Document: LT0439 Vigilant
MX1-Au
Operator Manual
Issue 1.73
23 October 2018
Page 8-17
6.
To end Commissioning Mode, press
STOP
F4.
You cannot stop the test by pressing TESTS and then
attempting to Reset or Disable the point (241.27.10)
indicating that Commissioning Mode is active. You need to
repeat the steps above and press
STOP
F4.
The
MX1
operation can be restarted from the LCD. This function requires
Access Level 3. Refer to Section 7 to log on to level 3. From the base
display, press the RESET key.
Do not press the f.b.p. RESET control when the Alarm List is
showing unless the intent is to reset all alarms.
Select an item to reset | ZONE
| POINT
| SYSTEM
|
Fig 8-23 – Access Level 3 Reset Menu
Press
SYSTEM
F3 to see the following prompt;
Reset system?
Press OK to confirm
or CANCEL for no action
Fig 8-24 – System Reset Confirmation Screen
Press OK to restart the
MX1
panel as if power had been removed and
re-applied.
Resetting the System (Access Level 3)