6/32
NT00000582-PILOT-PARC-MAITRE-AN-200723
3.
ELECTRICAL CONNECTION
3.1 Power supply
Three-phase 400V 50/60Hz + Earth, according to current standards.
Connect the power supply phases directly on the switch-disconnector and the earth connection conductor
on the specific PE connection strip.
•
If there are ready factory-fitted connections on the switch-disconnector terminals, check that they are
secured after connecting the power supply.
•
The cross-section of the conductor connection must be identical from the motor to the first magnetic
protection encountered upstream (PILOT PARC unit or Low Voltage Main Panel depending on model).
Application of type 1: for an installation in accordance with the regulations,
it is imperative to install elec-
tromagnetic protection on the power supply to the unit of the following type
:
PILOT PARC versions with 1 Motor
Rated current of HS
motor (max A)
Fuse protection
Only magnetic circuit breaker protection
Type
Rating (A)
Type
Rating (A)
3.5
aM 10x38
4
ABB-MO325
4
5.5
6
6.3
11.5
12
12.5
18
20
25
25
32
ABB-MO450
32
32
aM 22x58
40
50
63
65
100
80
125
95
125
115
aM 22x58
125
150
aM T0
160
185
aM T0
200
225
aM T1
250
Shaded cells
= fuses built into PILOT PARC (labelled F3) Otherwise, protection is installed by the in-
staller.
PILOT PARC versions with 2 Motors
Rated current HS motor
(max A)
Protection by fuses built into PILOT PARC (labelled F3 and F4)
Type
Rating (A)
3.5
aM 10x38
4
5.5
6
11.5
12
18
20
25
32
3.2 Motor power output
Connect the motors phases directly on the corresponding thermal relays and the earth conductor(s) on the
specific connection provided for this purpose.
For versions controlling one or several Dahlander motors, check the conductors connecting the KME to the
output of the Rtpv thermal relay once the motor is connected.
Set each thermal relay LS and HS to the corresponding value (s) on the plate of the motor(s) connected.