background image

TECHNICAL DATA

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

Telephone: 269-945-9501  Technical Services: 877-384-5464  Fax: 269-818-1680  Email: [email protected]

SPRINKLER OVERVIEW

Page 1 of 3

Form No. F_080814       18.12.06       Rev 14.1.P65

1.  DESCRIPTION

Viking fire sprinklers consist of a threaded frame with a specific waterway or orifice size and a deflector for distributing water in a 

specified pattern. A closed or sealed sprinkler refers to a complete assembly, including the thermosensitive operating element. An 

open sprinkler does not use an operating element and is open at all times. The distribution of water is intended to extinguish a fire 

or to control its spread.
Viking sprinklers are available in several models and styles. Refer to specific sprinkler technical data pages for available styles, 

finishes, temperature ratings, thread sizes, and nominal K-Factors for the particular model selected.

2.  LISTINGS AND APPROVALS

Refer to the Approval Charts on the appropriate sprinkler technical data page(s) and/or 

approval agency listings.

3.  TECHNICAL DATA

Pressure Ratings:

Maximum allowable water working pressure is 175 psig (12 Bar) unless rated and specified for high water working pressure [250 

psig (17.2 bar)]. 

Sprinkler Identification:

 

Viking sprinklers are identified and marked with the word “Viking”, the sprinkler identification number (SIN) consisting of “VK” plus 

a three digit number*, the model letter, and the year of manufacture.

Available Finishes:

 

Viking sprinklers are available in several decorative finishes. Some models are available with corrosion-resistant coatings or are 

fabricated from non-corrosive material. Refer to the sprinkler technical data page for additional information.

Available Temperature Ratings:

Viking sprinklers are available in several temperature ratings that relate to a specific temperature classification. Applicable installa-

tion rules mandate the use and limitations of each temperature classification. In selecting the appropriate temperature classifica-

tion, the maximum expected ceiling temperature must be known. When there is doubt as to the maximum temperature at the 

sprinkler location, a maximum-reading thermometer should be used to determine the temperature under conditions that would 

show the highest readings to be expected. In addition, recognized installation rules may require a higher temperature classifica-

tion, depending upon sprinkler location, occupancy classification, commodity classification, storage height, and other hazards. In 

all cases, the maximum expected ceiling temperature dictates the lowest allowable temperature classification. Sprinklers located 

immediately adjacent to a heat source may require a higher temperature rating.

K-Factors:

Viking sprinklers are available in several orifice sizes with related K-Factors. The orifice is a tapered waterway and, therefore, the 

K-Factor given is nominal. Nominal U.S. K-Factors are provided in accordance with the 1999 edition of NFPA 13, Section 3-2.3. 

Refer to the specific data page for appropriate K-Factor information. 

Available Styles:

Viking sprinklers are available for installation in several positions as indicated by a stamping on the deflector. The deflector style 

dictates the appropriate installation position of the sprinkler; it breaks the solid stream of water issuing from the sprinkler orifice to 

form a specific spray pattern. The following list indicates the various styles and identification of Viking sprinklers.

UPRIGHT SPRINKLER: A sprinkler intended to be installed with the deflector above the frame so water flows upward through the 

orifice, striking the deflector and forming an umbrella-shaped spray pat-

tern downward. Marked “SSU” (Standard Sprinkler Upright) or “UPRIGHT” 

on the deflector.

PENDENT SPRINKLER:

 

A sprinkler intended to be oriented with the deflec-

tor below the frame so water flows downward through the orifice, striking 

the deflector and forming an umbrella-shaped spray pattern downward. 

Marked “SSP” (Standard Sprinkler Pendent) or “PENDENT” on the de-

flector.

CONVENTIONAL SPRINKLER: An “old style” sprinkler intended to be installed with the deflector in either the upright or pendent 

position. The deflector provides a spherical type pattern with 40 to 60 percent of the water initially directed downward and a 

proportion directed upward. Must be installed in accordance with installation rules for conventional or old style sprinklers. DO 

NOT USE AS A REPLACEMENT FOR STANDARD SPRAY SPRINKLERS. Marked “C U/P” (Conventional Upright/Pendent) on 

the deflector.

Viking Technical Data may be found on 

The Viking Corporation’s Web site at 

http://www.vikinggroupinc.com.

The Web site may include a more recent 

edition of this Technical Data Page.

Replaces Form No. F_080814 Rev 14.1

(Added P65 Warning.)

Summary of Contents for VK512

Page 1: ...re differentials in the area around the sprinkler Condensation can lead to ice build up which could inhibit sprinkler operation or cause premature operation 2 LISTINGS AND APPROVALS FM Approved Class 2026 Refer to the Approval Chart and Design Criteria for requirements that must be followed 3 TECHNICAL DATA Specifications Available since 2022 Tube diameter 1 11 16 43 86 mm Minimum Operating Pressu...

Page 2: ...g This sprinkler is to be installed into an area with a maximum ambient temperature of 100 F 38 C meaning if the area will experience temperatures above the maximum ambient rating you shall use a higher temperature rated sprinkler TABLE 1 BASE PART NUMNBER 1 Available Part Numbers and Styles Base Part Number Nominal Length L Connection Style Connection Size 24850A 191 2 495 mm Grooved 11 2 24853A ...

Page 3: ... must be provided with adequate heat NOTICE Viking ESFR Dry Sprinklers shall be installed into the 1 1 2 grooved run of tee fittings that meet the dimensional require ments of ANSI B16 3 Class 150 The VK512 can be installed into welded outlets that meet the dimensional requirements of ANSI B16 11 WARNING Viking sprinklers are manufactured and tested to meet the rigid requirements of the approving ...

Page 4: ...5 Lubricate or seal the gaskets on the grroved coupling as necessary 6 Secure the sprinkler in place with a suitable grooved coupling 7 Clean the contact surfaces for the insulating boot NOTE When installing insulating boots pilot holes are required in metallic ceilings 8 Carefully pull apart the rubber rings A to install onto the barrel 9 Place the 2 halves of the seal casing B on either side of ...

Page 5: ...atest edition of this technical data page www vikinggroupinc com Page 5 of 8 Form No F_071221 Rev 001 12 10 2021 Fill space with one part expandable foam Fill space with one part expandable foam Figure 3 Recommended Sealing Methods Option 1 Option 3 Option 2 8 Jacket insulation maximum above deck penetration 6 Minimum Exposed Length at connection Insulated ceiling structure Minimum 31 2 clearance ...

Page 6: ...4 Maintain a minimum 12 300 mm vertical distance between the top of the area s ceiling and the overhead sprinkler piping that will feed the dry pendent sprinklers 5 5 2 NFPA Requirement for Minimum Exposed Barrel Lengths Refer to the latest edition of NFPA 13 Where dry sprinklers are connected to wet pipe sprinkler systems protecting areas subject to freezing temperatures the minimum exposed lengt...

Page 7: ...ble at the time of printing Other approvals may be in process IMPORTANT Refer to Bulletin Form No F_091699 Care and Handling of Sprinklers Also refer to Table 2 TABLE 4 COMMODITY SELECTION AND DESIGN CRITERIA OVERVIEW FOR MODEL VK512 ESFR PENDENT SPRINKLERS Storage Type NFPA FM Sprinkler Type ESFR Storage Response Type ESFR QR System Type Wet Pipe system only Wet Pipe system only Temperature Ratin...

Page 8: ...ons may vary due to corrosive atmospheres water supplies and activity around the device B Sprinklers that have been painted or mechanically damaged must be replaced immediately Sprinklers showing signs of corrosion shall be tested and or replaced immediately as required Installation standards require sprinklers to be tested and if necessary replaced after a specified term of service Refer to the i...

Page 9: ...stall sprinklers onto piping at the floor level Install sprinklers after the piping is in place to prevent mechanical damage DO NOT allow impacts such as hammer blows directly to sprinklers or to fittings pipe or couplings in close proximity to sprinklers Sprinklers can be damaged from direct or indirect impacts DO NOT attempt to remove drywall paint etc from sprinklers Take care not to over tight...

Page 10: ...D CAPS MUST BE REMOVED FROM SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE Figure 1 Sprinkler shield being removed from a pendent sprinkler Figure 2 Sprinkler cap being removed from a pendent sprinkler Figure 3 Sprinkler cap being re moved from and upright sprinkler HOW TO REMOVE SHIELDS AND CAPS No tools are necessary to remove the shields or caps from sprinklers DO NOT use any sharp objects to ...

Page 11: ... these sprinklers NOTE The protective cap is temporarily removed during installation and then placed back on the sprinkler for protection until finish work is completed Do not over tighten the sprinklers into fittings during installation Do not use the sprinkler deflector to start or thread the sprinklers into fittings during installation Do not attempt to remove drywall paint etc from the sprinkl...

Page 12: ...t the corrosion resistant properties of the sprinkler Use care when locating sprinklers near fixtures that can generate heat Do not install sprinklers where they would be exposed to temperatures exceed ing the maximum recommended ambient temperature for the temperature rating used Inspect the coated sprinklers frequently soon after installation to verify the integrity of the corrosion resistant co...

Page 13: ...t readings to be expected In addition recognized installation rules may require a higher temperature classifica tion depending upon sprinkler location occupancy classification commodity classification storage height and other hazards In all cases the maximum expected ceiling temperature dictates the lowest allowable temperature classification Sprinklers located immediately adjacent to a heat sourc...

Page 14: ...ly intended for installation with a concealed piping system The assembly con sists of a sprinkler installed in a decorative adjustable recessed escutcheon that minimizes the protrusion of the sprinkler beyond the ceiling or wall without adversely affecting the sprinkler distribution or sensitivity Refer to the appropriate technical data page for allowable sprinkler models temperature ratings and o...

Page 15: ...TENANCE Refer to NFPA 25 for Inspection Testing and Maintenance requirements 7 AVAILABILITY Viking sprinklers are available through a network of domestic and international distributors See The Viking Corporation web site for the closest distributor or contact The Viking Corporation 8 GUARANTEE For details of warranty refer to Viking s current list price schedule or contact Viking directly IMPORTAN...

Page 16: ...ction of fire protection products are provided herin as they relate to legally mandated jurisdictional regions WARNING STATE OF CALIFORNIA USA Installing or servicing fire protection products such as sprinklers valves piping etc can expose you to chemicals including but not li mited to lead nickel butadiene titaninum dioxide chromium carbon black and acrylonitrile which are known to the State of C...

Reviews: