered; closing the inputs for a short time causes the roller shutter to stop if it is
moving, or the slats to rotate if it is stationary (the slats rotate only if the chosen operation is roll-
er s slat via O8). This function requires you to connect a double push button such as, for
example, art. 20066-19066-14066, art. 20062-19062-14062 and art. 20060-19060-14060.
Caution: After installation you need to open and close the roller shutter completely, via the
relevant inputs, for the calibration process.
When input 9 closes, all the relays enabled for lights control are switched off while all the roller
shutters are lowered; in addition the "Lights OFF and roller shutters DOWN" message is sent
over the bus. The device receives the "Lights OFF and roller shutters DOWN", "Lights OFF",
"Roller shutters DOWN" and "Roller shutters UP" messages and switches off all the relays or
closes/opens all the roller shutters.
As the device is not configured it needs some default data:
- roller shutter up and down time = 180 s;
- slats turn time = 2 s;
- behaviour at power on = no change in the status of the actuators;
- delay in scenario activation = a random delay to avoid commanding all the roller shutters at
the same moment when a "Roller shutters DOWN" request arrives.
Hotel Climate.
With this configuration the following functions are available:
- I1 (door contact): when the contact opens relay O1 closes for 30 s (courtesy light).
- I2 (presence in the room): when the contact is closed the O1 relay opens to switch off the
courtesy light and relays O2 (connected for example to the room lights and radio), and O4
(V2 fancoil speed) close for 10 min; it also calls up the Welcome scenario (the scenario is sent
to the bus and intercepted by other 01470.1 devices which perform the same operations).
When the contact is opened, after 10 min, relays O2, O4, O5 open to switch off the fancoil
medium (V2) and maximum (V3) speeds.
- I3 (V1 fancoil speed): when the contact is closed relay O3 closes while when the contact is
opened relay O3 is opened.
- I4 (V2 fancoil speed): when the contact is closed relay O4 closes only if there is a presence
in the room while when the contact is opened relay O4 is opened.
- I5 (V3 fancoil speed): when the contact is closed relay O5 closes only if there is a presence
in the room while when the contact is opened relay O5 is opened.
- I6 (thermostat contact): when the contact is closed relay O6 is closed (output for room
solenoid valve or for summer-winter selector) only if I9 is closed, while when the contact is
opened relay O6 is opened.
- I7 (reset alarm): press quickly (< 2s) to toggle control output O7 (additional bathroom heating)
only if there is a presence in the room, while O7 is always open if there is no longer a pres-
ence. Press for longer (> 5s) to cancel the alarm generated by I8.
- I8 (bathroom alarm): when the contact is closed relay O8 is activated; to deactivate O8 press
and hold down I7.
- I9 (window contact): when the contact is opened the fancoil outputs (O3, O4, O5) and O6 are
deactivated while when it is closed the previous operation is restored.
Hotel Lights.
With this configuration the following functions are available:
- I1 (door contact): when the contact opens relay O1 closes for 30 s (courtesy light).
- I2 (presence in the room): when the contact is closed relays O2 (connected for example to
the room lights and radio), O4 and O5; it also calls up the Welcome scenario (the scenario
is sent to the bus and intercepted by other 01470.1 devices which perform the same oper-
ations). When the contact is opened, after 10 min, relays O2, O3, O4, O5, O6 and O7 open.
- I3 (light 1): when the contact is closed toggle O3 (bathroom light) is controlled only in the case
of presence in the room.
- I4 (light 2): when the contact is closed toggle O4 (bedside table light A) is controlled only in
the case of presence in the room.
- I5 (light 3): when the contact is closed toggle O5 (bedside table light B) is controlled only in
the case of presence in the room.
- I6 (light 4): when the contact is closed toggle O6 (main light) is controlled only in the case of
presence in the room.
- I7 (do not d reset alarm): press quickly (< 2s) to activate or deactivate relay O7 (do not
disturb). Press for longer (> 5s) to cancel the alarm generated by I8.
- I8 (ceiling pull): when the contact is closed relay O8 (bathroom alarm) is activated. To deacti-
vate O8 press and hold down I7.
- I9 (lights off button): when the contact is closed the lights relays O3, O4, O5, O6 open calling
up the scenario “lights OFF and roller shutters DOWN”.
CONFIGURATION WITH BY-ME CONTROL UNIT OR EASYTOOL
PROFESSIONAL.
For full details see the relevant Installer manuals that can be downloaded from the website
www.vimar.com.
MANUAL MANAGEMENT.
Pressing the
button enables the use of the buttons (located on the front of the device) to
actuate the relays. All messages from the bus are ignored. The LEDs below the buttons always
indicate the relay status with the relevant numbering.
CAUTION: If a roller shutter has been connected to a pair of relays, make sure that these
relays have been set to function for roller shutter control and not for lighting control in the
Lights and Roller shutters configuration. Simultaneous relay controls could damage the
roller shutter motor.
• Both in plug&play in the Lights and Roller shutters configuration, and after By-me configura-
tion, each relay that has been set for lighting control (default configuration) is controlled via
the button with the same numbering.
• Both in plug&play in the Lights and Roller shutters configuration and after By-me configura-
tion, the relays set in pairs for roller shutter control are controlled by the buttons on the front
panel with the same numbering for the UP (
), DOWN (
) and STOP functions with reversal
time in the passage from UP to DOWN. For example: a long press on OUT1 raises the roller
shutter connected on O1/O2, a long press on OUT2 lowers the roller shutter connected on
O1/O2, a short press on OUT1 or OUT2 stops the roller shutter or, if the latter is stationary,
turns the slat (if the chosen operation is roller s slat).
• In plug&play in the Hotel Climate configuration each relay is controlled by the button with
the same numbering except outputs 3,4,5 which are interlocked to prevent damage to the
fancoil.
• In plug&play in the Hotel Lights configuration, each relay is controlled by a button with the
same numbering.
In non-manual operation, pressing the relay actuation buttons is ignored.
INSTALLATION RULES.
• Installation should be carried out by qualified personnel in compliance with the current
regulations regarding the installation of electrical equipment in the country where the
products are installed.
• The 4 pairs of relay outputs are separated from each other by functional insulation at 250 V~
and not by double insulation; because of this, for example, do not connect a SELV circuit
to an output that is adjacent to another one that is connected to the 230 V~ power supply.
• The relay output power circuits must be protected against overcurrents by installing devices
or fuses with a rated breaking capacity of 1500 A or type-C circuit breakers, with rated
current not exceeding 16 A.
For the possible installation, please refer to SI-Connection diagrams for the relevant item
code at www.vimar.com -> Products -> Online catalogue.
STANDARD CONFORMITY.
LV directive. EMC directive.
Standards EN 60669-2-5, EN 50491.
WEEE - Information for users
If the crossed-out bin symbol appears on the equipment or packaging, this means the product
must not be included with other general waste at the end of its working life. The user must take
the worn product to a sorted waste center, or return it to the retailer when purchasing a new one.
Products for disposal can be consigned free of charge (without any new purchase obligation) to
retailers with a sales area of at least 400 m
2
, if they measure less than 25 cm. An efficient sorted
waste collection for the environmentally friendly disposal of the used device, or its subsequent
recycling, helps avoid the potential negative effects on the environment and people’s health, and
encourages the re-use and/or recycling of the construction materials.