4.  INSTALLATION

Refer to appropriate NFPA, FM Global, and/or any other applicable installation standards. 

 NOTICES

 

•  Sprinklers must be handled with care. They must be stored in a cool, dry place in their original shipping container. Never 

install sprinklers that have been dropped, damaged in any way, or exposed to temperatures in excess of maximum 

ambient temperature allowed. Such sprinklers should be destroyed immediately. 

•  Viking Institutional Sprinklers are not intended for use in corrosive environments. Use only sprinklers listed for 

corrosive environments when subject to corrosive atmospheres. 

•  Use care when locating sprinklers near fixtures that can generate heat. Do not install sprinklers where they will be 

exposed to temperatures that exceed the maximum recommended ambient temperature for the temperature rating used.

•  Adequate heat must be provided when the Institutional Sprinklers are installed on wet-pipe systems.

•  The sprinklers must be installed after the piping is in place to prevent mechanical damage. Before installing, be sure 

to have the appropriate sprinkler model and style, with the correct orifice size, temperature rating, and response 

characteristics.

 

 

WARNING  

Viking sprinklers are manufactured and tested to meet the rigid requirements of the approving agency. The sprinklers 

are designed to be installed in accordance with recognized installation standards. Deviation from the standards or any 

alteration to the sprinkler after it leaves the factory including, but not limited to: painting, plating, coating, or modifica-

tion, may render the sprinkler inoperative and will automatically nullify the approval and any guarantee made by The 

Viking Corporation. Flush sprinklers are decorative sprinklers and may be considered special purpose. As such, some 

Authorities may limit the use depending on the occupancy classification. Refer to the Authority Having Jurisdiction prior 

to installation.  

General Information: 

The tamper-resistant design of the Viking Institutional Sprinklers is dependant upon proper installation as outlined in this document 

as well as proper piping design and installation. Proper installation ensures that the sprinkler assembly will be held in place by the 

force of the escutcheon pressing outward on the sprinkler body. 

Pay close attention to the instructions below when installing these sprinklers.

Proper installation requires the following: 
•  The fitting in which the sprinkler is to be installed must be properly located according to the dimensions indicated below. 

•  The sprinkler fitting and drop nipple should be secured in place by installing the retaining flange as shown in the procedure below. 

•  The centerline of the fitting in which the sprinkler is to be installed must be perpendicular to the surface of the finished surface. 

•  Remove the sprinkler cap before placing the system into service.

•  After installation, the entire system must be tested in accordance with recognized installation standards. The test is applied after 

sprinkler installation to ensure that no damage has occurred to the sprinkler during shipping and installation, and to make sure 

the unit has been properly tightened. If a thread leak occurs, normally the unit must be removed, new pipe-joint compound or 

tape applied, and then reinstalled. This is due to the fact that when the joint seal leaks, the sealing compound or tape is washed 

out of the joint

 
Tools and recommended supplies: 
•  PTFE Tape

•  Institutional Sprinkler Wrench Part Number 22847M/B (requires a 1/2” socket wrench which is not available from Viking)

•  1/2” Ratchet wrench and (optional) extenstion

•  1/8” hex wrench (used for retaining flange hex screw; not available from Viking)

•  Level

INSTALLATION TIP:

Prior to final installation, temporarily install all components described in the procedure below to verify the correct measurements have 

been acheived. If necessary, re-cut the supply drop nipple and repeat the procedure in order to acheive the correct measurements. 

Summary of Contents for K5-6

Page 1: ...erage Flush sprinklers for extended areas of coverage up to 16 x 16 4 9 m x 4 9 m in Light Hazard occupancies only below smooth flat horizontal ceilings Refer to the Approval Chart and Design Criteria for requirements that must be followed NOTICE THE VIKING CORPORATION DISCLAIMS ANY RESPONSIBILITY FOR DAMAGES OR INJURY INCLUDING DEATH CAUSED BY THE OPERATION OR INOPERATION OF SPRINKLERS ARISING OU...

Page 2: ...96 QR EC HSW 22907 VK651 15 4 100 mm 23197 Examples Sprinkler 19663MC RAL9006 VK426 Quick Response Pendent with Painted gray Finish and 165 F 74 C Nominal tempera ture rating This sprinkler is to be installed into an area with a maximum ambient temperature of 100 F 38 C meaning if the area will experience temperatures above the maximum ambient rating you shall use a higher temperature rated sprink...

Page 3: ...1 03 Rev 20 1 2020 Viking Group Inc All rights reserved Figure 3 Sprinkler Components and Identification Horizontal Sidewall Pendent Pendent Deflector Sprinkler Type indicator Sprinkler Type indicator Horizontal Sidewall Deflector Sprinkler Data Location Stamped around the permimeter you will find Sprinkler Identification Number SIN K factor Coverage No mark for Standard Coverage and EC for Extend...

Page 4: ...orporation Flush sprinklers are decorative sprinklers and may be considered special purpose As such some Authorities may limit the use depending on the occupancy classification Refer to the Authority Having Jurisdiction prior to installation General Information The tamper resistant design of the Viking Institutional Sprinklers is dependant upon proper installation as outlined in this document as w...

Page 5: ...king on the protective cap Place the sprinkler wrench over the protective cap on the sprinkler body NOTE The wrench is uniquely designed to fit over the sprinkler cap and into the sprinkler in a specific alignment 6 Install the sprinkler into the fitting NOTE The Escutcheon plate MUST be tight against the ceiling or wall 7 Tighten the sprinkler to approximately 7 14 ft lbs 8 If desired use a level...

Page 6: ...sleeve 2 I D Cored Hole OR 2 Sch 40 Steel pipe sleeve Figure 5 Installation Dimensions Pendent Figure 6 Installation Dimensions HSW Upon activation the deflector actuates to approximately 7 8 22 mm beyond the sprinkler body 1 5 16 33 mm 1 4 6 mm 3 or 4 75 or 100 mm Face of fitting to finished surface of wall 7 8 22 mm Ensure the escutcheon plate is tight against the ceiling Ensure the escutcheon p...

Page 7: ... and or replaced immediately as required Installation standards require sprinklers to be tested and if necessary replaced after a specified term of service Refer to the installation standards and the Authority Having Jurisdiction for the specified period of time after which testing and or replacement is required Sprinklers that have operated cannot be reassembled or reused but must be replaced Whe...

Page 8: ...part number refer to Viking s current price schedule 2 This table shows the listings and approvals available at the time of printing Check with the manufacturer for any additional approvals 3 Other colors are available upon request with the same Listings and Approvals as the standard colors LISTED FLOW RATES AND COVERAGE AREAS LIGHT HAZARD FOR Viking EXTENDED COVERAGE Institutional Sprinklers Spri...

Page 9: ...nkler must be installed in the horizontal sidewall position in fixed fire protection systems wet dry deluge or preaction systems Orient the top of the deflector parallel with the ceiling The wrench ear on the top of the Viking Institutional Style Quick Response Flush Horizontal Sidewall Sprinkler is marked with the word top Must be located with deflector 4 to 12 102 mm to 304 mm below the ceiling ...

Reviews: