VIET GARDEN FX Troubleshooting Manual Download Page 3

 

A Hunter Industries Company 

 

 

 

 

  

 

 

Checking Voltage at Outlet 

 

 

 

 

 

 

Checking Voltage at Transformer Lugs 

 

 

 

 

 

 

 

Checking Voltage at Fixture Splice 

 

 

2. LX - Checking Voltage Using Voltmeter 

Using a digital voltmeter allows you to take important voltage readings at the transformer, at 

each  fixture  and  at  the  receptacle  the  transformer will  be  plugged  into.  Dial  the  digital 

voltmeter to the 200 ~ setting for measuring AC voltage. 

 

Each  lug  should  read  no  more  than  +/

–  0.3  to 0.9  volts  of  rated 

output.   Both  the  LX-150  and  LX-300  models  have  a  12V,  13V, 

and  14V  lug inside  the  controller.   The  FX  MultiTap  Transformer 

allows  you  the  opportunity  to  utilize  the voltage  tap  that  will 

provide each circuit with the proper voltage.  For cable runs in the 

“distant zone” you would typically select the 13 or 14 volt tap. For 
cable runs in the “close zone,” you would typically install the cable 

run  into  the  12  volt  tap  depending  upon  the  wattage  load  and 

size of cable. 

 

This  tool  tells  you  whether  or  not  the  120  volt  receptacle  you 

are plugging  the  FX  Transformer  into  is  wired  properly.  Follow 

the tool manufacturers instruction manual to assure proper wiring 

on the receptacle you will be using. 

This  procedure  should  only  be  performed  by  a  licensed 

electrician.

 

electrician.

 

 

 

Insert voltmeter probes into each wire connector (Optimum 

reading between 10.5 and 11.5 VAC for incandescant fixtures 

and 10-15 VAC for LED fixtures). 

 

Summary of Contents for FX

Page 1: ...lem Lamps are burning out prematurely Cause Excessive voltage at lamp Solution Drop the affected cable run down to the next lower voltage tap or increase wattage load on that cable to drop voltage Also some lamps are rated for a very short life such as the 4414 300 hours Use halogen lamps Problem The closest lamp to the transformer is burning out prematurely Cause Excessive voltage at lamp Solutio...

Page 2: ... make a good connection to the lamp base Problem System is getting dimmer with age Cause Splices are corroding Solution As non waterproof splices corrode they create electrical resistance which reduces voltage Problem Photocell transformer is coming on too soon Cause Transformer is in dark location Solution In order to operate properly the photocell must have a good look at daylight Move to a brig...

Page 3: ...s you the opportunity to utilize the voltage tap that will provide each circuit with the proper voltage For cable runs in the distant zone you would typically select the 13 or 14 volt tap For cable runs in the close zone you would typically install the cable run into the 12 volt tap depending upon the wattage load and size of cable This tool tells you whether or not the 120 volt receptacle you are...

Page 4: ...he Electrical Panel to the receptacle is OK or not If it does not indicate two orange lights something is wrong with the wiring Consult an electrician 4 LX Testing Transformer Power The first test to perform will determine if power is passing through the Transformer to the low voltage taps Turn your volt meter on and place one of the probes on the lug labeled C and the other probe on the voltage t...

Page 5: ... original setting complete the reset procedure listed below 1 Hold down the GREY ENTER and DOWN button on the face pack 2 As you are holding the buttons down press the reset button on the back of the face pack 3 Release the reset button first and then release the buttons on the front A successful reset will result in 12 00 on the display You can now reprogram your LX face pack Kit Includes 26 of c...

Page 6: ... the top of the transformer This fuse does not protect the incoming voltage just the low voltage side of the transformer The LX buss fuse is located in the top wiring compartment of the LX lighting transformer Replace with a UL Listed 3AG with the following specifications 10 Amp 250V This procedure should only be performed by a licensed electrician Disconnect power from the primary and secondary U...

Page 7: ...e transformer is tested in the field 9 LX Replacement Lamp Not Working A common mistake made by many is to replace existing lamps with lamps of higher wattage than those originally installed Example If you have an FX system with a PX 600 watt transformer 25 fixtures illuminating the landscape and all of the original fixtures have 20 watt lamps in them for a total load on the transformer of 500 wat...

Reviews: