7/32
NT00000582-PILOT-PARC-MAITRE-AN-200723
3.3 Maximum connection capacity and tightening torque
Data for rigid, solid conductors.
PILOT PARC versions with 1 Motor
Rated current
HS motor
(max A)
Power supply
Power output
Control terminal block
Max section
(mm²)
Tightening
torque
(Nm)
Max section
(mm²)
Tightening
torque
(Nm)
Max section
(mm²)
Tightening
torque
(Nm)
9
10
0.8
4
1.7
1.5
Automatic
(spring-mounted
terminal blocks)
18
10
0.8
4
2.5
1.5
25
10
0.8
6
2.5
1.5
32
25
3.5
6
2.5
1.5
50
25
3.5
35
5
1.5
65
35
23
35
5
1.5
80
50
23
35
9
1.5
95
50
23
35
9
1.5
115
50
22
50
9
1.5
150
70
22
70
18
1.5
185
95
22
95
35
1.5
225
120
44
120
35
1.5
PILOT PARC versions with 2 Motors
Rated current
HS motor
(max A)
Power supply
Power output
Control terminal block
Max section
(mm²)
Tightening
torque
(Nm)
Max section
(mm²)
Tightening
torque
(Nm)
Max section
(mm²)
Tightening
torque
(Nm)
9
10
0.8
4
1.7
1.5
Automatic
(spring-mounted
terminal blocks)
18
35
2
4
2.5
1.5
25
35
2
6
2.5
1.5
Reports on PILOT PARC SLAVES and active fire protection system:
-
Max section = 2.5mm
2
/ Tightening torque = 1.7Nm
Connection onto Q1E et Q2E outputs:
-
Max section = 1,5mm² / Tightening torque = 0,7Nm.
3.4 Cable gland
Cable diameter tolerance range (mm):
ISO M16
ISO M25
ISO M32
ISO M40
ISO M50
ISO M63
4.5-10
10-17
17-25
22-33
28-38
32-44 or 36-52*
* For PILOT PARC ratings 185 and 225A.
PILOT PARC versions with 1 Motor
Rated current HS motor
(max A)
Power supply
Power output
C
Communication
Type
Number
Type
Number
Type
Number
9
ISO M25
1
ISO M25
2
M16
M25
7
1
18
ISO M25
1
ISO M25
2
25
ISO M32
1
ISO M32
2
32
ISO M32
1
ISO M32
2
50
ISO M40
1
ISO M40
2
65
ISO M50
1
ISO M50
2
80
ISO M50
1
ISO M50
2
95
ISO M63
1
ISO M63
2
115
ISO M63
1
ISO M63
2
150
ISO M63
1
ISO M63
2
185
ISO M63
1
ISO M63
2
225
ISO M63
1
ISO M63
2