![Viking VFR400 Manual Download Page 80](http://html.mh-extra.com/html/viking/vfr400/vfr400_manual_1023432080.webp)
80
VFR-400 • 5403548 • REV W • 8/17
Soak Timer Description
This allows the user to select the amount of time the release circuit on output #3 will stay activated after the Firecycle zone
restores to normal. The available times are 30, 60, 90 seconds, 2-20 minutes in 1 minute incriments, or continous.
After describing all initiating zones or skipping to the next function, the following will appear in the display window:
SET
Press the SET button to set the description displayed.
SELECT
Press the SELECT button to scroll through the five descriptions.
(Supervisory, Valve Tamper, Low Air, High Air)
FUNCTION
Press the FUNCTION button to skip to the next function.
After Selecting SUP 1, the following will appear in the display window.
SET
Press the SET button to set the description displayed.
SELECT
Press the SELECT button to scroll through the four supervisory descriptions.
(Supervisory, Valve Tamper, Low Air, High Air)
FUNCTION
Press the FUNCTION button to skip to the next function.
After describing what the supervisory zone is to be or skipping to the next function, the following will appear
in the display window:
Output Description
This allows the user to describe the functions of the output circuits. Four descriptions are available:
1) ALARM INDICATING - Notification appliances include bells, horns, strobes and other appliances used to indicate an alarm.
2) RELEASING - Releasing appliances include solenoids and other electrically compatible devices.
3) SUPERVISORY BELL - Appliances on this circuit are used to indicate the presence of a supervisory condition. Any zone
programmed as LOW AIR ALARM, SUPERVISORY, TAMPER, HI AIR or LOW AIR is automatically mapped to this output.
4) TROUBLE BELL - Appliances on this circuit are used to indicate the presence of a trouble condition.
The user should describe each output circuit in the same manner as the initiating circuit was described by
pressing the SELECT
button to select and the SET button to set the desired function.
SET
Press the SET button to set the description displayed.
SELECT
Press the SELECT button to scroll through the descriptions.
FUNCTION
Press the FUNCTION button to skip to the next function.
S U P
E
R V S R Y
1
Z
O N
E
S U P
E
R V I S R Y
S U P
E
R V S R Y
2
Z
O N
E
S U P
E
R V I S R Y
O U T P U T
# 1
I N
D
I C A T I N
G