VFR-400 • 5403548 • REV W • 8/17
Program #21 Mode
1. Apply power to panel.
2. Move the program switch down.
3. Press the FUNCTION button until the display reads “PASSWORD = 000”.
4. To enter a password, press the SELECT button until the proper number is displayed above the ^ symbol, then press the SET
button to move to the next digit. After entering the third number the display will change.
(All panels are shipped with a 000 password.)
5. Press the FUNCTION button until the display reads “PROGRAM #0”.
6. Press the SELECT button until the display reads “PROGRAM #21”.
7. Press the SET button.
8. Press the SELECT button to change the pre-discharge time.
9. Press the SET button to enter the pre-discharge time displayed.
10. Press the SELECT button to change the abort mode. See page 80 for abort mode selections.
11. Press the SET button to enter the abort mode displayed.
12. The panel is completely programmed except for the custom banner and zone messages. Move the program switch back up.
PROGRAM #21
ZONES
SUPERVISORY 2
#1
#2
#3
#4
OUTPUTS
Supervisory
Detection
Detection
Detection
Detection
#1 ALARM INDICATING
X
X
#2 RELEASE
X
X
#3 ALARM INDICATING
X
X
#4 RELEASE
X
X
SUP 1 defaults to abort
OPERATION DESCRIPTION
Description
Dual Hazard, 2 detection zones mapped to 1 release circuit and 2 other detection zones mapped to
another release circuit
Inputs
1 supervisory zone, 4 detection zones, 1 abort circuit
Outputs
2 general alarm, 2 release circuit
Operation
Activation of either detection zone 1 or 2 will activate the alarm output #1 and start the pre-
discharge timer for the release circuit output #2
Activation of either detection zone 3 or 4 will activate the alarm output #3 and start the pre-
discharge timer for the release circuit output #2
When either zone 1 or 2 is in alarm, outputs 1 & 2 will operate
When either zone 3 or 4 is in alarm, outputs 3 & 4 will operate