The one or two digit code stored in the Relay Activation Command is the touch tone command that the person being 
called must enter on their phone in order to actuate relay 1 or 2 to control a doorstrike, mag-lock, gate controller, or 
other device. The code can contain the numbers 0 - 9, 00 - 99, ## or 

QQ

. The code cannot match a relay latching or 

toggle command (11, 10, 1#, 21, 20, or 2#). The code must be entered while the remote phone is communicating with 
the Entry phone. The Entry phone determines which direction the touch tone is coming from and only responds to 
touch tones from the called phone.  

Factory Setting:

 Relay 1 - 

QQ

,

 

Relay 2 - 

Q

18. Relay 1 or 2 Act (Activation) Command 

The value stored in the Relay 1 or 2 Activation Time is the amount of time relay 1 or 2 will be energized after a correct 
touch tone command is entered. This number can range from 0.5 - 99 seconds.  

Note:

 

This also affects timing in 

Doorbell Mode.  

Factory Setting:

 5 seconds

19. Relay 1 or 2 Activation Time 

Doorstrike Mode (Factory Setting):  

When programmed for Doorstrike Mode the relay will momentarily activate for 

the preprogrammed relay activation time after detecting the correct relay activation command (one or two digit touch 
tone) from the called party. 

Outbound Call Mode: 

 When programmed for Outbound Call Mode the relay will activate continuously for the duration 

of any outbound call from the Entry phone.  

Inbound/Outbound Call Mode:  

When programmed for Inbound/Outbound Call Mode the relay will activate 

continuously for the duration of any inbound or outbound call to or from the Entry phone. This mode is useful for turning 
on IR flood lights, for VoIP phones with cameras, etc.  

Doorbell Mode:  

When programmed for Doorbell Mode the relay will momentarily activate the relay for the 

preprogrammed relay activation time at the beginning of any outbound call from the Entry phone. This mode is useful 
for activating a door chime, etc. When activating door chimes, a 0.5 - 1 second relay activation time is recommended. 

Alarm Mode:  

When programmed in Alarm Mode the relay will activate continuously while the Entry phone is powered 

and registered to the SIP server. In the event the unit loses power and/or SIP registration the relay will turn off, which 
can be used to signal an alarm device. 

NOTE: 

Relay 2 should be set to “Alarm Mode” when mounting a 

PRX-3

 in close 

proximity of the 

K-1700-IP 

(when mounting the 

K-1700-IP

 and 

PRX-3

 to a 

PRX-3-MK-GNP

 gooseneck pedestal 

mounting plate) See Page 25.  

Ring Mode:  

When programmed for Ring Mode the relay will continuously activate while the ringing extension is called. 

This mode is useful for activating a Viking model 

SL-2

 strobe light, etc. 

Ring Flash Mode:  

When programmed for Ring Flash Mode the relay will momentarily turn on and off in a 400ms 

on/off cadence while the ringing extension is called. This mode is useful for activating a Viking 

LPL-1

 Remote Visual 

Indicator, etc.

17. Relay Mode 

20. Relay Activation Delay

A relay activation delay of 0.5 - 99 seconds can be programmed in the

 K-1700-IP

. A relay activation delay is useful in 

two door vestibule entrance applications. This allows you to program a delay time from when relay 1 (outside door) is 
activated to when relay 2 (inside door) is activated. The programmed delay time should be set to the average time it 
takes a person to walk from the outside door to the inside door. 

When a request for exit (REX) is activated, relay 2 will activate first, then after the programmed delay relay 1 will 
activate.  

Factory Setting:

 Disabled

The relay activation tone is a buzzing sound that is heard at the Entry phone when the door strike relay is activated. 
After the called party enters the correct relay activation command, the called party will hear 2 short confirmation beeps 
and the entry phone will output a buzzing sound (relay activation tone) while the door strike relay is activated. The tone 
(buzz) length will match the relay activation time up to a maximum of 5 seconds. The tone (buzz) can be programmed 
to three different volume settings 1 = Low, 2 = Medium, 3 = High or it can be disabled.  

Factory Setting:

 3

21. Relay Buzz Volume

Summary of Contents for K-1700-BN-IP

Page 1: ...one is connected to an apartment or business tenant a built in contact closure may be activated to control an electric gate or door strike Up to 1 000 keyless entry codes may be programmed providing t...

Page 2: ...to www vikingelectronics com and enter 944 in the search box 2 Click Application Note DOD 944 to open and download the PDF Scan the QR code below to open and download the Viking VoIP SIP System Compat...

Page 3: ...otocol is an Internet protocol standard that specifies a way for programs to manage the real time transmission of multimedia data over either unicast or multicast network services Server A computer or...

Page 4: ...c 12VDC 50mA max Brown Violet White Model PRX 1 Proximity Card Reader DOD 221 Model PRX 3 Medium Range Proximity Card Reader DOD 228 Model PRX 5 125KHz Mullion Mount Proximity Card Reader with Built I...

Page 5: ...stucco etc additional caulking may be required Earth Ground the Green Yellow wire using the provided wire nut Black Green White Black Green White To Wiegand Input on K 1700 IP Connect to Ground on En...

Page 6: ...Hub Available LAN with PoE class 2 6 5 watts Ethernet cable CAT5 minimum 1 MB minimum free hard drive space for installation 16MB of free physical RAM PC Programming Download and install the programmi...

Page 7: ...ng you to trouble shoot the failure B Connect Disconnect Open the Viking IP Programming software on the PC and the start screen shown below will appear Any Viking IP phones that are connected to the n...

Page 8: ...ettings tab Step 6 Select the appropriate value Static IP Settings or DHCP for Set Unit IP Address via Note changing the IP address will cause you to have to reconnect to the unit Enter the values for...

Page 9: ...cting an integer 1 to 4094 in ID for all packets Step 4 Set the Priority Code Point PCP value for all not SIP and RTP packets in the PCP for all packets input 0 is default priorities are from low to h...

Page 10: ...ash slowly for 3 seconds 2 beeps fast flash for 6 seconds 4 beeps then light steady indicating when to release button Step 4 You can now enter programming by following the steps in section B Step 1 Po...

Page 11: ...d factory set to ON 23 18 Speaker Volume 0 9 factory set to 3 24 18 Ring Volume 0 9 factory set to 5 25 18 Microphone Volume 0 9 0 Auto factory set to 5 26 18 In Band Audio Call Progress Enabled Disab...

Page 12: ...If Authentication ID is not required leave this field blank 2 SIP Server 1 Unit Name Up to a 31 character unit name can be assigned to the K 1700 IP Series Phone being programmed When registered to a...

Page 13: ...ociated with that Speed Dial Number If there is no answer or a busy signal is detected the K 1700 IP will then dial the Roll Over Phone Number The Primary Phone Number programmed in Index 0 is the num...

Page 14: ...ion which door gate was opened or closed entry code index and phone number index with tenant name The Event Log can store up to 4 095 events Events are stored in a first in first out format When the m...

Page 15: ...the ability to change any of the programming parameters Once entered any of the Remote Access Operation Commands can be used The code can be 1 6 digits in length and cannot contain a Q or Simply call...

Page 16: ...ection is set to outbound the 26 bit Wiegand connections become an output and can be connected to the card reader input on the access control system Unprogrammed keyless entry codes dialed by the user...

Page 17: ...second relay activation time is recommended Alarm Mode When programmed in Alarm Mode the relay will activate continuously while the Entry phone is powered and registered to the SIP server In the event...

Page 18: ...l truck Factory Setting 5 seconds 26 Microphone Volume Automatic Noise Cancelling Mode This feature selects switching time between talk and listen modes VOX switching time The Talk Listen Delay can be...

Page 19: ...SIP calls One option is to generate a loud ring sound through the speaker The K 1700 IP Phone can also auto answer a SIP call to transmit a page control the relay or listen to transmit audio from the...

Page 20: ...he gateway The three beeps can be muted by clicking on Mute Current Next Alarm The Status LED will continue to flash to assist troubleshooting The alarm beeps can also be permanently disabled See Perm...

Page 21: ...ically only used when Viking Technical Support has sent you updated firmware 43 Import Export The Import Export feature is useful for backing up all the K 1700 IP s programming or for importing progra...

Page 22: ...nd Toggle To use a keyless entry code the tenant simply dials followed by the entry code on the K 1700 IP s keypad These can be entered before or after pressing the call button After the one time use...

Page 23: ...nectors included Doorstrike Magnetic Lock 120V AC Door near Entry Phone 4 1 IN1 C IN2 IN3 C IN4 2 3 4 5 6 Relay 1 Output Contacts 5A 30VDC 250VAC max Connect to Doorstrike Mag Lock Gate Controller etc...

Page 24: ...x7 SS VE 6x7 PNL VE 6x7 PNL SS VE 5x10 VE 5x10 SS VE 5x10 PNL VE 5x10 PNL SS VE 3x5 VE 5x10 NR VE 5x10 NR SS The VE GNP gooseneck pedestals are designed to be used with the VE 5x5 VE 6x7 and VE 5x10 b...

Page 25: ...hich allow the reader to be conveniently adjusted and leveled To allow both indoor and outdoor operation the electronics are sealed in tamper resistant epoxy potting Concealing the mounting hardware t...

Page 26: ...the dispatcher the reason for the call Perform such tests in off peak hours such as early morning or late evenings PART 15 LIMITATIONS This equipment has been tested and found to comply with the limi...

Reviews: