VFR-400 • 5403548 • REV W • 8/17
PROGRAM #2
For Two Sprinkler Systems Operating Independantly From Each Other
Viking Sprinkler
System Types
2 Split Release
Zones and 2
Waterflow Zones
1. Single Interlocked Preaction System with Electric Release
2. Deluge System with Electric Release
3. Non-Interlocked Preaction System with Electric Release
4. Double Interlocked Preaction System with Electric/Pneumatic Release
OUTPUTS
(Indicating Circuits)
ZONES (Initiating Circuits)
SUP 1
SUP 2
#1
#2
#3
#4
Valve Tamper
Supervisory Zone
for Systems 1 & 2
Low Air
Supervisory Zone
for Systems 1 & 2
Conventional
Detection Zone
for System 1
Conventional
Detection Zone
for System 2
Waterflow
Zone for
System 1
Waterflow
Zone for
System 2
#1 General Alarm
X
X
X
X
#2 Release Solenoid #1
X
#3 Release Solenoid #2
X
#4 Waterflow
X
X
OPERATION DESCRIPTION
Inputs:
2 Conventional Detection zones, 2 Waterflow zones, 2 Supervisory zones
Outputs:
1 General Alarm, 1 Waterflow Alarm, 2 Solenoid Release
Operation:
Activation of Conventional Detection zone #1 will activate output #2 (Release Solenoid #1) and
output #1 (General Alarm)
Activation of Conventional Detection zone #2 will activate output #3 (Release Solenoid #2) and
output #1 (General Alarm)
Activation of Waterflow zone #3 or #4 will activate output #1 (General Alarm) and output #4
(Waterflow)
Activation of Valve Tamper Supervisory zone #1 or Low Air Supervisory zone #2 will operate
supervisory trouble relay.
NOTES
:
1. Connect EOL Diode assembly IN SERIES as shown with Solenoid on output #2 (Release Solenoid) and output #3 (Release
Solenoid). Black wire to negative terminal on panel and Red wire through Solenoid to positive terminal on panel.
2. Polarity is shown on indicating circuits in an activated (in alarm) condition.
3. Leave EOLR (provided) on all unnused circuits.
4. See the instruction manual for circuit information, panel limits, and battery sizing.
5. For wire routing instructions through the releasing panel, see Note 3 on page 20 of the instruction manual.
6. See instruction manual for proper programming.
7. See instruction manual for list of compatible smoke detectors.
8. See specific system type data page for proper pressure switch settings.