QUICK RESPONSE 

EXTRA-LARGE ORIFICE 

UPRIGHT SPRINKLER 

VK531 (STORAGE-DENSITY/AREA)

TECHNICAL DATA

Form No. F_120699    18.10.11     Rev 18.2.P65

Page 2 of 5

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

Telephone: 269-945-9501  Technical Services: 877-384-5464  Fax: 269-818-1680  Email: [email protected]

Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com

Finish Suffix: Brass = A, Chrome = F, White Polyester = M-/W, Black Polyester = M-/B, ENT = JN

Temperature Suffix: 155 °F (68 °C) = B, 175 °F (79 °F) = D, 200 °F (93 °C) = E, 286 °F (141 °C) = G, OPEN = Z (PTFE only).

For example, sprinkler VK531 with a Brass finish and a 155 °F (68 °C) temperature rating = Part No. 10633AB

Available Finishes And Temperature Ratings:

 Refer to Table 1.

Accessories:

 (Also refer to the Viking website.)

Sprinkler Wrenches:

A. Standard Wrench: Part No. 05118CW/B (available since 1981). 

B. Wrench for coated sprinklers: Part No. 11663W/B** (available since 2001)

  **A ½” ratchet is required (not available from Viking).

Sprinkler Cabinets:

A. Six-head capacity: Part No. 01724A (available since 1971)

B. Twelve-head capacity: Part No. 01725A (available since 1971)

4.  INSTALLATION

Refer to appropriate NFPA Installation Standards.

5.  OPERATION

During fire conditions, when the temperature around the sprinkler reaches its operating temperature, the heat-sensitive liquid in 

the glass bulb expands, causing the bulb to shatter, releasing the pip cap and sealing spring assembly. Water flowing through the 

sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern to extin- guish or control the fire. 

6.  INSPECTIONS, TESTS AND MAINTENANCE

Refer to NFPA 25 for Inspection, Testing and Maintenance requirements.

7.  AVAILABILITY

The Viking Quick Response Extra-Large Orifice Upright Sprinkler is available through a network of domestic and international dis-

tributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation.

8.  GUARANTEE

For details of warranty, refer to Viking’s current list price schedule or

contact Viking directly.

TABLE 1: AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES

Sprinkler Temperature 

Classification

Sprinkler Nominal

 

Temperature Rating

1

Maximum Ambient

 

Ceiling Temperature

2

Bulb Color

Ordinary

155 °F (68 °C)

100 °F (38 °C)

Red

Intermediate

175 °F (79 °C)

150 °F (65 °C)

Yellow

Intermediate

200 °F (93 °C)

150 °F (65 °C)

Green

High

286 °F (141 °C)

225 °F (107 °C)

Blue

Sprinkler Finishes:

 Brass, Chrome, White Polyester, Black Polyester, and ENT

Corrosion-Resistant Coatings

3

:

 White Polyester, and Black Polyester in all temperature ratings.  ENT in all temperature ratings 

except 135°F (57°C).

Footnotes

1

 The sprinkler temperature rating is stamped on the deflector. 

2

 Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction. 

Refer to specific installation standards.

3

 The corrosion-resistant coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Charts. These 

tests cannot and do not represent all possible corrosive environments. Prior to installation, verify through the end-user that the coatings are compat-

ible with or suitable for the proposed environment. For automatic sprinklers, the coatings indicated are applied to the exposed exterior surfaces only. 

Note that the spring is exposed on sprinklers with Polyester, and ENT. For all ENT coated sprinklers, the waterway is coated.

Summary of Contents for VK531

Page 1: ...red and or used as an open sprinkler glass bulb and pip cap assembly re moved on deluge systems Refer to Ordering Instructions below 2 LISTINGS AND APPROVALS cULus Listed Category VNIV FM Approved Class 2020 VdS Approved Certificate G413059 G413060 LPCB Approved Certificate 096e 14 Refer to Approval Chart 1 and Design Criteria on page 3 for cULus Listing requirements and refer to Approval Chart 2 ...

Page 2: ...r to NFPA 25 for Inspection Testing and Maintenance requirements 7 AVAILABILITY The Viking Quick Response Extra Large Orifice Upright Sprinkler is available through a network of domestic and international dis tributors See The Viking Corporation web site for the closest distributor or contact The Viking Corporation 8 GUARANTEE For details of warranty refer to Viking s current list price schedule o...

Page 3: ...page www vikinggroupinc com Figure 1 Sprinkler VK531 and Wrench Figure 2 Sprinkler VK531 Dimensions 05118CW B 1 3 4 45 mm 2 5 16 59 mm 3 4 NPT 20 mm Protective clip Wrench flat Coated Upright Sprinkler Step 1 Carefully slide the wrench sideways around the deflector ensuring engagement with the sprinkler wrench flats Sprinkler wrench 11663W B must be used for installing coated sprinklers A 1 2 ratc...

Page 4: ...ble shows the listings and approvals available at the time of printing Other approvals may be in process 4 Listed by Underwriters Laboratories Inc for use in the U S and Canada 5 cULus Listed only for use in wet pipe sprinkler systems or preaction systems qualifying as wet systems 6 Meets New York City requirements effective July 1 2008 7 cULus Listed as corrosion resistant DESIGN CRITERIA UL Also...

Page 5: ... time of printing Other approvals may be in process 4 FM Approved as corrosion resistant DESIGN CRITERIA FM Also refer to Approval Chart 2 above FM Approval Requirements Quick Response Extra Large Orifice Upright Sprinkler VK531 is FM Approved as a quick response upright Non Storage sprinkler and as a quick response upright Storage sprinkler as indicated in the FM Approval Guide For specific appli...

Reviews: