Viking VK503 Technical Data Manual Download Page 2

ESFR PENDENT SPRINKLER 

VK503 (K16.8)

TECHNICAL DATA

Page 2 of 6

Form No. F_120106    18.10.11    Rev 18.2

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

Telephone: 269-945-9501  Technical Services: 877-384-5464  Fax: 269-818-1680  Email: [email protected]

Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com

Trigger and Support: Stainless Steel UNS-S31600

Fusible Element Assembly: Beryllium Nickel, coated with black acrylic paint.

Ordering Information:

 (Also refer to the current Viking price list.)

Order ESFR Pendent K16.8 Sprinkler VK503 by first adding the appropriate suffix for the sprinkler finish and then the appropriate 

suffix for the temperature rating to sprinkler base part number.

Finish Suffix: Brass = A

Temperature Suffix: 165 °F (74 °C) = C, 205 °F (96 °C) = E

For example, sprinkler VK503 with a Brass finish and a 165 °F (74 °C) temperature rating = Part No. 14073AC. 

Accessories:

 (Also refer to the Viking website.)

Sprinkler Wrench: 

Part No. 13635W/B (double-ended wrench - Use Side A. Side B is for use with K25.2 ESFR Pendent Sprinkler 

VK510) Available since 2006.

Sprinkler Cabinet: 

Twelve-head capacity: Part No. 01725A (available since 1971)

4.  INSTALLATION

 WARNING

Viking sprinklers are manufactured and tested to meet rigid requirements of the approving agency. The sprinklers 

are designed to be installed in accordance with recognized installation standards. System design must be based on 

ESFR design guidelines described in the latest edition of Viking technical data, applicable FM Global Loss Prevention 

Data Sheets, the latest NFPA Standards, the latest standards of Verband der Sachversicherer (VdS), Loss Prevention 

Council (LPCB), the Authorities Having Jurisdiction, and also with the provisions of governmental codes, ordinances, 

and standards whenever applicable. Deviation from the standards or any alteration to the sprinkler after it leaves the 

factory including, but not limited to: painting, plating, coating, or modification, may render the sprinkler inoperative and 

will automatically nullify the approval and any guarantee made by The Viking Corporation.

A. Sprinklers must be handled with care. They must be stored in a cool, dry place in their original shipping container. Never install 

sprinklers that have been dropped or damaged in any way. Such sprinklers should be destroyed immediately. 

NOTE: Wet pipe systems must be provided with adequate heat.

B. The sprinklers must be installed after the piping is in place to prevent mechanical damage. Before installing, be sure to have the 

appropriate sprinkler model and style, with the correct orifice size, temperature rating, and response characteristics.

C. With the sprinkler contained in the plastic protective cap, apply a small amount of pipe-joint compound or tape to the male threads 

only, while taking care not to allow a build-up of compound in the sprinkler orifice.

D. 

Use ONLY sprinkler wrench 13635W/B (shown in Figure 1) for installing ESFR Sprinkler VK503! With the sprinkler con-

tained in the protective cap, install the sprinkler onto the piping by applying the sprinkler wrench to the sprinkler wrench 

flats only, while taking care not to damage the sprinkler operating parts.

DO NOT use any other type of wrench, as this could damage the unit.

DO NOT use the sprinkler deflector or fusible element to start or thread the sprinkler into a fitting.

DO NOT exceed 50 ft. lbs. of torque (hand tight, plus approximately two full turns with the wrench) to install these sprinklers. Higher 

levels of torque may distort the sprinkler inlet with consequent leakage or impairment of the sprinkler.

E. After installation, the entire sprinkler system must be tested. The test must be conducted to comply with the Installation Standards. 

Make sure the sprinkler has been properly tightened. If a thread leak occurs, normally the unit must be removed, new pipe-joint 
compound or tape applied, and then reinstalled. This is due to the fact that when the joint seal is damaged, the sealing compound 
or tape is washed out of the joint. Immediately replace any damaged units, using the special sprinkler wrench only.

F. After installation and testing and repairing of all leaks, remove the protective caps from the sprinklers. Do NOT use any 

type of tool to remove the cap. Remove the cap by hand: turn it slightly and pull it off the sprinkler. When removing caps, 

use care to prevent dislodging or damaging sprinkler ejector spring and fusible element. THE CAPS MUST BE REMOVED 

FROM SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE!

G. System design must be based on ESFR design guidelines described in applicable FM Global Loss Prevention Data Sheets, the 

Summary of Contents for VK503

Page 1: ...wed In addition some storage arrangements of rolled paper aerosols and rub ber tires may be protected by Viking ESFR Pendent Sprinkler VK503 2 LISTINGS AND APPROVALS cULus Listed Category VNWH Successfully meets UL 1767 test standard and compliance program for ESFR sprinklers installed in rack storage with high clearances to ceiling 20 ft or greater FM Approved Class 2027 NYC Approved MEA 89 92 E ...

Page 2: ...ing container Never install sprinklers that have been dropped or damaged in any way Such sprinklers should be destroyed immediately NOTE Wet pipe systems must be provided with adequate heat B The sprinklers must be installed after the piping is in place to prevent mechanical damage Before installing be sure to have the appropriate sprinkler model and style with the correct orifice size temperature...

Page 3: ...llation Standards e g NFPA 25 and the Authorities Having Jurisdiction for the specified period of time after which testing and or replacement is required Sprinklers that have operated cannot be reassembled or reused but must be replaced When replacing sprinklers use only new sprinklers C The sprinkler discharge pattern is critical for proper fire protection Therefore nothing should be hung from at...

Page 4: ...cation Sprinkler Nominal Temperature Rating1 Maximum Ambient Ceiling Temperature2 Frame Paint Color Ordinary 165 F 74 C 100 F 38 C None Intermediate 205 F 96 C 150 F 65 C White Sprinkler Finish Brass Footnotes 1 The sprinkler temperature rating is stamped on the deflector 2 Based on NFPA 13 Other limits may apply depending on fire loading sprinkler location and other requirements of the Authority ...

Page 5: ...is measured in kPa divide the metric K Factor shown by 10 0 3 This chart shows listings and approvals available at the time of printing Other approvals may be in process 4 Refer to the latest standards of NFPA 13 5 Listed by Underwriters Laboratories Inc for use in the U S and Canada 6 Accepted for use City of New York Department of Buildings MEA Number 89 92 E Vol 41 Approval Chart 2 FM ESFR Pend...

Page 6: ... Palletized Storage of Class I IV and Group A or B Plastics Refer to NFPA 13 Refer to FM 2 0 and 8 9 Idle Pallet Storage Refer to NFPA 13 Refer to FM 2 0 8 9 and 8 24 Rubber Tire Storage Refer to NFPA 13 Refer to FM 2 0 and 8 3 Rolled Paper Storage Refer to the standard Refer to NFPA 13 Refer to FM 8 21 Flammable Liquid Storage Refer to the standard Refer to NFPA 30 Refer to FM 7 29 Aerosol Storag...

Reviews: