Gasifying boilers VIGAS
VIGAS 18 DPA, VIGAS 26 DPA
4.1.3 Boiler switched on – burning mode
4.1.4 Boiler shutdown (automatic)
4.1.5 Boiler shutdown (manually)
4.2 Parametres setting for fuel - PELLETS
Mode of combustion, the boiler will get after successful ignition of the
pellets. Status is displayed by changing the "ON" → "520C". The burning
mode, the boiler is controlled by a "PID controller based on the
temperature of the boiler and flue temperatures. If the boiler temperature
exceeds the desired temperature by 1°C, output is 0% if the temperature
drops below 3°C desired temperature, the boiler is re-ignited. Current
output is displayed in percentage as a symbol.
"20%".
Inside boiler container is placed ultrasound sensor, which detects pellet
level. If pellets are above sensor level (container is full), this condition is
displayed by symbol „
“.
If pellets are below sensor level (container is half-empty), this condition is
displayed by symbol „
“. Simultaneously, information line shows
remaining time period for boiler to shutdown. This condition is displayed
by empty container symbol “
“ and sign „END“.
Pressing „ENTER“ display offers round button. Pressing button
⊳
boiler will shut down. After shutdown, the
blowing fan is switched on. During 60s period pellet burner is being cooled down. By pressing
round
button will disappear.
To change setting press
„ENTER“
for 2 seconds, in any boiler mode, by pressing button ▲. Parametres
setting depends on type of the boiler and its configuration.
By pressing buttons ▲ choose parameter to be changed and pressing
„ENTER“
figure starts flashing.
Using ▲ buttons select required figure and repeatedly press
„ENTER“
.
2sec.