LT0186 Issue 2.80
27 July 2012
Page 7 of 10
SPS Aux
Power
(Note 7)
+24V
0V
B-
B+
NO
COM
+ 24V
ALM -
0 V
Fault
4100ES
T-GEN 50
Master
(Note 2)
NC
EOL 10K
NAC3
3.5 T-GEN Wiring with Combined Alarm/Fault Supervision
F3200
ANCIL
Relay
+ 24V
+24V
0V
0V
0 V
NO
COM
ALM-
NC
SUP
C
NO
NC
S
Relay (Note 4)
+ 24V
0V
- /C
F3200 BELLS
ELD
(See Notes
5 & 6)
+24V
+24V
0V
0V
SIG
NO
COM
SIG
NO
COM
+ 24V
+ 24V
ALM-
0 V
0 V
Fault
Fault
F4000/MX4428
(Note 1)
F3200 Relay Bd
F4000 RRM
(Note 3)
ALM-
0V
+24V
0V
ALM-
T-GEN 50
Master
(Note 2)
T-GEN 50
Slave
(Note 2)
+24V
0V
ALM
Notes
1
. Cut “Ancil Sup link” on F4000, MX4428 Main Board.
2. Fit Lk7 in Relay position to enable Fault Relay. Turn SW4 off.
3. RRM must be inside FIP and wired to RESP IN.
4. Connect wire from NC term
inal of relay to “S” pin of supervision link. Do not fit Sup link at all.
5. 3k3 ELD for MX4428 Ancil Relay and RRM, F3200 Ancil Relay and F3200 Relay Bd. (2k5 (3k3//10k) for F3200 Bells.
6. Wire spare pole of AIE switch in series with ELD as per Section 3.1 Figure C if Fault indication required in Isolate.
7. The SPS Aux Power output is rated at 2A which is sufficient to power only 1 T-GEN 50 with a maximum speaker load
of 40W. The 4090-9118 Relay IAM can also be used to control and monitor the T-GEN 50. Please refer to LT0394 or
LT0350 for further details on using the T-GEN 50 with the 4100ES panel.
WARNING
If powering a
T-GEN50 via the
SPS Aux power
output the
speaker load
must not exceed
40W