Using the control panel
(cont.)
Installation sequence
Heating curve (only type VMN3):
The boiler control unit ensures that the correct
temperature is maintained in the central heating
installation depending on the outside temperature.
When there is a low outside temperature, the heat
demand inside the building is higher. On the other
hand, when there is a high outside temperature, it is
not necessary to maintain a high temperature inside
the installation. The correlation between the outside
temperature and the temperature of the heating
installation can be represented graphically with a
heating curve. The diagram below shows a summary
of the heating curves for a set room temperature of
22 °C. The corresponding heating curve must be
selected according to the building properties, climate
zone and type of heating installation.
If an offset of the heating curve is required, the
parameter [heating curve] must be changed. The
diagram below shows heating curve no. 12 with
an offset of -10 °C and 10 °C.
20,0
30,0
40,0
50,0
60,0
70,0
80,0
90,0
-20
-10
0
10
20
Tch [°C]
Tout [°C]
n=4
n=6
n=8
n=10
n=12
n=14
n=16
n=18
n=20
n=22
n=24
A
A
Heating curve no. (p = 0)
Tch [°C]
Tout [°C]
20,0
30,0
40,0
50,0
60,0
70,0
80,0
90,0
-20
-10
0
10
20
n=12, p=10
n=12, p=0
n=12, p=-10
A
A
p – heating curve offset