![Viessmann WAGO KNX/TP gateway Installation And Service Instructions For Contractors Download Page 9](http://html1.mh-extra.com/html/viessmann/wago-knx-tp-gateway/wago-knx-tp-gateway_installation-and-service-instructions-for-contractors_1017801009.webp)
9
Step
Responsibility
Page
1
Install the gateway and power supply unit.
Contractor
2
Establish the CAN bus connection to the control unit.
Contractor
3
Use a terminator.
Contractor
4
Establish the connection to the KNX.
IT expert/system integrator
5
Power supply
Electrician
6
Commission the gateway.
IT expert/system integrator
Installing the gateway and power supply unit
!
Please note
Incorrect ambient conditions and installation
locations may impair data transfer and cause
damage to the device.
The gateway, together with its components, con-
stitutes an open device with IP 20 protection rat-
ing. It may only be installed in enclosures, cabi-
nets or in electrical plant rooms.
Ambient conditions during operation
■
Permissible ambient temperature: 0 to 40 °C
■
Permissible relative humidity:
–
At 0 to 39 °C: Up to 95 %
–
At 40 °C: Up to 50 %
■
No direct sunlight
!
Please note
Operation by unauthorised persons may result
in damage to the device.
Access to the gateway must only be possible for
authorised specialists with a key or tool.
Requirements for the enclosure
Material
Sheet steel
Plastic
Min. dimensions
(width x height x depth)
200 x 200 x 120 mm
278 x 278 x 130 mm
Protective conductor
Connect the enclosure to the protec-
tive conductor.
Connect the top-hat rail to the protec-
tive conductor via a protective conduc-
tor terminal.
Flammability class
—
Min. flammability class V-1 according
to EN 62368-1 or EN 60950-1
Earthing
Enclosure and top-hat rail:
Depending on phase conductor
cross-section with min. 2.5 mm
2
Top-hat rail:
Depending on phase conductor cross-
section with min. 2.5 mm
2
IP rating
■
Installed at a height of up to 1.60 m: IP 20D
■
Installed at a height of 1.61 m or higher: IP 20B
Top-hat rail mounting
■
TS 35 to EN 50022
■
Length: Min. 190 mm
Installation sequence
Process overview
5853847
Installation
Summary of Contents for WAGO KNX/TP gateway
Page 25: ...25 Dismounting the KNX terminal 1 2 4 3 Fig 19 Dismounting the gateway cont 5853847 Service...
Page 26: ...26 Dismounting the CAN terminal 2 1 Fig 20 Dismounting the gateway cont 5853847 Service...
Page 27: ...27 Dismounting the controller 1 3 2 Fig 21 Dismounting the gateway cont 5853847 Service...
Page 28: ...28 1 2 Fig 22 Dismounting the power supply unit 5853847 Service...
Page 34: ...34 5853847...
Page 35: ...35 5853847...