background image

 

LT0186 Issue 2.80 

         27 July 2012 

Page 8 of 10 

3.6 Connecting T-GEN using the DEF- Output 
 

The following wiring is recommended for when the T-GEN is mounted in or adjacent to a fire panel that supports the 
DEF- signal. Using the DEF- output disables the T-GEN fault relay, and therefore the quiescent current is 17mA lower 
per T-GEN compared with using the fault relay.  But the DEF- line is not supervised for open circuit. Note that link Lk7 on 
the T-GEN(s) must be fitted in the DEF- position.  
 
The power supply for the T-GEN must be supplied from a monitored 24V supply. 

 

 

T-GEN

Master

+24V
+24V

0V
0V

ALM -

SIG
DEF-

T-GEN

Slave

+24V

+24V

0V

0V

SIG

DEF

-

+V

NO

C

BELLS

Resistors removed,

(Note 4)

EXT DEF -

Notes:

1.

Sigma 5, FP1600/OMEGA 64 Mk3 - EOL=10k.

Enable ALM- input monitoring on T-GEN - (MON
switch ON).

2.

Requires connection to a monitored 24V supply.

3.

FP1600/Omega64 Mk3 boards have three 7-

segment displays.

4.

Sigma 5 and FP1600/OMEGA Mk3 require resistors

to be removed. Remove R15, R16 for Sigma. Remove
R62, R63 for FP1600/OMEGA 64 Mk3.

0V

(see Note 2)

EOL

(see Note 1)

Sigma 5
FP1600 Mk3 (Note 3)
OMEGA 64 Mk3 (Note 3)

0V

 

 

 

3.7 Earth Connection 
 

The T-GEN must be connected to the cabinet EARTH using either the EARTH terminal on the T-GEN PCB (located 
beside the 100V Line Output)  or by using a metal standoff on the bottom left hand mounting hole (an M4 washer and 
nut are supplied).  
 
 

3.8 Power Connection 
 
WARNING:

   Each T-GEN 50 draws approximately 10A for 20 ms when first powered up. Any fuse between the T-GEN 

50 and its power supply must be a slow blow type rated 3A minimum (per T-GEN 50). Any switch contact 
used to supply power to a T-GEN 50 must also be rated at 10A minimum (per T-GEN 50).

 

 
 
The T-GEN 50 presents a significant capacitance (6600

μ

F) on its power terminals, hence the high inrush current.  This 

capacitance can also invalidate the battery connection tests (that lower the charger voltage to see if the battery is still 
present) on some power supplies (e.g. 1948 PSU) if the T-GEN 50 is the only device powered by the PSU.  In this case 
it may be necessary to add a power resistor to the PSU output to provide extra standing load.  For the 1948 24V PSU a 
820 ohm 5W resistor is typically required.  Note the 33mA this resistor draws needs to be included in any battery 
capacity calculations. 
 
 

Summary of Contents for T-GEN 50

Page 1: ...S These instructions apply to units with V1 70 software onwards Refer to LT0186 Issue 2 30 for instructions for earlier software versions A pre assembled Building Occupant Warning System BOWS that uti...

Page 2: ...lic address This is activated when the microphone s PTT button is pressed while the A I E switch is in the Auto or Evac position Public address overrides Alert and Evac tones A remote microphone can b...

Page 3: ...e Recorded Message OFF ON OFF Present ISO8201 keywords Msg 1 Msg1 Evacuate the building using the nearest fire exit OFF ON ON Don t Care TEST mode Msg2 Evacuate as directed x2 ON OFF OFF None Wail sou...

Page 4: ...the end of the line If wiring on two branches then two 100k ELDs are used one on each branch The capacitors must be bipolar and their value should be 1 5uF per Watt of their speaker s load see below S...

Page 5: ...esistor from the Isolate switch and blank off the word Isolate on the label ISOL 24V AUTO Yellow LED 2K7 0V EVAC ISOL AUTO ELD 0V EVAC COM A I E Switch Wiring Figure A Isolate Indication via Spare Swi...

Page 6: ...mega 64 Mk3 4100ES 4 Switch SW4 ON for the Master T GEN Fit LK7 in Relay Position for all T GENs 5 FP1600 Omega 64 Mk3 boards have three 7 segment displays 6 ELD value depends upon Input type not fitt...

Page 7: ...to enable Fault Relay Turn SW4 off 3 RRM must be inside FIP and wired to RESP IN 4 Connect wire from NC terminal of relay to S pin of supervision link Do not fit Sup link at all 5 3k3 ELD for MX4428 A...

Page 8: ...L see Note 1 Sigma 5 FP1600 Mk3 Note 3 OMEGA 64 Mk3 Note 3 0V 3 7 Earth Connection The T GEN must be connected to the cabinet EARTH using either the EARTH terminal on the T GEN PCB located beside the...

Page 9: ...upplied fitted to provide a complete functional unit A loom for power control and monitoring is factory fitted The loom is connectorised for direct use with MX1 The connector can be removed and the lo...

Page 10: ...T0186 Issue 2 80 27 July 2012 Page 10 of 10 Manufactured Tyco Fire Protection Products Distributed by 17 Mary Muller Drive PO Box 19 545 by Christchurch New Zealand Tel 64 3 389 5096 Fax 64 3 389 5938...

Reviews: