ESFR PENDENT SPRINKLER 

VK503 (K16.8)

TECHNICAL DATA

Page 6 of 6

Form No. F_120106    18.10.11    Rev 18.2

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

Telephone: 269-945-9501  Technical Services: 877-384-5464  Fax: 269-818-1680  Email: [email protected]

Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com

TABLE 2

COMMODITY SELECTION AND DESIGN CRITERIA OVERVIEW FOR MODEL VK503 ESFR PENDENT SPRINKLERS

Storage Type

NFPA

FM

Sprinkler Type

ESFR

Storage

Response Type

ESFR

QR

System Type

Wet Pipe system only

Wet Pipe system only

Temperature Rating(s) ºF (ºC)

165 ºF (74 ºC) and 205 (96 ºC)

165 ºF (74 ºC) and 205 (96 ºC)

Open Frame Single, Double, Multiple-
Row,  or  Portable  Rack  Storage  of  Class  I-IV                                                                 
and Group A or B Plastics

Refer to NFPA 13.

Refer to FM 2-0 and 8-9.

Solid  Pile  or  Palletized  Storage  of  Class  I-IV  and                                                                           
Group A or B Plastics

Refer to NFPA 13.

Refer to FM 2-0 and 8-9.

Idle Pallet Storage

Refer to NFPA 13.

Refer to FM 2-0, 8-9, and 8-24.

Rubber Tire Storage

Refer to NFPA 13.

Refer to FM 2-0 and 8-3.

Rolled Paper Storage (Refer to the standard.)

Refer to NFPA 13.

Refer to FM 8-21.

Flammable Liquid Storage (Refer to the standard.)

Refer to NFPA 30.

Refer to FM 7-29

Aerosol Storage (Refer to the standard.)

Refer to NFPA 30B

Refer to FM 7-31

Automotive  Components  in  Portable  Racks                                                                       

(Control mode only, refer to the standard.)

Refer to NFPA 13.

N/A

IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Viking ESFR Pendent Sprinklers 

are to be installed in accordance with the latest edition of Viking technical data, the latest standards of NFPA, FM Global, 

VdS, LPCB, and any other Authorities Having Jurisdiction, and also with provisions of governmental codes, ordinances, and 

standards whenever applicable.

Replaces Form No. F_120106 Rev 18.1 

(Replaced design criteria tables; added P65 Warning.)    

Summary of Contents for VK503

Page 1: ...wed In addition some storage arrangements of rolled paper aerosols and rub ber tires may be protected by Viking ESFR Pendent Sprinkler VK503 2 LISTINGS AND APPROVALS cULus Listed Category VNWH Successfully meets UL 1767 test standard and compliance program for ESFR sprinklers installed in rack storage with high clearances to ceiling 20 ft or greater FM Approved Class 2027 NYC Approved MEA 89 92 E ...

Page 2: ...ing container Never install sprinklers that have been dropped or damaged in any way Such sprinklers should be destroyed immediately NOTE Wet pipe systems must be provided with adequate heat B The sprinklers must be installed after the piping is in place to prevent mechanical damage Before installing be sure to have the appropriate sprinkler model and style with the correct orifice size temperature...

Page 3: ...llation Standards e g NFPA 25 and the Authorities Having Jurisdiction for the specified period of time after which testing and or replacement is required Sprinklers that have operated cannot be reassembled or reused but must be replaced When replacing sprinklers use only new sprinklers C The sprinkler discharge pattern is critical for proper fire protection Therefore nothing should be hung from at...

Page 4: ...cation Sprinkler Nominal Temperature Rating1 Maximum Ambient Ceiling Temperature2 Frame Paint Color Ordinary 165 F 74 C 100 F 38 C None Intermediate 205 F 96 C 150 F 65 C White Sprinkler Finish Brass Footnotes 1 The sprinkler temperature rating is stamped on the deflector 2 Based on NFPA 13 Other limits may apply depending on fire loading sprinkler location and other requirements of the Authority ...

Page 5: ...is measured in kPa divide the metric K Factor shown by 10 0 3 This chart shows listings and approvals available at the time of printing Other approvals may be in process 4 Refer to the latest standards of NFPA 13 5 Listed by Underwriters Laboratories Inc for use in the U S and Canada 6 Accepted for use City of New York Department of Buildings MEA Number 89 92 E Vol 41 Approval Chart 2 FM ESFR Pend...

Page 6: ... Palletized Storage of Class I IV and Group A or B Plastics Refer to NFPA 13 Refer to FM 2 0 and 8 9 Idle Pallet Storage Refer to NFPA 13 Refer to FM 2 0 8 9 and 8 24 Rubber Tire Storage Refer to NFPA 13 Refer to FM 2 0 and 8 3 Rolled Paper Storage Refer to the standard Refer to NFPA 13 Refer to FM 8 21 Flammable Liquid Storage Refer to the standard Refer to NFPA 30 Refer to FM 7 29 Aerosol Storag...

Reviews: