70
Application Rules & Formulas
Universal Hydronics Formula:
GPM=
BTUH
500 x ∆T
BTUH= GPM x 500 x ∆T
Quick Pipe Resistance Calculation:
1. Measure longest run of pipe
2. Add 50% for fittings
3. Multiply by .04
= A rough calculation on the feet of
head the pump needs to overcome
for that circuit.
Piping & Tubing Properties
Steel/Wrought Iron Pipe
Pex Tubing
Copper Tubing (Type L)
*Based on a velocity of 4fpm
*Based on 20°F ∆T
*Based on a velocity of 4fpm
*Based on 20°F ∆T
*Based on a velocity of 4fpm
*Based on 20°F ∆T
Size
Content/ft
(gal)
Max Flow Rate
1
(GPM)
Max Heat Carrying
Capability (BTUH)
2
1/2"
.016
4
40,000
3/4"
.028
7
70,000
1"
.045
12
120,000
1-1/4"
.078
20
200,000
1-1/2"
.106
28
280,000
2"
.174
44
440,000
Size
Content/ft
(gal)
Max Flow Rate
1
(GPM)
Max Heat Carrying
Capability (BTUH)
2
1/2"
.009
2.3
23,000
5/8"
.013
3.3
33,000
3/4"
.018
4.6
46,000
1"
.030
7.5
75,000
1-1/4"
.046
11.2
112,000
1-1/2"
.105
15.6
156,000
Size
Content/ft
(gal)
Max Flow Rate
1
(GPM)
Max Heat Carrying
Capability (BTUH)
2
3/8"
.007
2
20,000
1/2"
.012
3.2
32,000
3/4"
.025
6.5
65,000
1"
.043
10.9
109,000
1-1/4"
.065
16.3
163,000
1-1/2"
.092
22.9
229,000
2"
.161
39.6
396,000
Summary of Contents for Vitodens 200-W B2HA series
Page 1: ...Application Guide Vitodens 200 W B2HA B2HB Residential Boiler...
Page 2: ...II...
Page 4: ...IV...
Page 10: ...6...
Page 33: ...29 Vitodens 200 W Application 1 Application Code VD2X 1ZC1ZP 01 Notes Comments...
Page 39: ...35 Application 2 Operational Setup continued Notes Comments...
Page 47: ...43 Notes Comments Application 4 Operational Setup continued...
Page 55: ...51 Application 6 Operational Setup continued Notes Comments...
Page 59: ...55 Application 7 Operational Setup Instructions continued Notes Comments...
Page 77: ...73 Global presence local commitment...
Page 78: ......
Page 79: ......