30
Touch
to return the parameters to their factory values; since this operation cannot be
undone, you will see a confirmation notice and you will need to tap
again.
9.4 Info about the device
This menu lets you view information related to the thermostat and reset the device.
Via
and
you can select:
•
: displays the software version of the device.
• : displays the number of hours that the thermostat relay has been on (the same as the number of
hours of operation of the system).
The counter can be reset, for example at changes in season to differentiate between heating and
air-conditioning, by pressing and holding the
icon.
•
FWuP
: enables starting the procedure for updating the device software. This service requires a Vimar
cloud connection.
- Tap
to learn about the latest software version available for your device; if your device can be
upgraded the
icon will be blinking alongside the new SW version.
- Tap
to start the update from the Vimar cloud and wait until the next time the thermostat is
restarted.
Caution: While updating the SW do not turn off the device, nor access the thermostat with the
By-clima app.
10. Parameters table
Function
Parameters
Value range
Reso-
lution
Default value
Temperature control mode
Selection
TempCtrl
[Heat., Air-con.]
-
Heating
Control algorithm
Algorithm
[ON/OFF, PID]
-
ON/OFF
Hysteresis (ON/OFF)
δ
T
(Differential)
[0.1,..,1]°C
0.1°C
0.2°C
Proportional band (PID)
Band
[0.5,..,5]°C
0.1°C
1°C
Adjustment period (PID)
Period
[10,..,30] minutes
1 min
20 min
External temperature probe
External probe mode
[Off, View,
Temperature Con-
trol, Limitation]
-
OFF
Limitation
T
L
(Temp. limit)
[30,..,50]°C
0.1°C
35°C
Unit of measurement (tem-
perature)
Temperature unit
[°C , °F]
-
°C
Settings menu - Parameters table