TECHNICAL DATA

QUICK RESPONSE 

EXTENDED COVERAGE 

CONCEALED HSW 

SPRINKLER VK680 (K8.0)

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

Telephone: 269-945-9501  Technical Services: 877-384-5464  Fax: 269-818-1680  Email: [email protected]

Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com.

Form No. F_050611    18.10.25     Rev 17.1.P65

Page 2 of 5

Ordering Information:

 (Also refer to the current Viking price list.)

Viking QREC Concealed HSW Sprinkler VK680 and Cover Plate Assembly must be ordered separately:

Sprinkler: 

Part No. 17114AC (includes a 165 °F (74 °C) temperature rated sprinkler with a protective plastic cap covering the unit).

Cover Plate Assembly: 

Base Part No. 16207 (3-5/16” diameter)

Specify finish and temperature rating of the cover plate assembly by adding the appropriate suffixes for the finish and the cover 

temperature rating to the base part number:

Finish Suffix: Polished Chrome = F, Painted White = M-/W, Painted Ivory = M-/I, Painted Black = M-/B

Temperature Suffix: 135 °F (57 °C) = A  

For example, cover 16207 with a Polished Chrome finish and a 135 °F (57 °C) temperature rating = 16207FA. 

Available Finishes And Temperature Ratings:

 Refer to Table 1.

Accessories:

 (Also refer to the Viking website.)

Sprinkler Wrenches**:

A. Heavy Duty Wrench Part No. 16208W/R (available since 2010)

B. Head Cabinet Wrench Part Number 16267

***

 (available since 2010) 

C. Optional Large Concealed Cover Plate Installer Tool Part No. 14867 (available since 2007)

 **Requires a ½” ratchet (not available from Viking).

***Ideal for sprinkler cabinets.  

Sprinkler Cabinet: 

Part No. 01731A  (available since 1971)

4.  INSTALLATION

Refer to appropriate NFPA Installation Standards.

5.  OPERATION

During fire conditions, when the temperature around the sprinkler approaches its operating temperature, the cover plate detaches. 

Continued heating of the exposed sprinkler causes the fusible element to disengage, releasing the sealing assembly. Water flowing 

through the sprinkler orifice strikes the flow shaper, forming a uniform spray pattern to extinguish or control the fire.

6.  INSPECTIONS, TESTS AND MAINTENANCE

Refer to NFPA 25 for Inspection, Testing and Maintenance requirements.

7.  AVAILABILITY

The Viking Model VK680 Sprinkler is available through a network of domestic and international distributors. See The Viking 

Corporation web site for the closest distributor or contact The Viking Corporation.

8.  GUARANTEE

For details of warranty, refer to Viking’s current list price schedule or contact Viking directly.

Figure 1:  Identification of Custom Paint for Concealed Covers

FA

C

TO

R

Y

 A

PP

LIE

D CUSTOM

 PA

IN

T C

O

LO

R

All custom color painted cover plates will have an identifying label affixed 

to the inside of the cover that indicates the custom color and will have a 

representative sample (a paint dot) of the paint on the label.

Summary of Contents for VK680

Page 1: ...Listed Category VNIV CCCF Approved Approved by the China Certification Center for Fire Products CCCF Refer to the Approval Chart and Design Criteria on this Technical Data Page for cULus Listing requirements that must be followed 3 TECHNICAL DATA Specifications Available since 2011 Minimum Operating Pressure 7 psi 0 5 bar Maximum Working Pressure 175 psi 12 Bar Factory tested hydrostatically to 50...

Page 2: ...ble since 2010 B Head Cabinet Wrench Part Number 16267 available since 2010 C Optional Large Concealed Cover Plate Installer Tool Part No 14867 available since 2007 Requires a ratchet not available from Viking Ideal for sprinkler cabinets Sprinkler Cabinet Part No 01731A available since 1971 4 INSTALLATION Refer to appropriate NFPA Installation Standards 5 OPERATION During fire conditions when the...

Page 3: ...its may apply depending on fire loading sprinkler location and other requirements of the Authority Having Jurisdiction Refer to specific installation standards 3 Part number shown is the base part number For complete part number refer to current Viking price list schedule Figure 2 Sprinkler VK680 Installation and Correct Use of Wrench The internal design of the sprinkler wrench is shaped to fit ov...

Page 4: ...4 L min 1 72 Bar AX1 AX1 14 x 24 4 3 m x 7 3 m 34 gpm 18 1 psi 128 7 L min 1 25 Bar 4 3 8 112 mm to 6 3 8 162 mm AX1 16 x 24 4 9 m x 7 3 m 39 gpm 23 8 psi 147 6 L min 1 64 Bar AX1 14 x 24 4 3 m x 7 3 m 35 gpm 19 2 psi 132 5 L min 1 32 Bar 6 3 8 162 mm to 12 3 8 314 mm AX1 16 x 24 4 9 m x 7 3 m 40 gpm 25 psi 151 4 L min 1 72 Bar AX1 Sprinkler Temperature Rating A 165 F 74 C Cover Assembly Temperatu...

Page 5: ...ween sprinklers The distance shall be measured perpendicular to the wall The sprinkler installation and obstruction rules contained in NFPA 13 for extended coverage sidewall spray sprinklers must be followed NOTE Concealed sprinklers must be installed in neutral or negative pressure plenums only IMPORTANT Always refer to Bulletin Form No F_091699 Care and Handling of Sprinklers Also refer to Form ...

Reviews: