Installation sequence
Using the control panel
(cont.)
The following table describes the configuration parameters.
Type of parameter and symbol on display
Description/Comments
Heating type
Type of collector installed in heating circuit:
(Floor) – underfloor heating (20–55 °C)
(Radiator) – central heating (20–80 °C)
The parameter settings are determined by the range of the
heating circuit temperatures.
Maximum heating temperature
Maximum heating temperature in the circuit.
For example, if the installation requires a maximum
set temperature of 45 °C, it must be set accordingly.
Valve runtime
Time required for switching the valve by 90 degrees. Control
range from 60 to 480 seconds, standard setting: 120 seconds.
During the configuration process, the set value must be
balanced with the value of the valve drive.
Valve actuating time
Operating time of the valve in a control time of 30 seconds.
Control range of 2 to 15 seconds, standard setting: 5 seconds.
Pump operating mode
(Automatic pump mode) – the pump is only activated
when heating is active.
(Continuous pump mode) – the pump runs continuously;
used only during system commissioning.
Standard setting: Automatic mode.
Manual temperature
setting
Configuration of the heating medium in the circuit during
manual control of the circuit.
Identification number
Note: During system configuration, each appliance connected
to the bus (computer) must be assigned a unique identification
number.
Standard setting: 5
Press "Configuration" to exit the operating mode
.
The system enters standby mode.
Operating mode
To activate "Operating" mode, press button in
standby mode. Press buttons to call up the
parameter display, which contains the parameters
listed in the table below.
Type of parameter and symbol on display
Description
Temperature of the heating system
Heating circuit inlet temperature (after mixing valve)
Heating temperature setting
Current set flow temperature – display only.
If the heating circuit is inactive, the following symbols are
displayed: ---
The active display indicates the manual setting of
the heating medium temperature in the heating circuit.