TABLE 3:

COMMODITY SELECTION AND DESIGN CRITERIA OVERVIEW FOR MODEL VK510 

SPECIFIC APPLICATION LISTING (UL) AND 

ESFR, QUICK RESPONSE STORAGE, AND QUICK RESPONSE NON-STORAGE APPROVALS (FM)

Description

Specification, UL

Specification, FM

Sprinkler Type

ESFR

QR Storage

Temperature Rating

165 ºF (74 ºC) and 205 (96 ºC)

165 ºF (74 ºC) and 205 (96 ºC)

Response Type

ESFR

QR

Sprinkler Position

Pendent, frame arms aligned with pipe, deflectors 

parallel with ceiling or roof

Pendent, frame arms aligned with pipe, deflectors 

parallel to floor.

System Type

Wet Pipe System only

Wet Pipe System only

Maximum Area of Coverage

100 ft

(9.3 m

2

)

100 ft

Refer to FM 2-0, Table 17

Minimum Area of Coverage

64 ft

(5.9 m

2

)

64 ft

2

 (5.9 m

2

)

 

Refer to FM 2-0, Table 17

Maximum Ceiling Slope

2 in 12 

Up to 10° 

Refer to FM 2-0, Section 2.2.1.6

Maximum Spacing

10 ft. spacing (3.0 m)

Up to 30 ft.: 12 ft. (3.7 m)
For building over 30 ft.: 10 ft. (3.0 m)
Refer to FM 8-9, Section 2.3.3.3

Minimum Spacing

8 ft. spacing (2.4 m)

Refer to FM 8-9, Section 2.3.3.3

Deflector Distance from 

Walls

Minimum of 4 in. (102 mm) from walls but no more than 

1/2 the allowable distance permitted between sprinklers

Refer to FM 2-0, Section 2.2.3.3

Deflector to Top of Storage

Minimum of 36 in. (914 mm)

Minimum of 36 inches (914 mm) 

Refer to FM 2-0 Section 2.2.2.1 

and FM 8-9, Section 2.2.6

Deflector** to Ceiling 

Distance

Ceiling/roof heights up to 40 ft. (12.2 m): 
6–18 in. (152–457 mm)
Ceiling/roof heights of 40–45 ft. (12.2–13.7 m): 
6–14 in. (152–356 mm)

Refer to FM 2-0

Maximum Ceiling Height

45 ft. (13.7 m)

50 ft. (15.2 m)

Maximum Storage Height

40 ft. (12.2 m)

45 ft. (13.7 m)

Storage Arrangement

Palletized, solid piled, open frame; single row, double 

row, or multiple row and portable rack arrangement

Refer to FM 8-9, Tables 2 through 11

Commodity

Class I-IV, Cartoned unexpanded plastic

Refer to FM 8-1 and 8-9

Sprinkler System Design

NFPA 13 for ESFR Sprinklers based upon 40 psi  

(2.8 bar) design pressure 159.4 gpm (603.4 lpm) with 12 

sprinkler remote area

Refer to FM 8-9, Tables 2 through 11

Obstruction Criteria

Refer to NFPA 13 Chapter 8.

Refer to FM 2-0 Section 2.2

Minimum Aisle Width

3 ft.-6 in. (1.07 m)

Over 2 ft. (.61 m)

Hose  Stream  Allowance  and                                      

Water Supply Duration

250 gpm (946 lpm) for 60 minutes or as determined by 

the approval

250 gpm (946 lpm) for 60 minutes or as determined by 

the approval

* The maximum coverage area must not exceed 100 ft

2

.

** For FM, the measurement is from the centerline of the thermal sensing element to the ceiling.

Replaces Form No F_100102 Rev 19.2

(Revised FM Specification)

Summary of Contents for VK510

Page 1: ...M Approved for protection of exposed expanded polystyrene and ex posed expanded polyurethane commodities In addition some storage arrangements of rolled paper flammable liquids aerosols and rubber tires may be protected by Viking ESFR Pendent Sprinkler VK510 2 LISTINGS AND APPROVALS cULus Listed Category VNWH Listed as a Specific Application ESFR Sprinkler FM Approved Class 2026 VdS Approved Certi...

Page 2: ...emperature rating and response characteristics C With the sprinkler contained in the plastic protective cap apply a small amount of pipe joint compound or tape to the male threads only while taking care not to allow a build up of compound in the sprinkler orifice D Use ONLY sprinkler wrench 13635W B shown in Figure 1 for installing ESFR Sprinkler VK510 With the sprinkler contained in the protectiv...

Page 3: ...ttern is critical for proper fire protection Therefore nothing should be hung from attached to or otherwise obstruct the discharge pattern All obstructions must be immediately removed or if necessary additional sprinklers installed D When replacing existing sprinklers the system must be removed from service Refer to the appropriate system description and or valve instructions Prior to removing the...

Page 4: ...rature Rating1 Maximum Ambient Ceiling Temperature2 Frame Paint Color Ordinary 165 F 74 C 100 F 38 C None Intermediate 205 F 96 C 150 F 65 C White Sprinkler Finish Brass Footnotes 1 The sprinkler temperature rating is stamped on the deflector 2 Based on NFPA 13 Other limits may apply depending on fire loading sprinkler location and other requirements of the Authority Having Jurisdiction Refer to s...

Page 5: ...n is when pressure is measured in bar When pressure is measured in kPa divide the metric K Factor shown by 10 0 3 This chart shows listings and approvals available at the time of printing Other approvals may be in process 4 Refer to the latest standards of NFPA 13 FM Global Loss Prevention Data Sheets LPCB Loss Prevention Standards and the latest VdS standards 5 Listed by Underwriters Laboratories...

Page 6: ...PA 13 Refer to FM 2 0 and 8 9 Solid Pile or Palletized Storage of Class I IV and Group A or B Plastics Refer to NFPA 13 Refer to FM 2 0 and 8 9 Idle Pallet Storage Refer to NFPA 13 Refer to FM 2 0 8 9 and 8 24 Rubber Tire Storage Refer to NFPA 13 Refer to FM 2 0 and 8 3 Rolled Paper Storage Refer to the standard Refer to NFPA 13 Refer to FM 8 21 Flammable Liquid Storage Refer to the standard Refer...

Page 7: ... Refer to FM 8 9 Section 2 3 3 3 Deflector Distance from Walls Minimum of 4 in 102 mm from walls but no more than 1 2 the allowable distance permitted between sprinklers Refer to FM 2 0 Section 2 2 3 3 Deflector to Top of Storage Minimum of 36 in 914 mm Minimum of 36 inches 914 mm Refer to FM 2 0 Section 2 2 2 1 and FM 8 9 Section 2 2 6 Deflector to Ceiling Distance Ceiling roof heights up to 40 f...