background image

ESFR DRY PENDENT SPRINKLER 

VK512 K25.2 (GROOVED)

TECHNICAL DATA

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

Telephone: 269-945-9501  Technical Services: 877-384-5464  Fax: 269-818-1680  Email: [email protected]

Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com

Page 8 of 8

Form No. F_071221    Rev 001    12.10.2021

New form.

After Installation:

1.  The entire sprinkler system must be tested. The test must be conducted to comply with the Installation Standards. Make sure 

the sprinkler has been properly tightened. Repair any leaks as necessary. Air testing the sprinkler piping prior to testing with 

water may be considered in areas where leakage during testing must be prevented. Refer to the appropriate technical data and 

the AHJ prior to air testing the sprinkler piping. Immediately replace any damaged units.

2.  After installation and testing and repairing of all leaks, remove the protective shields from the sprinklers by hand. 

Do NOT

 

use any type of tool to remove the shield. When removing shields, use care to prevent damaging sprinkler fusible element.  

NOTICE: THE SHIELDS MUST BE REMOVED FROM SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE!

3.  System design must be based on ESFR design guidelines described in the latest standards and the Authorities Having 

Jurisdiction. All requirements of recognized ESFR storage sprinkler system design standards apply to systems utilizing Viking 

ESFR Dry Pendent Sprinklers.

6.  OPERATION

During fire conditions, the heat-sensitive fusible element assembly disengages, releasing the internal parts to open the waterway. 

Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern to suppress the fire.

7.  INSPECTIONS, TESTS AND MAINTENANCE

 NOTICE

 

The owner is responsible for maintaining the fire protection system and devices in proper operating condition. For 

minimum maintenance and inspection requirements, refer to NFPA 25 or FM 2-81 for Inspection, Testing and Maintenance 

requirements. In addition, the Authority Having Jurisdiction may have additional maintenance requirements that must be 

followed.

A.  The sprinklers must be inspected on a regular basis for corrosion, mechanical damage, obstructions, paint, etc. The frequency 

of inspections may vary due to corrosive atmospheres, water supplies, and activity around the device.

B.  Sprinklers that have been painted or mechanically damaged must be replaced immediately. Sprinklers showing signs of 

corrosion shall be tested and/or replaced immediately as required. Installation standards require sprinklers to be tested and, if 

necessary, replaced after a specified term of service. Refer to the installation standards and the Authority Having Jurisdiction 

for the specified period of time after which testing and/or replacement is required. Sprinklers that have operated cannot be 

reassembled or reused, but must be replaced. When replacing sprinklers, use only new sprinklers.

C.  The sprinkler discharge pattern is critical for proper fire protection. Nothing should be hung from the sprinkler, attached to it, or 

otherwise obstruct the discharge pattern. All obstructions must be immediately removed or, if necessary, additional sprinklers 

installed.

D.  When replacing existing sprinklers, the system must be removed from service. Refer to the appropriate system description 

and/or valve instructions. Prior to removing the system from service, notify all Authorities Having Jurisdiction. Consideration 

should be given to employment of a fire patrol in the affected area.

1.  Remove the system from service, drain all water, and relieve all pressure on the piping.

2.  Remove the ESFR dry sprinkler insulating boot assemblies.

3.  Remove the old sprinkler and install the new unit. Care must be taken to ensure that the replacement sprinkler is the proper 

model and style, with the correct orifice size, temperature rating, and response characteristics. 

4.  Install new ESFR dry sprinkler boot assemblies.

5.  Place the system back in service and secure all valves. Check the replaced sprinklers and repair all leaks.

E.  Sprinkler systems that have been subject to a fire must be returned to service as soon as possible. The entire system must be 

inspected for damage and repaired or replaced as necessary. Sprinklers that have been exposed to corrosive products of combustion, 

but have not operated, should be replaced. Refer to the Authorities Having Jurisdiction for minimum replacement requirements.

8.  AVAILABILITY

Viking Sprinklers are available through a network of domestic and international distributors. See The Viking Corporation web site for 

the closest distributor or contact The Viking Corporation.

9.  GUARANTEE

For details of warranty, refer to Viking’s current list price schedule or contact Viking directly.

Summary of Contents for VK512

Page 1: ...re differentials in the area around the sprinkler Condensation can lead to ice build up which could inhibit sprinkler operation or cause premature operation 2 LISTINGS AND APPROVALS FM Approved Class 2026 Refer to the Approval Chart and Design Criteria for requirements that must be followed 3 TECHNICAL DATA Specifications Available since 2022 Tube diameter 1 11 16 43 86 mm Minimum Operating Pressu...

Page 2: ...g This sprinkler is to be installed into an area with a maximum ambient temperature of 100 F 38 C meaning if the area will experience temperatures above the maximum ambient rating you shall use a higher temperature rated sprinkler TABLE 1 BASE PART NUMNBER 1 Available Part Numbers and Styles Base Part Number Nominal Length L Connection Style Connection Size 24850A 191 2 495 mm Grooved 11 2 24853A ...

Page 3: ... must be provided with adequate heat NOTICE Viking ESFR Dry Sprinklers shall be installed into the 1 1 2 grooved run of tee fittings that meet the dimensional require ments of ANSI B16 3 Class 150 The VK512 can be installed into welded outlets that meet the dimensional requirements of ANSI B16 11 WARNING Viking sprinklers are manufactured and tested to meet the rigid requirements of the approving ...

Page 4: ...5 Lubricate or seal the gaskets on the grroved coupling as necessary 6 Secure the sprinkler in place with a suitable grooved coupling 7 Clean the contact surfaces for the insulating boot NOTE When installing insulating boots pilot holes are required in metallic ceilings 8 Carefully pull apart the rubber rings A to install onto the barrel 9 Place the 2 halves of the seal casing B on either side of ...

Page 5: ...atest edition of this technical data page www vikinggroupinc com Page 5 of 8 Form No F_071221 Rev 001 12 10 2021 Fill space with one part expandable foam Fill space with one part expandable foam Figure 3 Recommended Sealing Methods Option 1 Option 3 Option 2 8 Jacket insulation maximum above deck penetration 6 Minimum Exposed Length at connection Insulated ceiling structure Minimum 31 2 clearance ...

Page 6: ...4 Maintain a minimum 12 300 mm vertical distance between the top of the area s ceiling and the overhead sprinkler piping that will feed the dry pendent sprinklers 5 5 2 NFPA Requirement for Minimum Exposed Barrel Lengths Refer to the latest edition of NFPA 13 Where dry sprinklers are connected to wet pipe sprinkler systems protecting areas subject to freezing temperatures the minimum exposed lengt...

Page 7: ...ble at the time of printing Other approvals may be in process IMPORTANT Refer to Bulletin Form No F_091699 Care and Handling of Sprinklers Also refer to Table 2 TABLE 4 COMMODITY SELECTION AND DESIGN CRITERIA OVERVIEW FOR MODEL VK512 ESFR PENDENT SPRINKLERS Storage Type NFPA FM Sprinkler Type ESFR Storage Response Type ESFR QR System Type Wet Pipe system only Wet Pipe system only Temperature Ratin...

Page 8: ...ons may vary due to corrosive atmospheres water supplies and activity around the device B Sprinklers that have been painted or mechanically damaged must be replaced immediately Sprinklers showing signs of corrosion shall be tested and or replaced immediately as required Installation standards require sprinklers to be tested and if necessary replaced after a specified term of service Refer to the i...

Page 9: ...stall sprinklers onto piping at the floor level Install sprinklers after the piping is in place to prevent mechanical damage DO NOT allow impacts such as hammer blows directly to sprinklers or to fittings pipe or couplings in close proximity to sprinklers Sprinklers can be damaged from direct or indirect impacts DO NOT attempt to remove drywall paint etc from sprinklers Take care not to over tight...

Page 10: ...D CAPS MUST BE REMOVED FROM SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE Figure 1 Sprinkler shield being removed from a pendent sprinkler Figure 2 Sprinkler cap being removed from a pendent sprinkler Figure 3 Sprinkler cap being re moved from and upright sprinkler HOW TO REMOVE SHIELDS AND CAPS No tools are necessary to remove the shields or caps from sprinklers DO NOT use any sharp objects to ...

Page 11: ... these sprinklers NOTE The protective cap is temporarily removed during installation and then placed back on the sprinkler for protection until finish work is completed Do not over tighten the sprinklers into fittings during installation Do not use the sprinkler deflector to start or thread the sprinklers into fittings during installation Do not attempt to remove drywall paint etc from the sprinkl...

Page 12: ...t the corrosion resistant properties of the sprinkler Use care when locating sprinklers near fixtures that can generate heat Do not install sprinklers where they would be exposed to temperatures exceed ing the maximum recommended ambient temperature for the temperature rating used Inspect the coated sprinklers frequently soon after installation to verify the integrity of the corrosion resistant co...

Page 13: ...t readings to be expected In addition recognized installation rules may require a higher temperature classifica tion depending upon sprinkler location occupancy classification commodity classification storage height and other hazards In all cases the maximum expected ceiling temperature dictates the lowest allowable temperature classification Sprinklers located immediately adjacent to a heat sourc...

Page 14: ...ly intended for installation with a concealed piping system The assembly con sists of a sprinkler installed in a decorative adjustable recessed escutcheon that minimizes the protrusion of the sprinkler beyond the ceiling or wall without adversely affecting the sprinkler distribution or sensitivity Refer to the appropriate technical data page for allowable sprinkler models temperature ratings and o...

Page 15: ...TENANCE Refer to NFPA 25 for Inspection Testing and Maintenance requirements 7 AVAILABILITY Viking sprinklers are available through a network of domestic and international distributors See The Viking Corporation web site for the closest distributor or contact The Viking Corporation 8 GUARANTEE For details of warranty refer to Viking s current list price schedule or contact Viking directly IMPORTAN...

Page 16: ...ction of fire protection products are provided herin as they relate to legally mandated jurisdictional regions WARNING STATE OF CALIFORNIA USA Installing or servicing fire protection products such as sprinklers valves piping etc can expose you to chemicals including but not li mited to lead nickel butadiene titaninum dioxide chromium carbon black and acrylonitrile which are known to the State of C...

Reviews: