Vitodens 200-W B2HA 88-150, 311- 530 Technical Data
5683 718 - 19
28
Boiler Temperature Sensor
The boiler temperature sensor is connected at the control
unit for weather-responsive operation and is built into the
boiler.
Max. ambient temp.
-
at operation:
32ºF to 266ºF (0ºC to 130ºC)
-
when storing
or transporting:
-4ºF to+158ºF (-20ºC to+70ºC)
Boiler Control
Design and Functions
(continued)
Outdoor Temperature Sensor
Sensor location:
-
North or northwest wall of building
-
6.6 to 8.2 ft. (2 to 2.5 m) above ground or in case
of a multi-storey building approximately halfway up
the second floor
Electrical connection:
-
2-wire cable, max. cable length 115 ft. (35 m) with
a wire size of min. AWG 16 copper
-
Cable to the outdoor sensor must not be laid near
line voltage wiring (120/240V)
DHW Tank Temperature Sensor
Supplied with:
-
Cable length approximately 13 ft. (3.75 m),
ready to plug in
-
All pipe connections are field supplied.
Specification:
Max. ambient temp.
-
at operation:
32ºF to 194ºF (0ºC to 90ºC)
-
when storing
or transporting:
- 4ºF to+158ºF (-20ºC to+70ºC)
Room Temperature Sensor
Separate room temperature sensor as supplement to
the Vitotrol and 300A; to be used if the 300A cannot
be installed inside the main living room or in a suitable
position where the unit can capture and adjust the
temperature.
Installation in the main living room on an internal wall
opposite radiators. Never install inside shelf units,
recesses, immediately by a door or heat source (e.g.
direct sunlight, fireplace, TV set, etc.).
Connect the room temperature sensor to the Vitotrol 300A.
Electrical connection:
-
2-wire cable with a wire size of min. AWG 18 copper
-
The cable length between the control unit, remote
control unit and room temperature sensor must not
exceed 98 ft. (30 m)
Max. ambient temp.
- at operation:
32ºF to 104ºF (0ºC to 40ºC)
- when storing
or transporting:
-4ºF to+149ºF (-20ºC to+65ºC)
Immersion Temperature Sensor
To capture the low loss temperature
Specification
Lead length fully wired: 12 ft. (3.75 m),
Permissable ambient temp.
- during operation:
32ºF to 194°F (0ºC to 90°C)
- during storage and
transport:
-4ºF to+158°F (-20ºC to+70°C)
Max. ambient temperature
during transport, storage
and operation: -40ºF to 194ºF (-40ºC to 90ºC)