background image

SPRINKLER GENERAL CARE, 

INSTALLATION, AND 

MAINTENANCE GUIDE

TECHNICAL DATA

Page 2 of 4

Form No. F_080614       18.10.11     Rev 16.1.P65

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: [email protected]

Visit the Viking website for the latest edition of this technical data page.

Before installation, be sure to have the appropriate sprinkler model and style, with the correct K-Factor, temperature rating, and 

response characteristics. Sprinklers must be installed after the piping is in place to prevent mechanical damage. Keep sprinklers 

with protective caps or bulb shields contained within the caps or shields during installation and testing, and any time the sprinkler 

is shipped or handled.

1a. For frame-style sprinklers, install escutcheon (if used), which is designed to thread onto the external threads of the sprinkler. 

Refer to the appropriate sprinkler data page to determine approved escutcheons for use with specific sprinkler models.

1b. For flush and concealed style sprinklers: Cut the sprinkler nipple so that the ½” or 3/4” (15 mm or 20 mm)* NPT outlet of the 

reducing coupling is at the desired location, and centered in the opening* in the ceiling or wall.

    *Size depends on the sprinkler model used. Refer to the sprinkler technical data page.

2. Apply a small amount of pipe-joint compound or tape to the external threads of the sprinkler only, taking care not to allow a 

build-up of compound in the sprinkler inlet. 

NOTE:

 Sprinklers with protective caps or bulb shields must have the caps or shields 

kept on them when applying pipe-joint compound or tape. 

Exception: For domed concealed sprinklers, remove the protective 

cap for installation, and then place it back on the sprinkler temporarily.. 

3. Refer to the appropriate sprinkler technical data page to determine the correct sprinkler wrench for the model of sprinkler used. 

DO NOT use the deflector or fusible element to start or thread the sprinkler into a fitting. 

a. Install the sprinkler onto the piping using the special sprinkler wrench only, taking care not to over-tighten or damage the 

sprinkler.

b. For flush and concealed style sprinklers: the internal diameter of the special sprinkler installation wrench is designed for use 

with the sprinkler contained in the protective cap. 

Exception: For domed concealed sprinklers, remove the protective cap for 

installation, and then place it back on the sprinkler temporarily. 

Thread the flush or concealed sprinkler into the ½” or 3/4” 

(15 mm or 20 mm)* NPT outlet of the coupling by turning it clockwise with the special sprinkler wrench. 

*Thread size depends 

on the particular sprinkler model used. Refer to the sprinkler technical data page.

 

C. Installation Instructions - Dry Sprinklers

WARNING:

 Viking dry sprinklers are to be installed in the 1” outlet (for dry and preaction systems), or run of malleable, ductile 

iron, or Nibco CPVC* threaded tee fittings (for wet systems) that meet the dimensional requirements of ANSI B16.3 (Class 150), 

or cast iron threaded tee fittings that meet the dimensional requirements of ANSI B16.4 (Class 125), even at branch line ends. The 

threaded end of the dry sprinkler is designed to allow the seal to penetrate and extend into the fitting to a predetermined depth. 

This prevents condensation from accumulating and freezing over the sprinkler seal. 

*NOTE: When using CPVC fittings with 

Viking dry sprinklers, use only new Nibco Model 5012-S-Bl. When selecting other CPVC fittings, contact Viking Technical 

Services.

1. 

DO NOT

 install the dry sprinkler into a threaded elbow, coupling, or any other fitting that could interfere with thread penetration. 

Such installation would damage the brass seal. 

2. 

DO NOT

 install dry sprinklers into couplings or fittings that would allow condensation to accumulate above the seal when the 

sprinkler is located in an area subject to freezing.

3. 

NEVER

 try to modify dry sprinklers. They are manufactured for specific “A” or “B” dimensions and cannot be modified. 

The dry sprinkler must be installed after the piping is in place to prevent mechanical damage. Before installation, be sure to have 

the correct sprinkler model and style, with the appropriate “A” or “B” dimension(s), temperature rating, orifice size, and response 

characteristics. Keep sprinklers with protective caps or bulb shields contained within the caps or shields during installation and 

testing, and any time the sprinkler is shipped or handled. 

Exception:

 For concealed and adjustable recessed dry sprinklers, the 

protective caps and shields are removed for installation.
To install the dry sprinkler, refer to the instructions below and the appropriate sprinkler technical data page for illustrated instruc-

tions. 

Dry upright sprinklers must be installed above the piping, in the upright position only. When installing dry upright or plain barrel style 

vertical sidewall sprinklers on piping located close to the ceiling, it may be necessary to lower the sprinkler into the fitting from above 

the ceiling. When installing dry upright or plain barrel vertical sidewall sprinklers from below the ceiling, verify that the opening in the 

ceiling is a minimum 1-1/2” (38.1 mm) in diameter.
For dry upright or plain barrel vertical sidewall sprinklers in the upright position: First, install the escutcheon (if used) over the 

threaded end of the sprinkler barrel. Slide the escutcheon past the external threads. NOTE: When installing the dry upright or plain 

barrel vertical sidewall sprinkler from above the ceiling, it will be necessary to install the escutcheon after lowering the threaded 

end of the sprinkler through the ceiling penetration.

A. 

For all dry sprinklers:

 Apply a small amount of pipe-joint compound or tape to the external threads of the sprinkler barrel only, 

taking care not to allow a build-up of compound or tape over the brass inlet and seal. 

NOTE:

 Sprinklers with protective caps or 

bulb shields must be contained within the caps or shields before applying pipe-joint compound or tape.

Summary of Contents for VK2021

Page 1: ... psi 12 bar water working pressure Factory tested hydrostatically to 500 psi 34 5 bar Thread size 3 4 NPT 20 mm BSPT Nominal K factor 8 0 U S 115 metric Glass bulb fluid temperature rated to 65 F 55 C Metric K factor measurement shown is in Bar When pressure is measured in kPa divide the metric K factor shown by 10 0 Material Standards Sprinkler Body Brass CW602N UNS C84400 or QM Brass Deflector S...

Page 2: ... area will experience temperatures above the maximum ambient rating you shall use a higher temperature rated sprinkler Accessories Sprinkler Wrenches see Figure 1 A Installer Wrench Part No 22055 available since 2017 B Cabinet Wrench Part No 20901M B available since 2017 C Recessed Socket Wrench Part No 20951M B2 available since 2017 D Straight Wrench Part No 22940MB Sprinkler Cabinet A Up to 6 sp...

Page 3: ...Approvals Maximum WWP 175 PSI 12 bar CE6 LPCB7 VdS8 19923 3 4 C1 D2X D3Y A1 B2X B3Y A1 19935 20 C1 D2X D3Y A1 B2X B3Y A1 Approved Temperature Ratings A 135 F 57 C 155 F 68 C 175 F 79 C 200 F 93 C and 286 F 141 C B 135 F 57 C 155 F 68 C 175 F 79 C and 200 F 93 C C 155 F 68 C 175 F 79 C 200 F 93 C and 286 F 141 C D 155 F 68 C 175 F 79 C and 200 F 93 C Approved Finishes 1 Brass Chrome White Polyester...

Page 4: ...priate standards of NFPA LPCB APSAD VdS or other similar organizations and also with the provisions of governmental codes ordinances and standards whenever applicable DESIGN CRITERIA FM FM Approval Requirements The Viking VK2021 Standard Response Pendent Sprinkler is FM Approved as standard response Non Storage Pendent sprinkler as indicated in the FM Approval Guide For specific application and in...

Page 5: ...re 3 Recessed Installation with Recessed Socket Wrench A 1 2 ratchet is required not available from Viking Figure 4 Recessed Installation with standard Installer s Wrench 2 Carefully slide the wrench sideways around the protective cap then push upwards to engage with the sprinkler wrench flats 2 Carefully slide the wrench sideways around the protective cap then push upwards to engage with the spri...

Page 6: ... Thread On Recessed Escutcheon NP 3 Outer ring has a larger diameter Max 1 7 16 37 mm Max 1 3 4 44 mm Min 13 16 21 mm Min 15 16 24 mm Ceiling opening size Minimum 2 5 16 59 mm Maximum 2 1 2 64 mm 1 7 16 37 mm Standard Surface Mounted Escutcheon Figure 6 Installation Dimensions with Viking Escutcheons 1 Install the escutcheon onto the sprinkler threads Figure 5 Installation with Straight Wrench 2 C...

Page 7: ...stall sprinklers onto piping at the floor level Install sprinklers after the piping is in place to prevent mechanical damage DO NOT allow impacts such as hammer blows directly to sprinklers or to fittings pipe or couplings in close proximity to sprinklers Sprinklers can be damaged from direct or indirect impacts DO NOT attempt to remove drywall paint etc from sprinklers Take care not to over tight...

Page 8: ...D CAPS MUST BE REMOVED FROM SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE Figure 1 Sprinkler shield being removed from a pendent sprinkler Figure 2 Sprinkler cap being removed from a pendent sprinkler Figure 3 Sprinkler cap being re moved from and upright sprinkler HOW TO REMOVE SHIELDS AND CAPS No tools are necessary to remove the shields or caps from sprinklers DO NOT use any sharp objects to ...

Page 9: ... these sprinklers NOTE The protective cap is temporarily removed during installation and then placed back on the sprinkler for protection until finish work is completed Do not over tighten the sprinklers into fittings during installation Do not use the sprinkler deflector to start or thread the sprinklers into fittings during installation Do not attempt to remove drywall paint etc from the sprinkl...

Page 10: ...t the corrosion resistant properties of the sprinkler Use care when locating sprinklers near fixtures that can generate heat Do not install sprinklers where they would be exposed to temperatures exceed ing the maximum recommended ambient temperature for the temperature rating used Inspect the coated sprinklers frequently soon after installation to verify the integrity of the corrosion resistant co...

Page 11: ...t readings to be expected In addition recognized installation rules may require a higher temperature classifica tion depending upon sprinkler location occupancy classification commodity classification storage height and other hazards In all cases the maximum expected ceiling temperature dictates the lowest allowable temperature classification Sprinklers located immediately adjacent to a heat sourc...

Page 12: ...ly intended for installation with a concealed piping system The assembly con sists of a sprinkler installed in a decorative adjustable recessed escutcheon that minimizes the protrusion of the sprinkler beyond the ceiling or wall without adversely affecting the sprinkler distribution or sensitivity Refer to the appropriate technical data page for allowable sprinkler models temperature ratings and o...

Page 13: ...TENANCE Refer to NFPA 25 for Inspection Testing and Maintenance requirements 7 AVAILABILITY Viking sprinklers are available through a network of domestic and international distributors See The Viking Corporation web site for the closest distributor or contact The Viking Corporation 8 GUARANTEE For details of warranty refer to Viking s current list price schedule or contact Viking directly IMPORTAN...

Page 14: ...he sprinkler technical data page Never install any glass bulb sprinkler if the bulb is cracked or if there is a loss of liquid from the bulb A small air bubble should be present in the glass bulb Any sprinkler with a loss of liquid from the glass bulb or damage to the fusible element should be destroyed immediately Note Installing glass bulb sprinklers in direct sunlight ultraviolet light may affe...

Page 15: ...uctile iron or Nibco CPVC threaded tee fittings for wet systems that meet the dimensional requirements of ANSI B16 3 Class 150 or cast iron threaded tee fittings that meet the dimensional requirements of ANSI B16 4 Class 125 even at branch line ends The threaded end of the dry sprinkler is designed to allow the seal to penetrate and extend into the fitting to a predetermined depth This prevents co...

Page 16: ...ther To remove caps from frame style sprinklers turn the caps slightly and pull them off the sprinklers SPRINKLER CAPS OR BULB SHIELDS MUST BE REMOVED FROM SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE Retain a protective cap or shield in the spare sprinkler cabinet 5 For flush style sprinklers the ceiling ring can now be installed onto the sprinkler body Align the ceiling ring with the sprinkle...

Page 17: ...Prior to removing the system from service notify all Authorities Having Jurisdiction Consideration should be given to employment of a fire patrol in the affected area 1 Remove the system from service drain all water and relieve all pressure on the piping 2a For frame style sprinklers use the special sprinkler wrench to remove the old sprinkler by turning it counterclockwise to unthread it from the...

Page 18: ...ction of fire protection products are provided herin as they relate to legally mandated jurisdictional regions WARNING STATE OF CALIFORNIA USA Installing or servicing fire protection products such as sprinklers valves piping etc can expose you to chemicals including but not li mited to lead nickel butadiene titaninum dioxide chromium carbon black and acrylonitrile which are known to the State of C...

Page 19: ...y render the sprinkler inoperative and will automatically nullify the approval and any guarantee made by The Viking Corporation Refer to the Authority Having Jurisdiction prior to installation 2 GENERAL INFORMATION A potential product performance issue may exist when listed products are combined with unlisted product s that have not been evaluated together by a recognized approval laboratory With ...

Reviews: