Vitodens 200-W B2HA 88-150, 311- 530 Technical Data
5683 718 - 19
4
Technical Data
Technical Data
*A
For high altitude installations 5,000 - 10,000 ft. (1500 m - 3000 m), the input for model B2HA 88,100, 150,
311, 352, 530 will have an altitude de-ration of 14% for 5,000 ft. (1500 m) and 29% for 10,000 ft. (3000 m)
average of 2.8% / 1,000 ft. (305 m).
*
B
The input for model B2HA 112, 399 at 10,000 ft. (3000 m) will have an input de-rate of 13%.
*C
Net AHRI rating based on piping and pick-up allowance of 1.15.
*D
Tested to AHRI, BTS-2000 Testing Standard Method to Determine Efficiency of Commercial Heating Boilers.
*1
If the gas supply pressure exceeds the maximum gas supply pressure value, a separate gas pressure regulator
must be installed upstream of the heating system.
*2
See “Waterside Flow” starting on page 9 of this manual.
*3
Output based on 180ºF (82ºC), 80ºF (26ºC) system supply/return temperature.
Boiler Model No. B2HA
88, 311 *
A
100, 352 *
A
112, 399 *
B
150, 530 *
A
CSA input Natural Gas (NG)
CSA input Liquid Propane Gas (LPG)
CSA output
NG
*3
CSA output LPG
*3
MBH
(kW)
MBH
(kW)
MBH
(kW)
MBH
(kW)
71-311
(21-91)
104-311
(30-91)
67-294
(20-86)
98-294
(29-86)
71-352
(21-103)
104-352
(30-103)
67-333
(20-98)
98-333
(29-98)
113-399
(33-117)
113-399
(33-117)
103-375
(30-110)
103-375
(30-110)
113-530
(33-155)
113-530
(33-155)
103-495
(30-145)
103-495
(30-145)
DOE/AHRI Gross output
Net AHRI Rating
*C
MBH
(kW)
MBH
(kW)
292
(85)
254
(74)
329
(96)
286
(84)
371
(109)
323
(95)
490
(144)
426
(125)
Heat exchanger surface area
ft.
2
(m
2
)
28.88
(2.68)
28.88
(2.68)
36.78
(3.41)
36.78
(3.41)
Min. gas supply pressure
Natural gas
Liquid propane gas
“w.c.
“w.c.
4
10
4
10
4
10
4
10
Max. gas supply pressure
*1
Natural gas
Liquid propane gas
“w.c.
“w.c.
14
14
14
14
14
14
14
14
ANSI Z21,13/CSA 4.9
Thermal efficiency
%
94.5
94.5
93.9
93.5
AHRI, BTS-2000
*D
Combustion efficiency
Thermal efficiency
%
%
94.2
94.0
94.0
93.5
93.5
93.0
93.0
92.5
Weight
lbs
(kg)
194
(88)
194
(88)
298
(135)
298
(135)
Boiler water content
USG
(L)
3.4
(12.8)
3.4
(12.8)
4
(15)
4
(15)
Boiler max. flow rate
*2
GPM
(L/h)
25
(5700)
25
(5700)
38
(8600)
38
(8600)
Max. operating pressure
at 210ºF (99ºC)
psig
(bar)
60
(4)
60
(4)
80
(5.5)
80
(5.5)
Boiler water temperature
- Adjustable high limit (AHL) range
space heating (steady state)
DHW production
- Fixed high limit (FHL)
ºF
(ºC)
ºF
(ºC)
ºF
(ºC)
68 to 185
(20 to 85)
185
(85)
210
(99)
68 to 185
(20 to 85)
185
(85)
210
(99)
68 to 185
(20 to 85)
185
(85)
210
(99)
68 to 185
(20 to 85)
185
(85)
210
(99)
Boiler connections
Boiler heating supply and return
Pressure relief valve
Drain valve
Boiler supply/return for
indirect-fired DHW storage tank
(field supplied)
Gas valve connection
NPTM
NPTF
(male
thread)
NPT
NPTF
1
b
in.
¾
in.
¾
in.
1
b
in.
1 in.
1
b
in.
¾
in.
¾
in.
1
b
in.
1 in.
2 in.
¾
in.
¾
in.
2 in.
1 in.
2 in.
¾
in.
¾
in.
2 in.
1 in.