ESFR PENDENT SPRINKLER 

UL: SPECIFIC APPLICATION ESFR SPRINKLER 

FM: STORAGE SPRINKLER

NFPA: SPECIAL SPRINKLER  

VK514 (K28.0)

TECHNICAL BULLETIN

Page 1 of 6

Form No. F_102422      Rev 01     October 2022

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

Telephone: 269-945-9501  Technical Services: 877-384-5464  Fax: 269-818-1680  Email: [email protected]

Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com

1.  DESCRIPTION

Viking Early Suppression Fast Response (ESFR) Pendent Sprinkler VK514 

incorporates the capability to suppress specific high-challenge fires. The larger 

K-Factor allows protection of higher hazard commodities at greater ceiling heights 

with lower end-head pressures. K28.0 sprinklers can:

•  Provide flexibility of fire protection designs.

•  Eliminate the use of in-rack sprinklers when protecting high piled storage of 

certain specified materials up to:

UL (Refer to Table 4):

 43 ft. (13,1 m) with ceilings up to 48 ft. (14,6 m)*  

FM (Refer to Table 5):

 50 ft. (15,2 m) with ceilings up to 55 ft. (16,76 m)*  

 

 

  

 

  

      OR

 

 

        45 ft. (13,5 m) with ceilings up to 50 ft. (15,2 m)*

NFPA 13 (Refer to Table 6): 

The VK514 is a

 

Special Sprinkler as defined by 

the National Fire Protection Association (NFPA 13, 2022 Ed.-Section 15.2).

Viking ESFR Pendent Sprinklers VK514 are primarily intended to protect the 

following types of storage, which tend to produce severe-challenge fires: palletized 

and solid pile storage and single, double, and portable open rack storage (no 

open-top containers or solid shelves). The VK514 is listed to utilize a minimum 

aisle width of 6’-0” (UL - 43’ storage or FM - 45’ storage) or 8’-0” (FM - 50’ storage).

Viking ESFR Pendent Sprinklers VK514 provide protection of most common 

storage materials, including: 

•  Encapsulated or unencapsulated Class I, II, III, and IV commodities*.

•  UL Listed for protection of cartoned nonexpanded** Group A plastic 

commodities*.

•  FM Approved for protection of cartoned unexpanded** plastic commodities.*

*  Refer the Approval Chart and Commodity Selection and Design Criteria Overview for Listing  

and Approval requirements that must be followed.

** The terms nonexpanded and unexpanded are equivalent.

2.  LISTINGS AND APPROVALS*

UL Listed:

 Category VNWH (Listed as an ESFR Sprinkler)

FM Approved:

 Class 2035

*  Refer the Approval Chart and Commodity Selection and Design Criteria Overview for Listing  and Approval requirements that must be followed.

3.  PATENT INFORMATION

Please refer to PATVK.COM for all appropriate patents and patent information pertaining to the Model VK514 ESFR Sprinkler.

4.  TECHNICAL DATA

Specifications:

Maximum Working Pressure: 175 psi (12 bar). Factory tested hydrostatically to 500 psi (34.5 bar).

Thread size: 1” NPT or 25 mm BSPT (Refer to Table 2)

Nominal K-factor: 28.0 U.S. (404 metric*)

* Metric K-factor measurement shown is in bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.

Overall Length: 3-3/16” (81 mm)

Deflector Diameter: 1-3/4” (45 mm)

Material Standards:

Frame Casting: Brass UNS-C84400 or CW602N

Deflector: Phosphor Bronze UNS-C51000

Seat: Copper UNS-C11000 and Stainless Steel UNS-S30400

Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE Tape

Compression Screw: Stainless Steel UNS-S31603

Trigger and Support: Stainless Steel UNS-S31600

Fusible Element Assembly: Beryllium nickel coated with a black epoxy, polyurethane (FM only), or acrylic paint

Ordering Information:

 Refer to Table 2

TABLE 1

SPRINKLER GENERAL INFORMATION

Item

Description

Sprinkler Identification 

Number (SIN)

VK514

K-factor, gpm/psi

½

 (lpm/bar

½

)

28.0 (404) 

Thread Size

1” NPT (25 mm)

Sprinkler Orientation

Pendent

Maximum Working Pressure

175 psi (12 bar)

Summary of Contents for VK514

Page 1: ...torage materials including Encapsulated or unencapsulated Class I II III and IV commodities UL Listed for protection of cartoned nonexpanded Group A plastic commodities FM Approved for protection of cartoned unexpanded plastic commodities Refer the Approval Chart and Commodity Selection and Design Criteria Overview for Listing and Approval requirements that must be followed The terms nonexpanded a...

Page 2: ...sequent leakage or impairment of the sprinkler E After installation the entire sprinkler system must be tested The test must be conducted to comply with the Installation Standards Make sure the sprinkler has been properly tightened If a thread leak occurs normally the unit must be removed new pipe joint compound or tape applied and then reinstalled This is due to the fact that when the joint seal ...

Page 3: ... products of combustion but have not operated should be replaced Refer to the Authorities Having Jurisdiction for minimum replacement requirements 8 AVAILABILITY The Viking Model VK514 Sprinkler is available through a network of domestic and international distributors See The Viking Corporation web site for the closest distributor or contact The Viking Corporation 9 GUARANTEE For details of warran...

Page 4: ...PT 28 0 404 3 3 16 81 A1 22894 VK514 1 NPT 28 0 404 3 3 16 81 A1 A1 22958 VK514 25 mm BSPT 28 0 404 3 3 16 81 A1 A1 Approved Temperature Ratings A 165 F 74 C and 205 F 96 C Approved Finish 1 Brass Footnotes 1 Base part number shown For complete part number refer to the price list 2 Metric K Factor measurement shown is when pressure is measured in bar When pressure is measured in kPa divide the met...

Page 5: ...of 4 in 102 mm from walls but no more than 1 2 the allowable distance permitted between sprinklers Deflector distance measured from ceiling to sprinkler deflector Minimum of 36 in 914 mm Sprinkler installation from ceiling For all building heights 6 14 in 152 356 mm Maximum Ceiling Height 48 ft 14 6 m Maximum Storage Height 43 ft 13 1 m Storage Arrangement Single and double row rack storage no ope...

Page 6: ...g Sprinkler Installation Guidelines As per FM 2 0 DS 2 0 Installation Guidelines for Automatic Sprinklers with the following exception Vertical distance from underside of the ceiling to the centerline of the sprinkler s thermal element no more than 13 inches 325 mm As per FM 2 0 DS 2 0 Installation Guidelines for Automatic Sprinklers with the following exception Vertical distance from underside of...