Installation on a Wall
36
Overview of System Installation
This installation method can be used for
any application type.
Panels can be stacked one above the
other or side by side.
Note:
Refer to page 43 for supply and return
piping configurations.
For this installation method the general
connection set with air-vented u-pipe
must be used. The collectors must be
installed so that the vacuum tubes are
slightly inclined upwards towards the
header. A slope of 1/4” per ft. is
recommended to eliminate air from
being trapped at the glass end of the
tube.
Maximum tube rotation is 25° to avoid
shading. This limits the absorber plate
angle of inclination range from 65° to
90°.