ESFR PENDENT 

SPRINKLER VK510 (K25.2)

TECHNICAL DATA

Page 4 of 7

Form No. F_100102   20.01.23    Rev 20.1

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

Telephone: 269-945-9501  Technical Services: 877-384-5464  Fax: 269-818-1680  Email: [email protected]

Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com

AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES

Sprinkler Temperature 

Classification

Sprinkler Nominal 

Temperature Rating

1

Maximum Ambient 

Ceiling Temperature

2

Frame Paint Color

Ordinary

165 °F (74 °C)

100 °F (38 °C)

None

Intermediate

205 °F (96 °C)

150 °F (65 °C)

White

Sprinkler Finish:

 Brass

Footnotes

1

 The sprinkler temperature rating is stamped on the deflector. 

2

 Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction. 

Refer to specific installation standards.

Figure 1:  

ESFR Pendent Sprinkler Wrench

Wrench Flat

Protective 

Sprinkler Cap

Use Side B for 

ESFR Pendent 

K25.2 Sprinkler  

VK510

Figure 2:  

ESFR Pendent Sprinkler VK510 Dimensions

Dimensions are 

approximate.

3-3/16” 

(81 mm)

1-9/16” 

(40 mm)

1-5/8” 

(42 mm)

1-3/4” 

(45 mm)

Summary of Contents for VK510

Page 1: ...M Approved for protection of exposed expanded polystyrene and ex posed expanded polyurethane commodities In addition some storage arrangements of rolled paper flammable liquids aerosols and rubber tires may be protected by Viking ESFR Pendent Sprinkler VK510 2 LISTINGS AND APPROVALS cULus Listed Category VNWH Listed as a Specific Application ESFR Sprinkler FM Approved Class 2026 VdS Approved Certi...

Page 2: ...emperature rating and response characteristics C With the sprinkler contained in the plastic protective cap apply a small amount of pipe joint compound or tape to the male threads only while taking care not to allow a build up of compound in the sprinkler orifice D Use ONLY sprinkler wrench 13635W B shown in Figure 1 for installing ESFR Sprinkler VK510 With the sprinkler contained in the protectiv...

Page 3: ...ttern is critical for proper fire protection Therefore nothing should be hung from attached to or otherwise obstruct the discharge pattern All obstructions must be immediately removed or if necessary additional sprinklers installed D When replacing existing sprinklers the system must be removed from service Refer to the appropriate system description and or valve instructions Prior to removing the...

Page 4: ...rature Rating1 Maximum Ambient Ceiling Temperature2 Frame Paint Color Ordinary 165 F 74 C 100 F 38 C None Intermediate 205 F 96 C 150 F 65 C White Sprinkler Finish Brass Footnotes 1 The sprinkler temperature rating is stamped on the deflector 2 Based on NFPA 13 Other limits may apply depending on fire loading sprinkler location and other requirements of the Authority Having Jurisdiction Refer to s...

Page 5: ...n is when pressure is measured in bar When pressure is measured in kPa divide the metric K Factor shown by 10 0 3 This chart shows listings and approvals available at the time of printing Other approvals may be in process 4 Refer to the latest standards of NFPA 13 FM Global Loss Prevention Data Sheets LPCB Loss Prevention Standards and the latest VdS standards 5 Listed by Underwriters Laboratories...

Page 6: ...PA 13 Refer to FM 2 0 and 8 9 Solid Pile or Palletized Storage of Class I IV and Group A or B Plastics Refer to NFPA 13 Refer to FM 2 0 and 8 9 Idle Pallet Storage Refer to NFPA 13 Refer to FM 2 0 8 9 and 8 24 Rubber Tire Storage Refer to NFPA 13 Refer to FM 2 0 and 8 3 Rolled Paper Storage Refer to the standard Refer to NFPA 13 Refer to FM 8 21 Flammable Liquid Storage Refer to the standard Refer...

Page 7: ... Refer to FM 8 9 Section 2 3 3 3 Deflector Distance from Walls Minimum of 4 in 102 mm from walls but no more than 1 2 the allowable distance permitted between sprinklers Refer to FM 2 0 Section 2 2 3 3 Deflector to Top of Storage Minimum of 36 in 914 mm Minimum of 36 inches 914 mm Refer to FM 2 0 Section 2 2 2 1 and FM 8 9 Section 2 2 6 Deflector to Ceiling Distance Ceiling roof heights up to 40 f...

Reviews: