42
sK
Internal H1 extension
■
Central fault message
■
DHW circulation pump
■
External heating circuit pump
■
Circulation pump for cylinder heating
dG
Gas train
gD
Flue gas damper (accessories)
aVG
KM-BUS subscriber (accessories)
■
Vitotrol 200-A or 300-A remote control
■
Mixer extension kit
■
Solar control module, type SM1
■
EA1 extension
■
Wireless base station
■
AM1 extension
a¢Ö
Fan motor
A1
Main PCB
A3
Coding card
A4
ON/OFF switch
A5
Programming unit
A6
Connection adaptor with Optolink
A7
Connection adaptor
A8
LON communication module (accessories)
A9
Reset
A10 Connection extension
A11 Output extension
Specification
Rated heating output range
P
cond
: TF/TR = 50/30
kW
16 - 80 32 - 120 32 - 160 48 - 200 48 - 240 64 - 280
64 - 318
P
n
: TF/TR = 80/60
kW
15 - 74 29 - 110 29 - 146 44 - 184 44 - 220 58 - 258
58 - 291
Rated heat input
kW
76
113
151
189
226
264
300
Product ID
CE-0085CR0391
Permiss. operating tempera-
ture
°C
95
Permiss. flow temperature
(= safety temperature)
°C
110
Max. permiss. operating pres-
sure
bar
6
MPa
0.6
Min. permiss. operating pres-
sure
*1
bar
1
MPa
0.1
Test pressure
bar
7.8
MPa
0.78
Boiler body dimensions
Length
mm
665
770
770
890
890
1004
1004
Width
mm
680
Height
mm
1650
Total dimensions
incl. casing,
boiler flow and return; excl. boil-
er flue connection
Length
mm
739
862
862
967
967
1085
1085
Width
mm
750
Height
mm
1650
Foundation dimensions
Length
mm
750
850
850
1000
1000
1100
1100
Width
mm
800
800
800
800
800
800
800
Height
mm
100
100
100
100
100
100
100
*1
The minimum operating pressure is essential for safe operation. A minimum pressure switch can be used to ensure this is
met (1 per system for multi boiler systems)
Connection and wiring diagram
(cont.)
5839818