19
The connection version must be selected subject to
the heating system and the required monitoring func-
tion. The recommended connection version is the
"power supply via the mains isolator".
Regulations
Connect the power supply and implement all safety
measures (e.g. RCD circuit) in accordance with
IEC 364, the connection requirements of your local
power supply utility, and VDE or national regulations.
Protect the power cable to the gateway power supply
unit with a maximum fuse rating of 16 A across all
poles.
Isolators for non-earthed conductors
■
Install an isolator in the power cable to provide
omnipolar separation from the mains for all active
conductors, corresponding to overvoltage cate-
gory III (3 mm) for complete isolation. This isolator
must be fitted in the permanent electrical installation
in line with installation requirements, e.g. mains iso-
lator or upstream circuit breaker.
■
We additionally recommend installing an AC/DC-
sensitive RCD (RCD class B
) for DC (fault)
currents that can occur with energy efficient equip-
ment.
Connecting cores in the power supply unit
3.
1.
2.
Fig. 14
Installation sequence
Power supply
(cont.)
5853847
Installation
Summary of Contents for WAGO KNX/TP gateway
Page 25: ...25 Dismounting the KNX terminal 1 2 4 3 Fig 19 Dismounting the gateway cont 5853847 Service...
Page 26: ...26 Dismounting the CAN terminal 2 1 Fig 20 Dismounting the gateway cont 5853847 Service...
Page 27: ...27 Dismounting the controller 1 3 2 Fig 21 Dismounting the gateway cont 5853847 Service...
Page 28: ...28 1 2 Fig 22 Dismounting the power supply unit 5853847 Service...
Page 34: ...34 5853847...
Page 35: ...35 5853847...