ESFR PENDENT SPRINKLER 

VK503 (K16.8)

TECHNICAL DATA

Page 3 of 6

Form No. F_120106    18.10.11    Rev 18.2

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

Telephone: 269-945-9501  Technical Services: 877-384-5464  Fax: 269-818-1680  Email: [email protected]

Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com

latest standards of Verband der Sachversicherer, LPCB, the National Fire Protection Association, and the Authorities Having 
Jurisdiction. All requirements of recognized sprinkler system design standards apply to systems utilizing Viking ESFR Pendent 
Sprinklers.

5.  OPERATION

During fire conditions, the heat-sensitive fusible element assembly disengages, releasing the seat and spring assemblies to open 

the waterway. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern to suppress 

the fire.

6.  INSPECTIONS, TESTS AND MAINTENANCE

NOTICE

The owner is responsible for maintaining the fire protection system and devices in proper operating condition. For 

minimum maintenance and inspection requirements, refer to the NFPA standard that describes care and maintenance 

of sprinkler systems. In addition, the Authorities Having Jurisdiction may have additional maintenance, testing, and 

inspection requirements that must be followed.

A. The sprinklers must be inspected on a regular basis for corrosion, mechanical damage, obstructions, paint, etc. The frequency of 

inspections may vary due to corrosive atmosphere, water supplies, and activity around the device.

B. Sprinklers that have been painted or mechanically damaged must be replaced immediately. Sprinklers showing signs of corrosion 

shall be tested and/or replaced immediately as required. Installation standards require sprinklers to be tested and, if necessary, 
replaced after a specified term of service. For Viking ESFR Pendent Sprinklers, refer to the Installation Standards (e.g., NFPA 25) 
and the Authorities Having Jurisdiction for the specified period of time after which testing and/or replacement is required. Sprinklers 
that have operated cannot be reassembled or reused, but must be replaced. When replacing sprinklers, use only new sprinklers.

C. The sprinkler discharge pattern is critical for proper fire protection. Therefore, nothing should be hung from, attached to, or other-

wise obstruct the discharge pattern. All obstructions must be immediately removed or, if necessary, additional sprinklers installed.

D. When replacing existing sprinklers, the system must be removed from service. Refer to the appropriate system description and/

or valve instructions. Prior to removing the system from service, notify all Authorities Having Jurisdiction. Consideration should be 
given to employment of a fire patrol in the affected area.

1. Remove the system from service, drain all water, and relieve all pressure on the piping.

2. Using the special sprinkler wrench, remove the old sprinkler and install the new unit. Care must be taken to ensure that the re-

placement sprinkler is the proper model and style, with the correct orifice size, temperature rating, and response characteristics. 

A fully stocked spare sprinkler cabinet should be provided for this purpose.

3. Place the system back in service and secure all valves. Check the replaced sprinklers and repair all leaks.

E. Sprinkler systems that have been subject to a fire must be returned to service as soon as possible. The entire system must 

be inspected for damage and repaired or replaced as necessary. Sprinklers that have been exposed to corrosive products of 
combustion, but have not operated, should be replaced. Refer to the Authorities Having Jurisdiction for minimum replacement 
requirements.

7.  AVAILABILITY

Viking ESFR K16.8 Pendent Sprinkler VK503 is available through a network of domestic and international distributors. See The 

Viking Corporation web site for the closest distributor or contact The Viking Corporation.

8.  GUARANTEE

For details of warranty, refer to Viking’s current list price schedule or contact Viking directly.

Summary of Contents for VK503

Page 1: ...wed In addition some storage arrangements of rolled paper aerosols and rub ber tires may be protected by Viking ESFR Pendent Sprinkler VK503 2 LISTINGS AND APPROVALS cULus Listed Category VNWH Successfully meets UL 1767 test standard and compliance program for ESFR sprinklers installed in rack storage with high clearances to ceiling 20 ft or greater FM Approved Class 2027 NYC Approved MEA 89 92 E ...

Page 2: ...ing container Never install sprinklers that have been dropped or damaged in any way Such sprinklers should be destroyed immediately NOTE Wet pipe systems must be provided with adequate heat B The sprinklers must be installed after the piping is in place to prevent mechanical damage Before installing be sure to have the appropriate sprinkler model and style with the correct orifice size temperature...

Page 3: ...llation Standards e g NFPA 25 and the Authorities Having Jurisdiction for the specified period of time after which testing and or replacement is required Sprinklers that have operated cannot be reassembled or reused but must be replaced When replacing sprinklers use only new sprinklers C The sprinkler discharge pattern is critical for proper fire protection Therefore nothing should be hung from at...

Page 4: ...cation Sprinkler Nominal Temperature Rating1 Maximum Ambient Ceiling Temperature2 Frame Paint Color Ordinary 165 F 74 C 100 F 38 C None Intermediate 205 F 96 C 150 F 65 C White Sprinkler Finish Brass Footnotes 1 The sprinkler temperature rating is stamped on the deflector 2 Based on NFPA 13 Other limits may apply depending on fire loading sprinkler location and other requirements of the Authority ...

Page 5: ...is measured in kPa divide the metric K Factor shown by 10 0 3 This chart shows listings and approvals available at the time of printing Other approvals may be in process 4 Refer to the latest standards of NFPA 13 5 Listed by Underwriters Laboratories Inc for use in the U S and Canada 6 Accepted for use City of New York Department of Buildings MEA Number 89 92 E Vol 41 Approval Chart 2 FM ESFR Pend...

Page 6: ... Palletized Storage of Class I IV and Group A or B Plastics Refer to NFPA 13 Refer to FM 2 0 and 8 9 Idle Pallet Storage Refer to NFPA 13 Refer to FM 2 0 8 9 and 8 24 Rubber Tire Storage Refer to NFPA 13 Refer to FM 2 0 and 8 3 Rolled Paper Storage Refer to the standard Refer to NFPA 13 Refer to FM 8 21 Flammable Liquid Storage Refer to the standard Refer to NFPA 30 Refer to FM 7 29 Aerosol Storag...

Reviews: