background image

QUICK RESPONSE 

EXTRA-LARGE ORIFICE 

UPRIGHT SPRINKLER 

VK531 (STORAGE-DENSITY/AREA)

TECHNICAL DATA

Form No. F_120699    18.10.11     Rev 18.2.P65

Page 1 of 5

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

Telephone: 269-945-9501  Technical Services: 877-384-5464  Fax: 269-818-1680  Email: [email protected]

Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com

1.  DESCRIPTION

The Viking Quick Response Extra-Large Orifice Upright Sprinkler VK531 is a ther-

mosensitive glass bulb spray sprinkler available in several different finishes and 

temperature ratings to meet design requirements. The special Polyester, Electroless 

Nickel PTFE (ENT), and PTFE coatings can be used in decorative applications where 

colors are desired. In addition, these coatings have been investigated for installa-

tion in corrosive environments and are listed/approved as indicated in the Approval 

Charts.
The extra-large orifice provides greater flows at lower pressures than standard 

orifice or large orifice sprinklers. This feature allows reduced pipe sizing for hy-

draulically calculated sprinkler systems, which require high densities of water. 

Viking Standard Response Extra-Large Orifice Sprinklers may eliminate the 

need for a fire pump or reduce the size of the pump if it is required. On existing 

systems, replacing large orifice sprinklers with extra-large orifice sprinklers may 

provide the higher densities required to allow an increase in the hazard classifica-

tion of an occupancy.
Viking Quick Response Extra-Large Orifice Upright Sprinkler VK531 may be 

ordered and/or used as an open sprinkler (glass bulb and pip cap assembly re-

moved) on deluge systems. Refer to 

Ordering Instructions 

below. 

2.  LISTINGS AND APPROVALS

cULus Listed: 

Category VNIV

FM Approved:

 Class 2020

VdS Approved:

 Certificate G413059, G413060

LPCB Approved: 

Certificate 096e/14

Refer to Approval Chart 1 and Design Criteria on page 3 for cULus Listing requirements, and refer to Approval Chart 2 and Design 

Criteria on page 4 for FM Approval requirements that must be followed.

3.  TECHNICAL DATA

Specifications:

Available since 2000.

Maximum Working Pressure: 175 psi (12 bar). Factory tested hydrostatically to 500 psi (34.5 bar).

Thread size: See Approval Charts 

Nominal K-Factor: 11.2 U.S. (161.3 metric

*

)

* Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown 

by 10.0.

Glass-bulb fluid temperature rated to -65 °F (-55 °C)

Overall Length: 2-5/16” (58.7 mm)

Material Standards:

Sprinkler Frame: Brass UNS-C84400

Deflector: Brass UNS-C26000

Bulb: Glass, nominal 3 mm diameter

Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-S30400

Compression Screw: Brass UNS-C36000

Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with Teflon Tape

For Polyester Coated Sprinklers:

 

Belleville Spring-Exposed

For ENT Coated Sprinkler: Belleville Spring-Exposed, Screw and Pipcap-ENT plated.

Ordering Information:

 (Also refer to the current Viking price list.)

Order Quick Response Extra-Large Orifice Upright Sprinkler VK531 by first adding the appropriate suffix for the sprinkler finish 

and then the appropriate suffix for the temperature rating to the sprinkler base part number. 

Replaces Form No. F_120699 Rev 18.2 

(Added P65 Warning.)

  

NOTE: As of May 2018 all logos have been removed from the 

wrench boss.

Summary of Contents for VK531

Page 1: ...red and or used as an open sprinkler glass bulb and pip cap assembly re moved on deluge systems Refer to Ordering Instructions below 2 LISTINGS AND APPROVALS cULus Listed Category VNIV FM Approved Class 2020 VdS Approved Certificate G413059 G413060 LPCB Approved Certificate 096e 14 Refer to Approval Chart 1 and Design Criteria on page 3 for cULus Listing requirements and refer to Approval Chart 2 ...

Page 2: ...r to NFPA 25 for Inspection Testing and Maintenance requirements 7 AVAILABILITY The Viking Quick Response Extra Large Orifice Upright Sprinkler is available through a network of domestic and international dis tributors See The Viking Corporation web site for the closest distributor or contact The Viking Corporation 8 GUARANTEE For details of warranty refer to Viking s current list price schedule o...

Page 3: ...page www vikinggroupinc com Figure 1 Sprinkler VK531 and Wrench Figure 2 Sprinkler VK531 Dimensions 05118CW B 1 3 4 45 mm 2 5 16 59 mm 3 4 NPT 20 mm Protective clip Wrench flat Coated Upright Sprinkler Step 1 Carefully slide the wrench sideways around the deflector ensuring engagement with the sprinkler wrench flats Sprinkler wrench 11663W B must be used for installing coated sprinklers A 1 2 ratc...

Page 4: ...ble shows the listings and approvals available at the time of printing Other approvals may be in process 4 Listed by Underwriters Laboratories Inc for use in the U S and Canada 5 cULus Listed only for use in wet pipe sprinkler systems or preaction systems qualifying as wet systems 6 Meets New York City requirements effective July 1 2008 7 cULus Listed as corrosion resistant DESIGN CRITERIA UL Also...

Page 5: ... time of printing Other approvals may be in process 4 FM Approved as corrosion resistant DESIGN CRITERIA FM Also refer to Approval Chart 2 above FM Approval Requirements Quick Response Extra Large Orifice Upright Sprinkler VK531 is FM Approved as a quick response upright Non Storage sprinkler and as a quick response upright Storage sprinkler as indicated in the FM Approval Guide For specific appli...